Digital controller with off cycle defrost
XR20C
CONTENTS
1.
GENERAL WARNING___________________________________________ 1
2.
GENERAL DESCRIPTION _______________________________________ 1
3.
CONTROLLING LOADS _________________________________________ 1
4.
FRONT PANEL COMMANDS_____________________________________ 1
5.
TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP) ___ 1
6.
MAIN FUNCTIONS _____________________________________________ 1
7.
Parameters ________________________________________________ 2
8.
Digital Input________________________________________________ 2
9.
11. HOW TO USE THE HOT KEY ____________________________________ 3
14. CONNECTIONS _______________________________________________ 3
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
•
This manual is part of the product and should be kept near the instrument for
easy and quick reference.
•
The instrument shall not be used for purposes different from those described
hereunder. It cannot be used as a safety device.
•
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
•
Check the supply voltage is correct before connecting the instrument.
•
Do not expose to water or moisture: use the controller only within the operating
limits avoiding sudden temperature changes with high atmospheric humidity to
prevent formation of condensation
•
Warning: disconnect all electrical connections before any kind of maintenance.
•
Fit the probe where it is not accessible by the End User. The instrument must
not be opened.
•
In case of failure or faulty operation send the instrument back to the distributor
or to «Dixell s.r.l.» (see address) with a detailed description of the fault.
•
Consider the maximum current which can be applied to each relay (see
Technical Data).
•
Ensure that the wires for probes, loads and the power supply are separated
and far enough from each other, without crossing or intertwining.
•
In case of applications in industrial environments, the use of mains filters (our
mod. FT1) in parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XR20C, format 32 x 74 mm, is a digital termostat with off cycle defrost
designed for refrigeration applications at normal temperature. It provides a relay
output to drive the compressor and a PTC or NTC probe input. A internal timer
manages the off cycle defrost. The instrument is fully configurable through special
parameters that can be easily programmed through the keyboard.
3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according to the temperature measured by the
thermostat probe with a positive differential from the set point: if the temperature
increases and reaches set point plus differential the compressor is started and then
turned off when the temperature reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are
timed through parameters «COn» and «COF».
3.2 DEFROST
Defrost is performed through a simple stop of the compressor. Parameter «IdF»
controls the interval between defrost cycles, while its length is controlled by
parameter «MdF».
4. FRONT PANEL COMMANDS
SET: To display target set point; in programming mode it selects a parameter or
confirm an operation.
(DEF) To start a manual defrost
(UP): To see the last temperature alarm happened; in programming mode it
& &
browses the parameter codes or increases the displayed value.
(DOWN) To see the last temperature alarm happened; in programming mode it
browses the parameter codes or decreases the displayed value.
KEY COMBINATIONS:
& &
+
To lock & unlock the keyboard.
& &
SET +
To enter in programming mode.
SET +
To return to the room temperature display.
4.1 USE OF LEDS
Each LED function is described in the following table.
LED MODE
ON
Compressor enabled
Flashing -Programming Phase (flashing with
— Anti-short cycle delay enabled
ON
Defrost enabled
Flashing — Programming Phase (flashing with
ON
An temperature alarm happened
5. TEMPERATURE ALARM AND ITS DURATION
RECORDING (HACCP)
XR20C signals and records temperature alarms, together with their duration and
max value reached. See drawing:
Ex. High temperature alarm
Tem pera ture
M ax
Tem p erature
A Lu
H igh te mp. alarm
S et
A LL
Low te mp . alarm
5.1 HOW TO SEE THE ALARM DURATION AND MAX (MIN)
TEMPERATURE
If the alarm LED is on, an alarm has taken place.
To see the kind of alarm, the max (min) reached temperature and alarm duration do
as follows:
1.
Push the Up or Down key.
2.
On the display the following message is shown::
«HAL» for high temperature alarm («LAL» fot the minimum allarm), followed by
the Maximum (minimum) temperature.
Then the «tiM» (tiMe) message is displayed, followed by the «Duration» in
h.mm.
3.
Then the instrument displays the temperature once again.
NOTE1: if an alarm is still occurring the «tim» shows the partial duration.
NOTE2: the alarm is recorded when the temperature come back to normal values
5.2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS
STILL OCCURRING
1.
Hold the SET key pressed for more than 3s, while the recorded alarm is
displayed. (the rSt message will be displayed)
2.
To confirm the operation, the «rSt» message starts blinking and the normal
temperature will be displayed.
6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
1.
Push and immediately release the SET key: the display will
show the Set point value;
2.
Push and immediately release the SET key or wait for 5 seconds to display the
probe value again.
6.2 HOW TO CHANGE THE SETPOINT
1.
Push the SET key for more than 2 seconds to change the Set point value;
2.
The value of the set point will be displayed and the
3.
To change the Set value push the
4.
To memorise the new set point value push the SET key again or wait 10s.
6.3 HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 seconds and a manual
defrost will start.
FUNCTION
)
)
Safe food zone
Tim e
Alarm duration
LED starts blinking;
& &
or
arrows within 10s.
Модель XR20C контроллер с простейшим циклом оттайки, сконструированный для применения в холодильной области при нормальной температуре. Прибор обеспечен реле выхода, для того, чтобы управлять компрессором, и входом, для датчиков РТС или NТС. Внутренний таймер организует простейший цикл оттайки. Прибор полностью программируется через параметры при помощи клавиатуры.
Документация
Корпус | передняя панель 32×74 мм; глубина 60 мм |
Монтаж | панель монтируется в отверстие 71×29 мм |
Защита передней панели | IP65 |
Соединения | Провода клеммного блока Ј 2,5 мм2, с винтовым креплением |
Энерго потребление | 12Vac/dc, ±10% на вы(бор 230, 110, ± 10%, 50/60Hz) |
Энерго поглащение | 3VA max |
Дисплей | 3 цифры, красные LED, 14,2 мм высота |
Входы | 1 PTC или NTC датчики |
Реле выхода | компрессор SPDT реле 8(3) A, 250Vac или SPST реле 20(8)A; 250Vac |
Блок памяти | данные сохраняются даже при отсутсвии питания (EEPROM) |
Рабочая температура | 0 — 60 °C |
Температура хранения | -30 — 85 °C |
Относительная влажность | 20 — 85% (отсутствие какого-либо конденсата) |
Диапазон измерения и регуляции | PTC датчик: -50ч150°C (-58ч302°F) NTC датчик: -40ч110°C (-58ч230°F) |
Разрешающая способность | 0,1 °C или 1°C или 1 °F (на выбор) |
Точность (окруж.темпер. 25°C) | ±0,7 °C ±1 цифра |
Разрешающая способность
— Hy Дифференциал: (0,1 ч 25,5°C / 1ч255 °F) Дифференциал вмешательства для контр.точки.Компрессор ВКЛ, при Set Point Плюс Differential (Hy). Компрессор ВЫКЛ, при достижении температурой значения контр.точки.
— LS Миним. Контр.точка: (- 50°CчSET / — 58°FчSET): Устанавливает минимальное возможное значение для контр.точки.
— US Максим. Контр.точка: (SETч 150°C / SETч302°F): Устанавливает максимальное возможное значение для контр.точки.
— Ot Калибровка термостата: (-12.0ч12.0°C; -120ч120°F) позволяет установить возможно-допустимое отклонение от реального значения датчика.
— OdS Задержка действий при старте: (0ч255min) Эта функция срабатывает только при первоначальном старте прибора и предотвращает какие-либо действия на период времени, установленном в параметрах.
— AC Противоцикличная задержка: (0ч50 min) минимальный интервал между остановкой и последующим запуском компрессора.
— CCt Время работы компрессора во время полного цикла: (0.0ч24.0h; res. 10min) Позволяет установить продолжительность полного цикла:компрессор работает без перерыва в течении CCt времени. Можно использовать, например, когда камера заполнена новым продуктом.
— COn Время работы компрессора при неисправном датчике: (0ч255 min) время, в течении которого компрессор работает при неисправном датчике термостата. При COn=0 компрессор всегда ВЫКЛ.
— COF Компрессор ВЫКЛ при неисправном датчике: (0ч255 min) время, в течении которого компрессор всегда ВЫКЛ в случае неисправного датчика термостата. При COF=0 компрессор всегда работает. CH Вид действия: CL = охлаждение; Ht = нагрев.
Дисплей
— CF Единица измерения температуры: °C = Цельсий; °F = Фаренгейт.
— rES Разрешающая способность (для °C): (in = 1°C; dE = 0.1 °C) позволяет появление на дисплее десятичной точки.
Оттайка
— IdF Интервал между циклами оттайки: (1ч120h) Определяет период времени между началом двух циклов оттайки.
— MdF Продолжительность оттайки: (0ч255min) Устанавливает продолжительность цикла .
— dFd Показ значения температуры во время оттайки: (rt = реальная температура; it = температура во время начала оттайки; SEt = контрольная точка; dEF = “dEF” метка)
— dAd MAX задержка показа данных после оттайки: (0ч255min). Устанавливает max время между концом оттайки и показом реального значения комнатной температуры.
Сигналы тревоги
— ALC Конфигурация температурного сигнала тревоги: (Ab; rE) Ab= абсолютная температура: аварийное значение температуры задается ALL или ALU. rE = аварийное значение температуры относительно контр.точки. Температурный
сигнал тревоги срабатывает, когда температура превышает значения “SET+ALU” или “SET-ALL” .
— ALU Сигнал тревоги по MAX температуре: (ALLч150°C; ALL ч302°F) при достижении температурой этого значения срабатывает сигнал тревоги, после времени задержки “ALd” .
— ALL Сигнал тревоги по Min температуре : (-50.0°C ч ALU; -58°F ч ALU) при достижении температурой этого значения срабатывает сигнал тревоги, после времени задержки “ALd” .
— ALd Время задержки температурного сигнала тревоги: (0ч255 min) временной интервал между моментом опредиления
аварийной ситуации и срабатыванием сигнала тревоги.
— dAO Исключение температурного сигнала тревоги при запуске: (от 0.0 мин до 23.5ч) временной интервал между моментом опредиления аварийной ситуации после включения прибора и срабатыванием сигнала.
Цифровой вход (только для моделей с цифровым входом)
— i1P Полярность цифрового входа: oP: цифровой вход срабатывает по открытому контакту; CL: цифровой вход срабатывает по закрытому контакту.
— i1F Конфигурация цифрового входа: EAL = внешний сигнал тревоги: “EA” появляется следующее сообщение; bAL = серийный сигнал тревоги: “CA” ” появляется следующее сообщение и выход отключен; dEF = активизирование цикла оттайки; AUS = не выбирайте.
— did Задержка сигнала тревоги цифрового входа: (0ё255 min) временной интервал между моментом опредиления аварийной ситуации (i1F= EAL or i1F = bAL) и срабатыванием сигнала тревоги.
Другое
— PbC Выбор датчика: (Ptc=PTC датчик; ntc=NTC датчик). Это позволяет выбрать тип датчика.
,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
6.4 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing the Set and
DOWN key for 3s (
2. Select the required parameter.
3. Press the «SET» key to display its value (now only the
LED is blinking).
4. Use «UP» or «DOWN» to change its value.
5. Press «SET» to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the
time-out to expire.
6.5 THE HIDDEN MENU
The hidden menu Includes all the parameters of the instrument.
6.5.1 HOW TO ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing the Set +
for 3s (LED 1 and
2. When a parameter is displayed keep pressed the Set+
for more than 7s. The Pr2 label will be displayed
immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
3. Select the required parameter.
4. Press the «SET» key to display its value (Now only the
‘ ‘
5. Use
or
to change its value.
6. Press «SET» to store the new value and move to the following parameter.
‘ ‘
To exit: Press SET +
or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the
time-out to expire.
6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE
FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into «THE
FIRST LEVEL» (user level) by pressing «SET +
In HIDDEN MENU when a parameter is present in First Level the decimal point is
on.
6.6 HOW TO LOCK THE KEYBOARD
1.
Keep pressed for more than 3 s the
2.
The «POF» message will be displayed and the keyboard will be locked. At this
point it will be possible only to see the set point or the MAX o Min temperature
stored
3.
If a key is pressed more than 3s the «POF» message will be displayed.
6.7 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the
will be displayed.
6.8 THE CONTINUOUS CYCLE
When defrost is not in progress, it can be activated by holding
‘ ‘
the «
» key pressed for about 3 seconds.
The compressor operates in continuous mode for the time set through the «CCt»
parameter. The cycle can be terminated before the end of the set time using the
‘ ‘
same activation key «
» for 3 seconds.
NOTE: the parameters preceded by dots are in the Hidden Menu.
REGULATION
Hy Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point.
Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is
when the temperature reaches the set point.
•
LS
Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum
acceptable value for the set point.
•
US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum
acceptable value for set point.
Ot Thermostat probe calibration: (-12.0÷12.0°C;
-120÷120°F) allows to adjust possible offset of the thermostat probe.
•
OdS Outputs activation delay at start up: (0÷255min) This function is
enabled at the initial start up of the instrument and inhibits any output activation
for the period of time set in the parameter.
AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressor
stop and the following restart.
•
CCt Compressor ON time during continuous cycle: (0.0÷24.0h; res. 10min)
Allows to set the length of the continuous cycle: compressor stays on without
interruption for the CCt time. Can be used, for instance, when the room is filled
with new products.
•
COn Compressor ON time with faulty probe: (0÷255 min) time during which
the compressor is active in case of faulty thermostat probe. With COn=0
compressor is always OFF.
•
COF Compressor OFF time with faulty probe: (0÷255 min) time during which
the compressor is OFF in case of faulty thermostat probe. With COF=0
compressor is always active.
CH Type of action: CL = cooling; Ht = heating.
and
start blinking).
start blinking).
LED is blinking).
«.
‘ ‘
and
keys.
‘ ‘
and
keys, till the «Pon» message
DISPLAY
•
CF Temperature measurement unit:
°C=Celsius; °F=Fahrenheit. WARNING: When the measurement unit is
changed the SET point and the values of the parameters Hy, LS, US, Ot, ALU
and ALL have to be checked and modified if necessary).
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.
DEFROST
IdF Interval between defrost cycles: (0÷120h) Determines the time interval
between the beginning of two defrost cycles.
MdF (Maximum) length for defrost: (0÷255min) When P2P = n, (not evaporator
probe: timed defrost) it sets the defrost duration, when P2P = y (defrost end
based on temperature) it sets the maximum length for defrost.
•
dFd Temperature displayed during defrost: (rt = real temperature; it =
temperature at defrost start; SEt = set point; dEF = «dEF» label)
•
dAd MAX display delay after defrost: (0÷255min). Sets the maximum time
between the end of defrost and the restarting of the real room temperature
display.
key
ALARMS
•
ALC Temperature alarms configuration: (Ab; rE)
Ab= absolute temperature: alarm temperature is given by the ALL or ALU
values. rE = temperature alarms are referred to the set point. Temperature
alarm is enabled when the temperature exceeds the «SET+ALU» or «SET-ALL»
values.
ALU
MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this
temperature is reached the alarm is enabled, after the «ALd» delay time.
ALL Minimum temperature alarm: (-50.0 ÷ SET°C;
-58÷230°F when this temperature is reached the alarm is enabled, after the
«ALd» delay time.
•
ALd
Temperature alarm delay: (0÷255 min) time interval between the
detection of an alarm condition and alarm signalling.
•
dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time
interval between the detection of the temperature alarm condition after
instrument power on and alarm signalling.
DIGITAL INPUT
i1P Digital input polarity: oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
i1F Digital input configuration:
EAL = external alarm: «EA» message is displayed; bAL = serious alarm «CA»
message is displayed. PAL = pressure switch alarm, «CA» message is
displayed; dor = door switch function; dEF = activation of a defrost cycle; LHt
=not enabled; Htr = kind of action inversion (cooling – heating).
did: (0÷255 min)
with i1F= EAL or i1F = bAL digital input alarm delay: delay between the
detection of the external alarm condition and its signalling.
with i1F= dor: door open signalling delay
with i1F = PAL: time for pressure switch function: time interval to calculate
the number of the pressure switch activation.
nPS Pressure switch number: (0
switch, during the «did» interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the did time is reached, switch off and on the
instrument to restart normal regulation.
•
odc
Compressor status when open door: no, Fan = normal; CPr, F_C =
Compressor OFF
OTHER
PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC
= PBC probe, ntC = NTC probe.
•
rEL
Software release for internal use.
•
Ptb
Parameter table code: readable only.
8. DIGITAL INPUT
The free contact digital input is programmable in five different configurations by the
«i1F» parameter.
8.1 DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the
«odc» parameter:
no, Fan = normal (any change);
CPr, F_C = Compressor OFF;
Since the door is opened, after the delay time set through parameter «did», the door
alarm is enabled, the display shows the message «dA» and the regulation restarts.
The alarm stops as soon as the external digital input is disabled again. With the
door open, the high and low temperature alarms are disabled.
8.2 GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for «did» time delay before
signalling the «EAL» alarm message. The outputs status don’t change. The alarm
stops just after the digital input is de-activated.
8.3 SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit will wait for «did» delay before signalling
the «CA» alarm message. The relay outputs are switched OFF. The alarm will stop
as soon as the digital input is de-activated.
8.4 PRESSURE SWITCH (i1F = PAL)
If during the interval time set by «did» parameter, the pressure switch has reached
the number of activation of the «nPS» parameter, the «CA» pressure alarm message
will be displayed. The compressor and the regulation are stopped. When the digital
input is ON the compressor is always OFF.
÷
15) Number of activation of the pressure
Manual, Installing And Operating Instructions for dixell XR20C Controller, Thermostat (5 pages)
Specifications:949/949324-xr20c.pdf file (08 Mar 2023) |
Accompanying Data:
dixell XR20C Controller, Thermostat PDF Installing And Operating Instructions (Updated: Wednesday 8th of March 2023 11:24:08 PM)
Rating: 4.8 (rated by 47 users)
Compatible devices: XWA11V, iCHILL IC205D EVO, WING XW60L, XW60LS, xc440c, Ichill 260L_D DUO, XM440K, XR01-02CX.
Recommended Documentation:
Text Version of Manual, Installing And Operating Instructions
(Ocr-Read Summary of Contents of some pages of the dixell XR20C Document (Main Content), UPD: 08 March 2023)
-
1, ,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV Digital controller with off cycle defrost XR20C CONTENTS 1. GENERAL WARNING___________________________________________ 1 2. GENERAL DESCRIPTION _______________________________________ 1 3. CONTROLLING LOADS ________________________________________…
-
2, ,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV 6.4 HOW TO CHANGE A PARAMETER VALUE To change the parameter’s value operate as follows: 1. Enter the Programming mode by pressing the Set and DOWN key for 3s ( and start blinking). 2. Select the required parameter. 3. Press the “SET” …
-
3, ,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation. 8.5 START DEFROST (i1F = dFr) It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will r…
-
4, dixell XR20C ,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV 15. DEFAULT SETTING VALUES Label Name Range °C/°F Set Set point LS÷US 3.0/37 Hy Differential 0,1÷25.5°C/ 1÷ 255°F 2.0/4 LS Minimum set point -50°C÷SET/-58°F÷SET -40,0/-40 US Maximum set point SET÷110°C/ SET ÷ 230°F 110/230 Ot Thermostat probe …
-
5, dixell XR20C Controller :DIXELL-XR20C Parameter setting code:D20-001M Parameter setting sheet for Entree Refrigerator CODE PARAMETER SET Set Main Set point 34 Hy Differential(hysteresis) 4 LS Lower limit of main set point 28 US Upper limit of main set point 50 Ot Offset -1 P2P Evapo…
-
dixell XR20C User Manual
-
dixell XR20C User Guide
-
dixell XR20C PDF Manual
-
dixell XR20C Owner’s Manuals
Recommended: 20646X9A, FAQE7011KW — 7 cu. Ft. Cycle Electric Dryer Drum, TY-ST08S
-
Bogart Engineering SC-2030
SC-2030 Solar Charge Controller Installation and User GuideBogartEngineering2017www.bogartengineering.comUPDOWNTM-2030 Connected.Charging. Flashing = OverloadSOLARBATTERYBOGART ENGINEERING30A CHARGERSystem Volts: 12V-down 24V-upBattery Type: AGM-down Flood-upSC-2030Warranty:Allitemshavea� …
SC-2030 3
-
Finelite HP-4 Recessed
RecessedCustomer:Job: PO:© 2018 FINELITE, INC. ALL RIGHTS RESERVED CPG0043. V2 08/18HP-4 Recessed / RegressedMounting and Feed GuideFinelite, Inc. •30500 Whipple Road •Union City, CA 94587-1530 •510 / 441-1100 •FAX: 510 / 441-1510 •www.finelite.comPage 1RECESSED MOUNTING OPTIONSFlush Screw Slot (C3F)1& …
HP-4 Recessed 3
-
Dynojet Power commander III
i129-411 www.powercommander.com 2007 Honda CB600F — 12007 Honda CB600FInstallation InstructionsDynojet Research 2191 Mendenhall Drive North Las Vegas, NV 89081 (800) 992-4993 www.powercommander.comParts List1 Power Commander1 USB Cable1 CD-ROM1 Installation Guide1 Power Adapter2 Power Commander …
Power commander III 4
-
AUMA SAVEx 07.2
ControlParallelProfibus DPProfinetModbus RTUModbus TCP/IPFoundation FieldbusHART→ EtherNet/IPMulti-turn actuatorsSAVEx 07.2 – SAVEx16.2SARVEx 07.2 – SARVEx16.2Control unit: electronic (MWG)with actuator controlsACVExC 01.2 Non-IntrusiveAssembly and commissioningOperation instructions …
SAVEx 07.2 100
Additional Information:
Popular Right Now:
Operating Impressions, Questions and Answers:
Модель XR20C , термостат с простейшим циклом оттайки, сконструированный для применения в холодильной области при нормальной температуре. Прибор обеспечен реле выхода, для того, чтобы управлять компрессором, и входом, для датчиков РТС или NТС. Внутренний таймер организует простейший цикл оттайки.
Скачать
Модель XR60C , прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. Прибор обеспечен 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической, так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.
Скачать
Модель XR70C , прибор с циклом оттайки, сконструированный для применения в холодильной области при нормальной и низкой температуре, также позволяет контролировать работу вентиляторов. Прибор обеспечен 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической , так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.)
Скачать
XC440C, XC440D, XC460D — серия семейства регуляторов Dixell разработан, чтобы управлять централями из нескольких компрессоров или конденсаторами с несколькими вентиляторами. Эта возможность гибко и всесторонне управлять устройствами улучшена возмлжностью выбирать номер и размер нагрузок, тип заданного действия: прямое или инверсивное, и 3 вида различной функциональной логики.
Скачать
Серии XC650C управляют как компрессорами, так и вентиляторами в системах конденсации. Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и в круге высокого давления (конденсаторы). Специальный алгоритм балансирует часы работы компрессоров, распределяя нагрузку равномерно. Контроллеры могут конвертировать как высокое, так и низкое давление и отображать их в виде температур.
Скачать
Контроллеры XC807M, XC811M, XC907M, XC911M управляют как компрессорами, так и вентиляторами в системах конденсации. Компрессора могут быть простыми, многоступенчатыми или с разными мощностями. Управление осуществляется при помощи нейтральной зоны или пропорционального регулирования и основано на давлении или температуре определяемой в зоне низкого давления (компрессоры) и в круге высокого давления (конденсаторы). Специальный алгоритм балансирует часы работы компрессоров, распределяя нагрузку равномерно. Контроллеры могут конвертировать как высокое, так и низкое давление и отображать их в виде температур.
Скачать
XP110C, XP111C, (32×74мм размер), XP110D, XP111D (на ДИН-РЕЙКУ) и XP111R, (72×72мм размер), является одноступенчатым релейным регулятором для управления давлением с прямым или обратным (выбираемым) действием. Аналоговый тип входа должен быть выбран и определен при заказе, согласно технологическому параметру, которым нужно управлять.
Скачать
Модели XR160C и XR170C , приборы с циклом оттайки, сконструированные для применения в холодильной области при нормальной и низкой температуре, также позволяют контролировать работу вентиляторов. Приборы обеспечены 3 реле выхода, для того, чтобы управлять компрессором, вентилятором и оттайкой, которая может быть как электрической, так и оттайкой горячим газом. Входами для 2 датчиков NТС ,один из которых нужен для контролдя температуры в объеме, другой для контроля температуры в испарителе и управления циклом оттайки и работы вентилятора.
Скачать
XT120C, XT121C, XT124C, XT125C (корпус 32×74 мм.), XT120D, XT121D (крепёж на ДИН-РЕЙКУ) и XT121R, XT125R (корпус 72×72 мм.), является универсальным прибором на основе микропроцессора с выходом на реле, разработанные для широкого диапазона применения в индустриальном секторе, особенно когда требуется два ступенчатых конфигурируемых регулятора.
Скачать
XR06CX, в формате 32 x 74 x 60мм — это микропроцессорный контроллер, подходящий для применения в средне и низкотемпературных блоках охлаждения с вентиляцией. У него есть три релейных выхода для управления компрессором, вентилятором и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячим газом). Прибор также снабжен 2 входами для датчиков NTC, первый — для контроля температуры, а второй должен размещаться на испарителе — для контроля температуры окончания оттайки и для управления вентилятором. Также он снабжен конфигурируемым цифровым входом. Имеется возможность легко и быстро запрограммировать контроллер с помощью ключа HOTKEY.
Скачать
Контроллер XC645CX разработан для управления и компрессорами, и вентиляторами конденсатора, работающими в составе агрегата. Компрессоры могут быть цифровыми спиральными (digital scroll), простыми, многоступенчатыми или разной мощности. Управление осуществляется по типу с «нейтральной зоной» или с «зоной пропорциональности» и основано на считывании величины давления или температуры в контурах всасывания LP (низкое давление — компрессоры) и нагнетания HP (высокое давление — конденсатор). Специальный алгоритм выравнивает часы наработки компрессоров, чтобы равномерно распределять рабочую нагрузку. Данный контроллер может конвертировать сигналы датчиков как низкого, так и высокого давления и показывать их на дисплее в виде температуры. Полная информация о состоянии системы предоставляется на передней панели путем показа давления (температур) всасывания и конденсации, состояния нагрузок, возможных аварий или условий обслуживания. Каждая нагрузка имеет свой аварийный вход, который способен остановить ее при активации. Для обеспечения общей безопасности системы также имеются два входа для реле низкого и высокого давления: при их срабатывании система останавливается. Контроллер можно легко запрограммировать при подаче на него питания с помощью ключа HOT KEY. Контроллер также можно подключить к системе управления и мониторинга семейства XWEB благодаря последовательному TTL-выходу, используя стандартный протокол ModBus RTU.
Скачать
Электронный контроллер для компрессорно-конденсаторных Установок. Примечание: При программировании параметров в зависимости от версии прошивки прибора, некоторые параметры могут не совпадать с указанными в инструкции. Они могут перескакивать на несколько пунктов по списку, либо вообще могут быть не указаны в таковом. Опыт работы показывает, что это ни как не сказывается на работе. Работают без сбоев в течении 5 лет непрерывной работы.
Скачать
XR03CX, в коротком формате 32х74×50 мм, — это микропроцессорный контроллер, подходящий для применения в блоках охлаждения с нормальной температурой. У него есть два релейных выхода: один – для компрессора, а другой — для выдачи аварии или как дополнительный выход. Он также снабжен входом для датчика NTC и одним цифровым входом для сигнала аварии, для включения дополнительного выхода или для запуска оттайки. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры или ключом HOTKEY.
Скачать
Модель XW60K является микропроцессорным контроллером подходящим для применения в средне- и низкотемпературных холодильных системах. При помощи двужильного кабеля (диам. 1мм) к нему на дистанции до 30м могут подключаться клавиатуры T620T или T620 или V620 или CX620. У него есть 3 релейных выхода для управления компрессором, вентилятором, освещением и оттайкой, которая может быть либо электрической, либо с реверсивным циклом (горячий газ). Он также снабжен четырьмя входами датчиков NTC или PTC, первый – для контроля температуры, второй, расположенный на испарителе — для контроля температуры окончания оттайки и управления вентилятором, третий и четвертый — для подачи сигнала аварии по температуре конденсатора или для показа температуры, отличной от температуры, по которой происходит регулирование. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга dIXELL семейства XWEB. Также он позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры.
Скачать
Модель TB77, с панелью размерами 32х74 мм, является контроллером с микропроцессором и предназначена для использования в средне- и низкотемпературных агрегатах. Она поставляется с тремя выходными реле для управления компрессором, оттайкой — которая может производиться как электронагревателями, так и горячим хладагентом — и вентиляторами воздухоохладителей. Она также комплектуется двумя входными датчиками (PTC): один для контроля температуры в камере, другой расположен в воздухоохладителе для контроля температуры прекращения оттайки. Каждый прибор полностью настраивается с помощью специальных параметров, которые могут быть легко запрограммированы с помощью кнопок.
Скачать
Модель XR10C, с панелью размерами 32х74 мм, является одноступенчатым температурным контроллером, предназначенным для использования при охлаждении или обогреве.
Скачать
Модель XR20CX, формата 32×74мм – это цифровой термостат с оттайкой «off cycle», предназначенный для применения в холодильных системах с нормальной температурой. У него имеется релейный выход для управления компрессором. Он также снабжен 2 входами датчиков NTC или PTC, первый — для контроля температуры, второй, опциональный, подключается к разъему HOT KEY и используется для подачи сигнала аварии по температуре конденсатора или для показа температуры. Цифровой вход может работать как третий датчик температуры. Выход HOT KEY позволяет подключать блок с помощью внешнего модуля XJ485-CX к сети, совместимой с ModBUS-RTU, такой как блоки мониторинга DIXEL семейства XWEB. Также он позволяет программировать контроллер с помощью ключа программирования HOT KEY. Прибор полностью конфигурируется с помощью специальных параметров, которые могут быть легко запрограммированы с клавиатуры.
Скачать
Контроллеры серии подключаются к системе мониторинга через выход RS485. Они повсеместно эксплуатируются в вентиляционных системах и устройствах охлаждения воздуха для обеспечивания максимальной производительности. Управление компрессором в данном случае выполняется по одному релейному выходу микропроцессора. Наличие двух NTC позволяет одним датчиком контролировать температурный диапазон, а другим пользоваться как элементом визуализации. Благодаря удобному программированию, контроллеры XR120D-XR130D в кратчайшие сроки настраиваются под конкретные требования системы охлаждения.
Скачать
Модели серии устанавливаются на DIN-рейку. Они оснащаются циклом оттайки, разработанный для эксплуатации в области холодильного оборудования. Контроллеры работают в нормально- и низкотемпературной среде, также обеспечивая управление вентиляционными системами. Электронное устройство основывается на 3х реле выхода, через которые выполняется контроль функционирования оттайки, компрессора и вентилятора. Программирование прибора осуществляется в кратчайшие сроки через клавиатуру, поэтому функции контроллера можно легко настроить под рабочие требования.
Скачать
Скачать инструкции по эксплуатации для оборудования Dixell — максимально упростить процесс знакомства с данными техническим аппаратами. В условиях современности, мануал можно скачать прямо на планшет, потому как используется популярный формат pdf-файла. Для большинства потребителей — это единственный выход ознакомиться с техникой, ведь в сложных экономических условиях вызов специалиста может влететь в копеечку. Скачать бесплатно инструкцию по эксплуатации сегодня очень просто. Большая часть специализированных сайтов и интернет-порталов готовы предоставить всем желающим данную услугу.