Бесперебойник liebert upstation gxt инструкция

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

P

P

OWER

ROTECTION

R

UPStation GXT™

700-3000 VA

120V

U

M

SER

ANUAL

English / Español

loading

Related Manuals for Liebert UPStation GXT

Summary of Contents for Liebert UPStation GXT

  • Page 1
    OWER ROTECTION UPStation GXT™ 700-3000 VA 120V ANUAL English / Español…
  • Page 2: Important Safety Instructions

    IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dangerous voltages, even when the AC cord is disconnected from the electrical outlet. Refer all servicing to qualified service personnel. SAVE THESE INSTRUCTIONS.

  • Page 3: Introduction And System Description

    The UPStation GXT™ protects equipment from these disturbances. The UPStation GXT™ comes in nominal power ratings of 700, 1000, 1500, 2000, or 3000 VA. Complete specifications appear near the end of this section. The UPStation GXT™ is a compact, “on-line” UPS.

  • Page 4: Major Components

    UPS, and the amount of distortion reflected on the utility is reduced. This results in cleaner power being available to other devices in the building not being protected by the UPStation GXT™. INVERTER In normal operation, the inverter utilizes the DC output of the power factor correction circuit and “inverts”…

  • Page 5
    Typical Battery Discharge Curves. DYNAMIC BYPASS The UPStation GXT™ provides an alternate path for utility power to the connected load, in the unlikely event of a UPS malfunction. Should the UPS have an overload, over temperature, or UPS failure condition, the UPS automatically transfers the connected load to bypass.
  • Page 6: General Installation

    GENERAL INSTALLATION MINI-TOWER/TOWER UPS INSTALLATIONS Unpack the UPS carefully noting the packing method. Retain the box and packing material for possible future shipment. CAUTION: The UPS is heavy (see specifications). Take proper precautions when lifting or moving it. Visually inspect the UPS for freight damage. Report damage to the carrier and your dealer.

  • Page 7: Rack-Mount Conversion Diagrams

    4 and 5. Remove display template to change the orientation of the display. You may also rotate the “Liebert UPStation GXT™” plate located at left of display area. NOTE: UPS unit MUST be supported by a shelf, brackets or slide rails on each side.

  • Page 8: Battery Cabinet Installation Diagram

    12. Plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with the National And Local Codes. Use a 15 amp rated device for the 1000, or 1500 VA units, a 20 amp device for the 2000 VA unit, and a 30 amp device for the 3000 VA unit.

  • Page 9
    FERRITE BEAD INSTALLATION Serial Communications Attach the smaller enclosed ferrite bead clamp to the communication cable as shown in the drawing using the following directions: Open the ferrite bead. Place the communication cable inside the ferrite bead grove. Position the ferrite beads as close as possible to the end of the cable that connects to the DB9 connector of the UPS.
  • Page 10: Upstation Gxt Overview

    UPSTATION GXT™ Fault Indicator On/Alarm Silence/ Bypass Indicator Manual Battery Test Button UPS On Indicator Battery Indicator Off/ Bypass Button AC Input Indicator Load/Battery Level Indicators 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inlet 4- Intellislot ™ Communications Port…

  • Page 11: Controls And Indicators

    To silence alarms, press this button for at least one half second while alarm conditions are present. After the alarm is silenced, the UPStation GXT™ will reactivate the alarm system to alert of additional problems. Note: The low battery and bypass reminder alarms cannot be silenced.

  • Page 12: Operation

    UPS On Indicator (Green) The UPS On indicator is illuminated when the UPS inverter is operating and supplying power to your connected loads. Battery Indicator (Amber) The Battery indicator is illuminated when the UPS is operating from the battery system. AC Input Indicator (Green) The AC Input indicator is illuminated when utility power is available and within the input specification.

  • Page 13
    BATTERY MODE OPERATION Battery mode occurs in event of an extreme input voltage condition or complete utility failure. The battery system supplies power through the DC-DC converter to the inverter to generate power for the connected load. During battery mode an alarm sounds every 10 seconds. This will change to 2 beeps every 5 seconds when battery runs low (approximately 2 minutes remaining).
  • Page 14: Communications Interface Port

    Monitoring of the UPS via a computer system is easily made with a Liebert SiteNet® 1 shutdown kit (sold separately).

  • Page 15: Ups Intelligent Communications

    24 hours every four to six months to ensure full recharge of the batteries. The UPStation GXT™ UPS is designed to allow the user to safely replace the batteries. Read the safety cautions before proceeding. Contact your dealer to…

  • Page 16: Battery Replacement Procedures

    Do not dispose of batteries in a fire, the batteries may explode. If you feel unqualified to replace the batteries, do not open the battery door. Call Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.

  • Page 17
    Replace battery door by inserting the three metal tabs into the slots and pushing it toward the front of the UPS. Replace and tighten the five screws to lock the battery door closed. Carefully stand the UPS upright. Connect the UPS to the utility supply socket and turn on the UPS by pressing the on button.
  • Page 18: Rack/Tower Battery Replacement

    RACK / TOWER BATTERY REPLACEMENT Top cover screws Flange screws Rear View Aerial View w/top cover removed Two front Front bezel (cover) rubber feet Small battery door Large battery door Screw hidden by small battery door Battery connector Large battery door…

  • Page 19
    UPSTATION GXT BATTERY RUN TIMES (Discharge times are at 25° C ambient) Internal Battery (minutes) Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT 100% Internal Battery + 1 External Battery Cabinet (minutes) Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT…
  • Page 20: Audible Alarm Conditions

    FUSE REPLACEMENT PROCEDURES CAUTION: Before changing the input fuse, turn off the UPS, and unplug the supply lead from the AC input supply and from the UPS. Replace the fuse with the same type and rating. 700 / 1000 VA 1500 VA Insert flat blade screwdriver into slot…

  • Page 21: Troubleshooting

    5 minutes while battery charger is not operational. If a problem persists consult your dealer, or contact Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.

  • Page 22: Troubleshooting Guide

    TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION UPS fails to start UPS is short circuited or Ensure UPS is off. Disconnect all loads when on button is overloaded and ensure nothing is lodged in output pressed sockets. Ensure loads are not defective or shorted internally.

  • Page 23: Specifications

    SPECIFICATIONS MODEL NUMBER GXT700MT-120 GXT1000MT-120 MODEL RATING 700 / 490 1000 / 700 VA/W DIMENSIONS: in (mm) Unit 6.4 x 15.6 x 8.9 6.4 x 15.6 x 8.9 W x D x H (162 x 430 x 225) (162 x 430 x 225) Shipping 11.0 x 19.75 x 14.25 11.0 x 19.75 x 14.25…

  • Page 24
    SPECIFICATIONS MODEL NUMBER GXT1000RT-120 GXT1000RTE-120 MODEL RATING 1000 / 700 1000 / 700 VA/W DIMENSIONS: in (mm) Unit 7.0 x 19.3 x 16.9 7.0 x 19.3 x 16.9 W x D x H (177 x 522 x 430) (177 x 522 x 430) Shipping 13.38 x 26.0 x 22.25 13.38 x 26.0 x 22.25…
  • Page 25
    SPECIFICATIONS MODEL NUMBER GXT1500RT-120 GXT2000RT-120 GXT3000RT-120 MODEL RATING 1500 / 1050 2000 / 1400 3000 / 2100 VA/W DIMENSIONS: in (mm) Unit 7.0 x 19.3 x 16.9 7.0 x 19.3 x 16.9 7.0 x 19.3 x 16.9 W x D x H (177 x 522 x 430) (177 x 522 x 430) (177 x 522 x 430)
  • Page 26: Battery Cabinet Specifications

    BATTERY CABINET SPECIFICATIONS MODEL NUMBER GXT36VBATT GXT48VBATT GXT96VBATT Used w/ UPS Model 1000RT 1500RT 2000RT/3000RT DIMENSIONS: in (mm) Unit 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 W x D x H (7.0 x 19.3 x 16. 9) (7.0 x 19.3 x 16.

  • Page 27: Limited Warranty

    (4) to six (6) months when not in use. If the UPS fails to conform with the above warranty within the two year warranty period, Liebert will repair or replace the UPS, at Liebert’s option. Repairs or replacements are warranted for the remainder of the original warranty period.

  • Page 28: Technical Support

    614-841-5471 The Company Behind The Products With more than 500,000 installations around the While every precaution globe, Liebert is the world leader in computer been taken to ensure accuracy protection systems. Since its founding in 1965, completeness this Liebert has developed a complete range of support…

Краткое содержание страницы № 1

POWER PROTECTION
™
UPStation GXT 6kVA Maintenance Bypass
USER MANUAL
Transformerless
with Configurable
Output Distribution

Краткое содержание страницы № 2
Краткое содержание страницы № 3

TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Краткое содержание страницы № 4
Краткое содержание страницы № 5

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE CAUTION ! To reduce the risks of fire, connect INSTRUCTIONS only to a circuit provided with maximum branch circuit This manual contains important instructions that overcurrent protection of 40A in should be closely followed during installation and accordance with applicable maintenance of this UPStation GXT 6kVA national and local electrical codes. Maintenance Bypass. Install the bypass equipment in a clean This product is designed for commerci

Краткое содержание страницы № 6

GLOSSARY OF SYMBOLS Risk of electrical shock Indicates Warning or Caution followed by important instructions Requests the user to consult the manual i Equipment grounding conductor On Off 2

Краткое содержание страницы № 7

GENERAL DESCRIPTION Congratulations on your purchase of Liebert’s Features UPStation GXT 6 kVA Maintenance Bypass. As • Supports up to 30A loads with every Liebert product, we stand behind our • Compact design quality. If you have any questions concerning this • Highly configurable Maintenance Bypass, please feel free to contact • Multiple power path indicators your local sales representative, or call the • High-speed, break-before-make transfer appropriate Technical Support number liste

Краткое содержание страницы № 8

Maintenance Bypass component layout Bypass availability UPS input power indicator (amber) present (amber) UPS input switch Bypass (SW2) switch (SW1) Output UPS output breaker availability (CB1) indicator (green) Hardwire 12 3 4 output terminal block Configurable (TB4) Output Distribution GND3 GND1 12 3 1122 2 3 12 3 4 GND2 TOP VIEW Utility UPS UPS input input output TB1 TB2 TB3 INSIDE VIEW— RECEPTACLE PLATES AND END PLATE REMOVED 4

Краткое содержание страницы № 9

MAJOR COMPONENTS The following is a general description of each 20 Amp Options component and its functions. Please review this 5-20R2 (T-Slot) section carefully, as it will give you a better L5-20R understanding as to how the UPStation GXT 6 kVA Maintenance Bypass operates. L6-20R-208 L6-20R-240 BYPASS SWITCH L14-20R-240 The Bypass Switch allows easy and rapid transfer 20A, 120V, 1 Pole Breaker for 1/2″ & 3/4″ conduit of connected loads between the UPS and bypass 20A, 208V, 2 Pole Breaker

Краткое содержание страницы № 10

CABLE INSTALLATION WIRING PREPARATION POWER CABLE INSTALLATION Refer to the chart below when selecting cables: ! CAUTION Power Cable and Protection Ratings Please read this section 208V 240V thoroughly before attempting to Max Input Current 30 A 30 A install wiring to this unit. Input Protection 40 A 40 A Be sure that the unit is not Max Output Current 30 A 30 A connected to any AC mains power source or UPS before installing 2 Max: 16 mm (6 AWG) any wiring to this unit. This should 2 Ter

Краткое содержание страницы № 11

Connecting Maintenance Bypass to UPStation GXT6000T — 208 208 VAC Output TB4 12 3 4 GND3 MAINTENANCE BYPASS NOTE When using the Maintenance Bypass with an UPStation GXT6000T-208, a jumper GND1 (included with the accessory kit) must be connected to the TB3 (UPS output) terminal block on the Maintenance Bypass between TB3-1 and TB3-2, as shown. Utility UPS input UPS output GND2 TB1 TB2 TB3 13 2 132 2 134 Utility L1 input L2 NOTE GMB12 models are supplied with an attached input power L1

Краткое содержание страницы № 12

Connecting Maintenance Bypass to UPStation GXT6000T — 208X 120V 208V 120V Output TB4 12 3 4 GND3 MAINTENANCE BYPASS GND1 Utility UPS input UPSoutput GND2 TB1 TB2 TB3 13 2 132 132 4 Utility L2 input L1 N GEC NOTE L1 L2 N L1 L2 L2A GMB12 models are supplied +- with an attached input power Input Output Ext. battery cord complete with L14-30 plug. GXT6000T — 208X 8

Краткое содержание страницы № 13

Connecting Maintenance Bypass to UPStation GXT6000T — 240X 120V 240V 120V Output TB4 12 3 4 GND3 MAINTENANCE BYPASS GND1 Utility UPS input UPSoutput GND2 TB1 TB2 TB3 13 2 132 132 4 Utility L2 input L1 N GEC NOTE L1 L2 N L1 L2 +- GMB12 models are supplied with an attached input power Input Output Ext. battery cord complete with L14-30 plug. GXT6000T — 240X 9

Краткое содержание страницы № 14

WALL-MOUNT DIAGRAM DIAGRAM FOR ATTACHING UNIT TO WALL Use the following diagram, which shows the location and measurements of factory-cut mounting slots, when preparing to attach the GXT Maintenance Bypass to a wall. Liebert recommends using 1/4-20 mounting screws. Rubber pads are supplied for placing the Maintenance Bypass on the floor. 178mm 7.00″ 514mm 20.25″ C L 10

Краткое содержание страницы № 15

HARDWIRE OUTPUT OPTION This product is intended to be installed by a 6. Connect the remaining wires in accordance qualified electrician only. with the wiring diagram (located inside the base enclosure). 1. COMPLETELY REMOVE ALL POWER FROM THE FRAME. If the Maintenance Bypass is NOTE connected to the UPS, disconnect external When wiring 120 V loads, LINE must be battery supply. alternated between TB4-1 and TB4-3 to 2. Remove the end cover plate to access the balance the 120V load. Connec

Краткое содержание страницы № 16

OPERATING PROCEDURES START-UP AND INITIALIZATION TRANSFERRING SYSTEM FROM UPS TO MAINTENANCE BYPASS Follow these steps in order to start up the GXT 6kVA UPS while connected to the OPERATION Maintenance Bypass. 1. On UPS verify that Bypass LED is lit, if not, press UPS OFF/Bypass button for at least ON MAINTENANCE BYPASS one second. 1. Set the Maintenance Bypass switch (SW1) to 2. On Maintenance Bypass verify that the UPS position. Bypass lamp is illuminated. 2. Close (position I) UPS I

Краткое содержание страницы № 17

SPECIFICATIONS Typical Transfer Time < 6 milliseconds (to or from maintenance bypass) Input Voltage Nominal 208VAC or 240VAC Total Current 30A max. Operating Ambient Temperature 0° to +40° C Storage Ambient Temperature -20° to +60° C Dimensions, W x D x H, in (mm) 8.2 x 21.0 x 6.2 (209 x 534 x 158) Chassis Weight (no receptacles) 10 lbs. Distribution Module Weights (each) 2 lbs. Connections to UPS Hardwire Terminal Blocks Humidity 0 to 95%, non-condensing Agency/Standards UL 1778, c-UL 13

Краткое содержание страницы № 18
Краткое содержание страницы № 19
Краткое содержание страницы № 20

POWER PROTECTION UPStation GXT 6kVA Maintenance Bypass USER MANUAL Technical Support/Service The Company Behind the Products Web Site With over a million installations around the globe, www.liebert.com Liebert is the world leader in computer protection Monitoring systems. Since its founding in 1965, Liebert has 800-222-5877 developed a complete range of support and monitoring@liebert.com protection systems for sensitive electronics: Outside the US: 614-841-6755 • Environmental systems—close-con

WARNING: Do not attempt to service this product yourself except to replace

the battery. Opening or removing the cover may expose you to dangerous

voltages, even when the AC cord is disconnected from the electrical outlet.

1.

SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT

INSTRUCTIONS THAT SHOULD BE FOLLOWED DURING INSTALLATION

AND MAINTENANCE OF THE UNINTERRUPTIBLE POWER SYSTEM

(UPS) AND BATTERIES.

CONSERVER CES INSTRUCTIONS. CETTE NOTICE CONTIENT DES

INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ.

2.

This product is not intended for use with life support and other U.S.

FDA designated «critical» devices. See Limited Warranty.

3.

CAUTION: A BATTERY PRESENTS A RISK OF ELECTRICAL SHOCK OR

BURN FROM HIGH SHORT CIRCUIT CURRENT. OBSERVE PROPER

PRECAUTIONS.

ATTENTION:

ÉLECTRIQUE OU DE BRÛLURE PAR TRANSFERT D’ÉNERGIE. SUIVRE

LES PRÉCAUTIONS QUI S’IMPOSENT.

4.

WHEN REPLACING THE BATTERIES, USE THE SAME NUMBER AND

TYPE OF BATTERIES.

REQUIRED.

REQUIREMENTS.

POUR LE REMPLACEMENT, UTILISER LE MÉME NOMBRE ET TYPE DE

BATTERIES. L’ÉLIMINATION DES BATTERIES EST RÉGLE-MENTÉE.

CONSULTER LES CODES LOCAUX À CER EFFET.

5.

Read all safety and operating instructions before operating the UPS. Adhere

to all warnings on the unit and in this manual. Follow all operating and user

instructions.

6.

Turn the UPS off and unplug it before cleaning. Use only a soft cloth, never

liquid or aerosol cleaners.

7.

The UPS is designed for data processing equipment.

appliances, such as hair dryers, heaters, vacuum cleaners, or electric drills,

into the UPS output receptacles.

8.

WARNING: Do not modify input cable. Consult your dealer if connector

does not match the utility receptacle. The UPS must be grounded at all

times while in use. Turn the UPS off before unplugging it, or the safety

ground will be removed. Operate UPS only from a properly grounded 120

VAC outlet (2 wire plus ground).

9.

The UPS is equipped with a grounded NEMA 5-15, 5-20, or L5-30 input

power plug (depending upon model). Do not defeat the safety purpose of

this plug. If unable to fully insert the plug into the wall outlet, contact a

qualified electrician for assistance.

Refer all servicing to qualified service personnel.

UNE BATTERIE PRESENT UN RESQUE DE CHOC

REFER TO YOUR LOCAL CODES FOR DISPOSAL

PROPER DISPOSAL OF BATTERIES IS

2

Do not plug

Понравилась статья? Поделить с друзьями:

Новое и полезное:

  • Бесперебойник eaton 9130 инструкция на русском
  • Бесперебойник back ups 650 инструкция на русском
  • Бесперебойник apc back ups es 550 инструкция
  • Бесперебойник apc back ups 650 инструкция
  • Бесперебойник apc 750 smart ups инструкция по применению

  • 0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии