Series Temperature Controller
Instruction Sheet
Thank you very much for choosing Delta DTD series temperature controller. Please read this instruction sheet
before using your DTD to ensure proper operation. Keep this instruction sheet handy for quick reference.
Warning
DANGER! CAUTION! ELECTRIC SHOCK! When the power is on, DO NOT touch the AC terminals in case
an electric shock may occur. Make sure the power is disconnected when you check the input power.
DTD is an OPEN-TYPE device. If it will cause serious injury to workers or damage on other equipments
when used in a dangerous environment, please make sure it is installed in an automatic safety protection
device.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, Max. width 7.2mm). Please be
sure to tighten them properly and make sure the wire is connected to the correct terminal.
2. Prevent dust or metallic debris from falling into the device and cause malfunctions. DO NOT modify or uninstall DTD
series without being permitted. DO NOT use empty terminals.
3. Keep away from high-voltage and high-frequency environment during installation in case of interference. Prevent using
the device in premises which contain:
(a) dust or corrosive gas; (b) high humidity and high radiation; (c) shock and vibration
4. The power has to be switched off when wiring or changing temperature sensor.
5. Make sure to use compensation wire which matches the thermocouple when extending or connecting the thermocouple
wire.
6. Use wires with resistance when extending or connecting the platinum resistance sensor.
7. Keep the wire as short as possible when wiring a sensor to the temperature controller. Separate the power cable and load
wire in order to prevent interference and induced noise.
8. DTD is an open-type device. Make sure to install it in an enclosure which prevents dust and humidity in case of an
electric shock.
9. Make sure the power cables and signal device are installed correctly before switching on the power; otherwise serious
damage may occur.
10. DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur.
11. Please wait for one minute after the power is switched off to allow the capacitor to discharge and DO NOT touch the
internal wiring within this period. Use dry cloth to clean the device. DO NOT use acid or alkaline liquid to clean the
device.
Display, LED &
Pushbuttons
Present value/function
PV
display (red 7-segment LED)
Series name
Set value
SV
(green 7-segment LED)
1 2 3 4
Flashes when PID
AT
auto-tuning (green LED)
Panel size
(W × H)
OUT
On when output (green LED)
5
ALM
On when alarm (red LED)
Selecting modes
Optional
completing setup
Displaying functions
Left-shifting the digit
Up key
Specifications
Power input
AC100 ~ 240V 50/60Hz
Input power range
85% ~ 110%, rated voltage
Power consumption
6VA Max.
Display
7-segment LED; PV in red, SV in green
Input temperature
Thermocouple: K, J, T, E, N, R, S, B, U, L,
sensor
Txk
Analog input
Current: 0 ~ 20mA, 4 ~ 20mA
For temperature input: K2, J2, T2, Pt100-2, JPt100 and Cu50 can display to 0.1
Display scale
degree; others display in 1degree as a unit.
Control method
PID, PID programmable control, On/Off, manual output
Relay output: AC 250V, 5A, SPST
Control output type
Voltage pulse output: DC 14V, Max. output current 40mA
Sampling cycle
0.4 second (including analog input signal and sensor input signal)
2
Vibration resistance
10 ~ 55Hz 10m/s
3 axes 10mins
2
Shock resistance
Max. 300m/ s
3 axes 6 directions, 3 times each
Ambient temperature
0°C ~ 50°C
Storage temperature
-20°C ~ +65°C
Operation altitude
Less than 2,000m
Ambient humidity
35% ~ 85% RH (non-condensing)
Operation Instructions on Keys
Switching Modes
DTD is in operation mode (the first level) when the power is switched on. Press
regulation mode (the second level), or press
setting mode (the third level). Press
Switching Functions
Press
in each mode to select functions. Press
function when press
Modifying Settings
Select the item to be set up by using
digit of the SV will flash. If you press
of the digit or select parameters. When setting up the value, press
Examples
1. DTD from STOP to RUN: Press
will flash. Press
2. Modifying SV from 80 to 120: Press
once and 8 will flash. Next, press
the 100s digit 0 will flash. Press
save the setting.
Input Settings
Setting up Input Type
When DTD is switched on, SV will display the type of the input sensor (default K1 = thermocouple type). Press
for more than 3 seconds in the operation mode and PV will display the parameter
sensor types (see the table below) and press
screen of operation mode.
If the setting is current input, a 249Ω resistor has to be connected to the current input terminals.
Ordering Information
Setting up Input Unit
In the operation mode, press
once to select the unit. If the input type is thermocouple or platinum resistance, the PV will display
DTD
0
case, press
1 2 3 4 5
. In this case, you can set up the position of the decimal point for the analog input. Press
and save the setting.
DTD: Delta D series temperature
controller
4848: 1/16 DIN W48 × H48 mm
Setting up Input Range
4896: 1/8 DIN W48 × H96 mm
After you complete setting up the input unit, press
R: Relay output SPST (250VAC, 5A)
V: Voltage pulse output 14V +10% ~
to set the maximum value for the temperature range. Press
-20% (Max. 40mA)
and
to set the minimum value for the temperature range. The default range is the maximum range
0: None
measurable (see the table below) and both parameters cannot exceed this range. When PV exceeds the range, PV
will flash and DTD will stop its operation.
When in analog input, the temperature range also refers to the maximum and minimum input values. For example,
when 4 ~20mA input is adopted,
12mA and the unit is 0.01mA.
Adjusting Input Inaccuracy
When there is the need to correct the measured input PV, press
regulation mode. Press
Platinum resistance: Pt100, JPt100
Modifying this parameter will make the PV = measured value + input compensation value. Press
Copper resistance: Cu50
display the parameter of input gain
Voltage: 0 ~ 5V, 0 ~ 10V, 0 ~ 70mV
compensation value. Press
this parameter to enhance the stability of the PV; however, this will result in slow reaction to the input value.
Input Sensor Type
4 ~ 20mA input
0 ~ 20mA input
0V ~ 10V input
0V ~ 5V input
0 ~ 70mV input
Cu50 type
Pt100 type 2
once to switch to the
for more than 3 seconds in operation mode to switch to the initial
once in other screens to return to the operation mode.
once to switch to the next function, or return to the first
in the last function.
and
. Next, press
. If the item to be set up is a value, the last
to select parameters, the SV will flash. Press
to left shift to the digit to be modified.
once and select parameter
. SV will display
to save the setting and
will stop flashing.
and display 0080 (the last digit in right hand side 0 will flash). Press
4 times and «2» in the display 0020 will flash. Press
once and «1» in the display 0120 will flash. Press
to complete and save the setting. The screen will return to the
for more than 3 seconds and PV will display the parameter
to select the temperature unit (°C or °F). If the input type is an analog input, the PV will display
once to display the parameter
again to display the parameter
= 2,000,
= 400. That is to say, PV = 1,200 refers to the input is
once in the operation mode to enter the
repeatedly until the parameter of input compensation value
and make PV = measured value × (1 + input gain/1,000) + input
again and display the parameter of software filter
Display
Temperature Range
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
o
o
-50
C ~ 150
C (-90.0
o
o
-99.9
C ~ 600.0
C (-99.9
Input Sensor Type
Pt100 type 1
JPt100 type
Thermocouple TXK type
Thermocouple U type
Thermocouple L type
Thermocouple B type
Thermocouple S type
Thermocouple R type
Thermocouple N type
Thermocouple E type
to increase the value
Thermocouple T type 2
Thermocouple T type 1
Thermocouple J type 2
Thermocouple J type 1
. Press
and
Thermocouple K type 2
Thermocouple K type 1
once and
to complete and
Control Settings
Setting up Control Mode
In the operation mode, press
for more than 3 seconds and PV will display the parameter
for 4 times to display the parameter
to select PID control
, PID programmable control
and display the parameter
for selecting the control method. You can select heading (default)
. Press
to select the
cooling
. Press
to return to the operation mode.
Setting up RUN and STOP
In the operation mode, press
and display parameter
STOP
. Press
to complete the setting and the output will be disabled.
. Press
. In this
Setting up On/Off Control Parameters
Press
in the operation mode. If DTD is in On/Off heating mode, the PV will display
to complete
mode, the PV will display
. Modify these parameters to set up the hysteresis of On/Off. The default setting is
0 (without hysteresis). When the output reaches SV, the control output will be disabled. When the input is bigger
(cooling) or smaller (heating) than the SV and hysteresis, the control output will be enabled. When the On/Off
hysteresis is not 0, the control output will be like the diagrams below.
. Use
and
, and use
SV
OFF
OFF
ON
ON/OFF Control for Heating
Setting up PID Parameters
When in PID control mode, you have to first decide the On/Off cycle time for the control output, i.e. the control cycle.
Press
in the operation mode and PV will display
appears.
heating control cycle
or cooling control cycle
again to
the control system. In principle, the faster the reaction, the shorter the cycle and more accurate the control. A short
control cycle indicates that there will be more times of On/Off. If you adopt relay output, the short cycle will shorten
the life span of the relay. Therefore, it is recommended that you adopt voltage output in the PID control mode. The
(default = 2). Increase
default setting of the control cycle is 20 seconds.
Parameters P, I and D can be set up manually or auto-tuned by DTD. Follow the steps below for the auto-tuning.
Press
in the operation mode and PV will display the parameter
parameter to
and DTD will perform an auto-tuning. The AT indicator will flash and after the setup is
completed, the AT indicator will be off. The PID parameters will be written in automatically and saved.
To set up the parameters manually, enter the regulation mode and select the parameter
to display the parameter of proportion band
o
o
F ~ 302.0
F)
diagrams in the next page.
o
o
F ~ 999.9
F)
Display
Temperature Range
o
o
o
o
-200
C ~ 600
C (-360
F ~ 1,112
F)
o
o
o
o
-20.0
C ~ 400.0
C (-36.0
F ~ 752.0
F)
o
o
o
o
-200
C ~ 800
C (-360
F ~ 1,472
F)
o
o
o
o
-200
C ~ 500
C (-360
F ~ 932
F)
o
o
o
o
-200
C ~ 850
C (-360
F ~ 1,562
F)
o
o
o
o
100
C ~ 1,800
C (180
F ~ 3,272
F)
o
o
o
o
0
C ~ 1,700
C (0
F ~ 3,092
F)
o
o
o
o
0
C ~ 1,700
C (0
F ~ 3,092
F)
o
o
o
o
-200
C ~ 1,300
C (-360
F ~ 2,372
F)
o
o
o
o
0
C ~ 600
C (0
F ~ 1,112
F)
o
o
o
o
-99.9
C ~ 400.0
C (-99.9
F ~ 752.0
F)
o
o
o
o
-200
C ~ 400
C (-360
F ~ 752
F)
o
o
o
o
-99.9
C ~ 999.9
C (-99.9
F ~ 999.9
F)
o
o
o
o
-200
C ~ 1,200
C (-360
F ~ 2,192
F)
o
o
o
o
-99.9
C ~ 999.9
C (-99.9
F ~ 999.9
F)
o
o
o
o
-200
C ~ 1,300
C (-360
F ~ 2,372
F)
. Press
. The default setting of this parameter is «On/Off control»
. Use
or manual control
. Press
again
or
. The default is RUN
. Use
to select
; if in On/Off cooling
Hysteresis
Hysteresis
HtS
CtS
SV
ON
ON
OFF
ON/OFF Control for Cooling
. Press
5 times to display the parameters of
. Set up the cycle depending on the reaction speed of
. In RUN state
, set the
. Press
once
, indicating the range where P control is enabled. See the
Содержание
- Инструкция и руководство для Delta Electronics DTD на русском
- industrialautomation Регулятор температуры серии DTD Руковод.
- Регулятор температуры DTD. Руководство по эксплуатации.
- Регулятор температуры DTD. Руководство по эксплуатации.
- Delta Electronics DTD4848R0
- Инструкции и файлы
- Delta Electronics DTD4848V0
- Инструкции и файлы
- Delta Electronics DTK4848R01
- Инструкции и файлы
- Температурные контроллеры Delta. Сброс на заводские настройки.
- Температурные контроллеры DTA и DTB
- Температурные контроллеры DTD
- Температурные контроллеры DTC
- См. также:
Инструкция и руководство для
Delta Electronics DTD на русском
13 страниц подробных инструкций и пользовательских руководств по эксплуатации
Delta Products DTB Series Temperature Controllers for PID Controls & How to Navigate
Delta Electronics Corporate Video 2019
Распайка серверного блока Delta Electronics DPS-2500BB
Energy Storage and Fast-charging at 150 kW with Delta Electronics
Delta Electronics EMEA Partner Event 2019 (full version)
Delta DTB 4848LV, Delta temperature controller in Hindi
Delta Electronics Thailand Profile
Delta Electronics DPS-475CB A 475W Power Supply
industrialautomation Регулятор температуры серии DTD Руковод.
Датчики Delta Electronics
Регулятор температуры серии DTD
Руководство по эксплуатации
Перед началом использования регулятора температуры DTD, далее по тексту, –
прибора, обязательно прочтите данное руководство по эксплуатации
Внимание! Опасность поражения электрическим током!
Не прикасайтесь к клеммам питания.
Не вскрывайте прибор, не убедившись в отсутствии на клеммах напряжения питания.
Данный прибор является устройством открытого исполнения, т.е. не имеет
защиты от попадания твердых тел и проникновения влаги (IP00). Убедитесь в
том, что требования к применению оборудования в данном производстве не
допускают возможности возникновения человеческих травм и серьезного
материального ущерба при использовании прибора.
Требуется использование имеющихся соединений без применения пайки (винтовое
соединение типа М3, максимальная ширина шайбы 7.2 мм или меньше) с контролем
Не допускайте попадания внутрь прибора пыли и металлических изделий. Это может
привести к повреждению прибора.
Не пытайтесь разбирать прибор. Не прилагайте недопустимых внешних воздействий к
корпусу и лицевой панели. Это может привести к отказу в работе прибора.
Не подключайте провода к терминалам функции «No».
Убедитесь, что все провода подключены в соответствии с полярностью клемм.
Не устанавливайте и не используйте прибор в местах с присутствием следующих
газы или жидкости, способные вызвать коррозию;
высокий уровень влажности;
высокий уровень радиации;
наличие вибраций, возможность присутствия ударов;
высокие значения напряжений, частот.
При подключении и замене термодатчика необходимо убедится в отсутствии
напряжения питания на клеммах прибора.
При подключении проводов термопары убедитесь в наличии термокомпенсационного
провода, требующегося для большинства типов термопар.
При подключении платинового термометра сопротивления необходимо использовать
наиболее короткие (по возможности) длины проводов и максимально удалять провода
питания от сигнальных проводов термометра сопротивления во избежание влияния
наводок и помех на полезный сигнал.
Корпус прибора не обеспечивает защиту от попадания твердых тел и проникновения
влаги (IP00). В связи с этим он должен быть установлен в месте, защищенном от
воздействия высоких температур, влажности, капель воды, пыли, коррозионно-
опасных материалов, электрических разрядов и вибраций.
Перед включением прибора убедитесь, что все соединения выполнены правильно, не
перепутаны силовые и сигнальные провода, в противном случае возможно серьезное
ООО «НПО «СТОИК ЛТД», 107392 Москва ул.Просторная 7, (495) 661-24-61, http://www.stoikltd.ru
Регулятор температуры DTD. Руководство по эксплуатации.
Регулятор температуры DTD. Руководство по эксплуатации.
После отключения питания нельзя прикасаться к внутренним цепям прибора в
течение одной минуты – до полной разрядки внутренних конденсаторов. Иначе
возможно поражением электрическим разрядом.
При очистке не используйте кислото- или щелочесодержащих жидкостей.
Используйте сухую чистую ветошь.
Наименование отображаемых функций
дисплей – отображение переменной процесса или
дисплей – отображение уставки, параметров чтения
переменной, регулирующего параметра или установка
светодиод – мигает в режиме работы
светодиод – индикация состояния управляющего
светодиод — индикация режима тревоги.
Включается при срабатывании тревоги Alarm.
функциональная клавиша. При нажатии выбирается требуемый режим
Клавиша режима. При нажатии выбираются устанавливаемые параметры для
каждого режима отображения.
Клавиша «вверх». Служит для увеличения изменяемого значения параметра в
Регулятор температуры Delta серии D
размер лицевой панели
(ширина х высота)
тип управляющего выхода
: релейный выход однополюсный
нормально-открытый контакт — 250 В
переменного тока, 5 А;
: импульсный выход по напряжению – 14В
20% (Макс. ток 40 мА);
функция связи отсутствует
240 В переменного тока, 50/60Гц
Рабочий диапазон напряжений 85%-110% от номинального
сегментные светодиодные индикаторы
переменная процесса (PV) – красный цвет, значение
уставки (SV) – зеленый цвет.
ООО «НПО «СТОИК ЛТД», 107392 Москва ул.Просторная 7, (495) 661-24-61, http://www.stoikltd.ru
Регулятор температуры DTD. Руководство по эксплуатации.
Регулятор температуры DTD. Руководство по эксплуатации.
Тип используемых датчиков
Термопары: K, J, T, E, N, R, S, B, U, L, Txk
Платиновые термосопротивления: тип Pt100, JPt100,
Cu50
Токовый: 0-20мА, 4-20мА
Напряжения: 0-5В, 0-10В, 0-70мВ.
двухпозиционный метод управления
релейный выход однополюсный нормально-
открытый контакт для серии — 250 В переменного
: импульсный выход по напряжению – 14В +10%
20% (Макс. ток нагрузки 40 мА);
для температурного входа K2, J2, T2, Pt100-2,
Источник
Delta Electronics DTD4848R0
Категория: | Промышленная Техника |
Группа: | Температурный Контроллер |
Устройство: | Delta Electronics DTD4848R0 |
Инструкции и файлы
Файл | Страниц | Формат | Размер | Действие | |||||||||||||||||||||||||||||||
Чтобы ознакомиться с инструкцией выберите файл в списке, который вы хотите скачать, нажмите на кнопку «Скачать» и вы перейдете на страницу, где необходимо будет ввести код с картинки. При правильном ответе на месте картинки появится кнопка для получения файла. Если в поле с файлом есть кнопка «Просмотр», это значит, что можно просмотреть инструкцию онлайн, без необходимости скачивать ее на компьютер. В случае если материал по вашему не полный или нужна дополнительная информация по этому устройству, например драйвер, дополнительные файлы например, прошивка или микропрограмма, то вы можете задать вопрос модераторм и участникам нашего сообщества, которые постараются оперативно отреагировать на ваш вопрос. Также вы можете просмотривать инструкции на своем устройстве Android Источник Delta Electronics DTD4848V0
Инструкции и файлы
|
Регулятор температуры DTD. Руководство по эксплуатации.
2
12.
После отключения питания нельзя прикасаться к внутренним цепям прибора в
течение одной минуты – до полной разрядки внутренних конденсаторов. Иначе
возможно поражением электрическим разрядом.
13.
При очистке не используйте кислото- или щелочесодержащих жидкостей.
Используйте сухую чистую ветошь.
Наименование отображаемых функций
PV
дисплей – отображение переменной процесса или
тип параметра;
SV
дисплей – отображение уставки, параметров чтения
переменной, регулирующего параметра или установка
значения параметра.
AT
светодиод – мигает в режиме работы
«Автонастройка» (Autotuning).
OUT
светодиод – индикация состояния управляющего
выхода.
ALM
светодиод — индикация режима тревоги.
Включается при срабатывании тревоги Alarm.
–
функциональная клавиша. При нажатии выбирается требуемый режим
отображения параметров.
–
Клавиша режима. При нажатии выбираются устанавливаемые параметры для
каждого режима отображения.
–
Клавиша «вверх». Служит для увеличения изменяемого значения параметра в
поле SV.
Расшифровка обозначения
DTA —
1_2_3_4_5_
0
Серия
Регулятор температуры Delta серии D
1_2_3_4 –
размер лицевой панели
(ширина х высота)
4848: 48х48 мм;
4896: 48х96 мм;
5 –
тип управляющего выхода
R
: релейный выход однополюсный
нормально-открытый контакт — 250 В
: импульсный выход по напряжению – 14В
+10% ~ —
20% (Макс. ток 40 мА);
0 —
опция
0 –
функция связи отсутствует
Технические характеристики
Напряжение питания
100-
240 В переменного тока, 50/60Гц
Рабочий диапазон напряжений 85%-110% от номинального
Потребляемая мощность
Максимально 6ВА
Метод индикации
7-
сегментные светодиодные индикаторы
переменная процесса (PV) – красный цвет, значение
уставки (SV) – зеленый цвет.