Service manual
Room air conditioner
Split Wall-Mounted Type
GC/CU-S05CR
GC/CU-S07HR
GC/CU-S09HR
GC/CU-S12HR
GC/CU-S18HR
Climatic Control Corporation
Wall-Mounted Split Type
Content
1. Precaution 1
1.1
1.2
Safety Precaution
Warning1
1
2. Function 3
3. Dimension 5
3.1
3.2
Indoor unit 5
Outdoor unit
6
4. Specification 7
5. Refrigerant cycle diagram 9
6. Operation limits 10
6.1
6.2
Cooling operation
Heating operation
10
10
7. Schematic diagram and Wiring diagram
7.1
7.2
11
Schematic diagram 11
Wiring diagram 12
8. Installation details 15
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
Wrench torque sheet for installation 15
Connecting the cables 15
Pipe length and the elevation 15
Air purging of the piping and indoor unit 16
Pumping down (Re-installation) 17
Re-air purging (Re-installation) 18
Balance refrigerant of the 2-way, 3-way valves 19
Evacuation 20
Gas charging
21
9. Capacity table 22
9.1
9.2
9.3
9.4
9.5
10.
10.1
10.2
10.3
10.4
10.5
10.6
10.7
10.8
10.9
GC/GU-S05CR
GC/GU-S07HR
GC/GU-S09HR
GC/GU-S12HR
GC/GU-S18HR
22
22
23
23
24
Electronic function 25
Electronic control working environment 25
Proper symbols and their meaning
25
Function
25
Protection 26
Fan-only mode 26
Cooling mode 26
Dehumidifying mode 27
Heating mode 28
Defrosting mode(available for heating mode) 29
www.generalclimate.com
Wall-Mounted Split Type
10.10
Auto mode 30
10.11 Force cooling function 30
10.12
Sleep mode 31
10.13
Auto restart function 31
10.14
Anion (optional) 31
11.Model and Parameters 33
12.
Troubleshooting
34
12.1
12.2
12.3
12.4
12.5
12.6
12.7
12.8
12.9
13.
Display board 34
Troubleshooting 34
Diagnostic chart 35
Resetting phenomenon often occurs during operation. 36
Operation lamp flashes and Timer lamp off. 36
Operation lamp flashes and Timer lamp on. 36
Operation lamp off and Timer lamp flashes
37
Operation lamp on and Timer lamp flashes
37
Operation lamp flashes, Timer lamp flashes . 37
Characteristic of temperature sensor
www.generalclimate.com
38
Wall-Mounted Split Type
1. Precaution
1.1
Safety Precaution
n To prevent injury to the user or other people and property damage, the following instructions must be followed.
n Incorrect operation due to ignoring instruction will cause harm or damage.
n Before service unit, be sure to read this service manual at first.
1.2
Warning
Ø Installation
n Do not use a defective or underrated circuit breaker. Use
There is risk of fire or electric shock.
n For electrical work, contact the dealer, seller, a qualified
electrician, or an Authorized service center.
Do not disassemble or repair the product, there is
risk of fire or electric shock.
n Always ground the product.
There is risk of fire or electric shock.
n Install the panel and the cover of control box securely.
open.
Moisture may condense and wet or damage
furniture.
n Take care to ensure that power cable could not be pulled
out or damaged during operation.
There is risk of fire or electric shock.
n Do not place anything on the power cable.
There is risk of fire or electric shock.
n Do not plug or unplug the power supply plug during
There is risk of fire of electric shock.
n Always install a dedicated circuit and breaker.
operation.
Improper wiring or installation may cause fore or
electric shock.
n Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
n Do not modify or extend the power cable.
There is risk of fire or electric shock.
n Do not install, remove, or reinstall the unit by yourself
(customer).
There is risk of fire, electric shock, explosion, or
injury.
n Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially
careful of the case edges and the fins on the
condenser and evaporator.
n For installation, always contact the dealer or an
Authorized service center.
There is risk of fire, electric shock, explosion, or
injury.
n Do not install the product on a defective installation
stand.
It may cause injury, accident, or damage to the
product.
n Be sure the installation area does not deteriorate with
age.
If the base collapses, the air conditioner could fall
with it, causing property damage, product failure,
and personal injury.
www.generalclimate.com
n Do not let the air conditioner run for a long time when the
humidity is very high and a door or a windows is left
this appliance on a dedicated circuit.
1
There is risk of fire or electric shock.
n Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
n Do not place a heater or other appliance near the power
cable.
There is risk of fire and electric shock.
n Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric
shock.
n Do not store or use flammable gas or combustible near
the product.
There is risk of fire or failure of product.
n Do not use the product in a tightly closed space for a
long time.
Oxygen deficiency could occur.
n When flammable gas leaks, turn off the gas and open a
window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off.
There is risk of explosion or fire.
n If strange sounds, or small or smoke comes from
product. Turn the breaker off or disconnect the power
supply cable.
There is risk of electric shock or fire.
n Stop operation and close the window in storm or
hurricane. If possible, remove the product from the
window before the hurricane arrives.
Wall-Mounted Split Type
There is risk of property damage, failure of product,
or electric shock.
n Do not open the inlet grill of the product during operation.
(Do not touch the electrostatic filter, if the unit is so
equipped.)
There is risk of physical injury, electric shock, or
product failure.
n When the product is soaked (flooded or submerged),
contact an Authorized service center.
n Do not expose the skin directly to cool air for long
periods of time. (Do not sit in the draft).
This could harm to your health.
n Do not use the product for special purposes, such as
preserving foods, works of art, etc. It is a consumer air
conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
n Do not block the inlet or outlet of air flow.
There is risk of fire or electric shock.
n Be caution that water could not enter the product.
There is risk of fire, electric shock, or product
damage.
n Ventilate the product from time to time when operating it
together with a stove, etc.
There is risk of fire or electric shock.
n Turn the main power off when cleaning or maintaining
the product.
There is risk of electric shock.
n When the product is not be used for a long time,
disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or
unintended operation.
n Take care to ensure that nobody could step on or fall
onto the outdoor unit.
This could result in personal injury and product
damage.
It may cause product failure.
n Use a soft cloth to clean. Do not use harsh detergents,
solvents, etc.
There is risk of fire, electric shock, or damage to the
plastic parts of the product.
n Do not touch the metal parts of the product when
removing the air filter. They are very sharp.
There is risk of personal injury.
n Do not step on pr put anything on the product. (outdoor
units)
There is risk of personal injury and failure of
product.
n Always insert the filter securely. Clean the filter every
two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air
conditioner and could cause product malfunction or
damage.
n Do not insert hands or other object through air inlet or
outlet while the product is operated.
Ø CAUTION
n Always check for gas (refrigerant) leakage after
installation or repair of product.
Low refrigerant levels may cause failure of product.
n Install the drain hose to ensure that water is drained
away properly.
There are sharp and moving parts that could cause
personal injury.
n Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
n Use a firm stool or ladder when cleaning or maintaining
the product.
A bad connection may cause water leakage.
n Keep level even when installing the product.
Be careful and avoid personal injury.
n Replace the all batteries in the remote control with new
To avoid vibration of water leakage.
n Do not install the product where the noise or hot air from
the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
n Use two or more people to lift and transport the product.
Avoid personal injury.
n Do not install the product where it will be exposed to sea
wind (salt spray) directly.
It may cause corrosion on the product. Corrosion,
particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient
operation.
www.generalclimate.com
Ø Operational
2
ones of the same type. Do not mix old and mew batteries
or different types of batteries.
There is risk of fire or explosion.
n Do not recharge or disassemble the batteries. Do not
dispose of batteries in a fire.
They may burn of explode.
n If the liquid from the batteries gets onto your skin or
clothes, wash it well with clean water. Do not use the
remote of the batteries have leaked.
The chemical in batteries could cause burns or
other health hazards.
Wall-Mounted Split Type
2. Function
Indoor unit
Operation ON/OFF by remote controller
Sensing by room temperature
Room temperature sensor.
Pipe temperature sensor.
Room temperature control
Maintain the room temperature in accordance with the setting temperature.
Starting temperature control
Indoor fan is delayed for 5 sec at the
starting.
Time Delay Safety control
Restarting is for approx. 3 minutes..
Indoor fan speed control
High, med, low, breeze.
Operation indication Lamps (LED)
Light up in the LED (LCD) for each operation mode.
Two-direction air vane
Anti-cold function
The unit will decide the louver direction according to operation mode.
Sleep mode auto control
The fan is turn to low speed (cooling/heating).
The unit will be turn off after seven hours.
Independent dehumidification
Prevent the cold wind at
the beginning of unit
start.
Temp. Compensation
Defrost mode
The function is usually used in rainy days in
springtime or damp areas.
Auto-restart function
Self-diag. function
The function will be
operate in any operation
mode.
Flexible wiring connection
Air flow Direction control
Easy clean panel
The louver can be set at the desired position or swing up
and down automatically
Auto mode
The unit can be change by the room temperature.
www.generalclimate.com
3
Wall-Mounted Split Type
Outdoor unit
Power relay control
The unit has 3 mins delay between continuously ON/OFF operations.
Low ambient kit
The unit can operate in cooling mode at low ambient temperature conditions.
Low noise air flow system
Bird tail propeller fan makes the outdoor unit run more quietly.
Hydrophilic aluminum fin
The hydrophilic fin can improve the heating efficiency at operation mode.
4 way valve control
It is only operated in the heating operation mode except defrosting operation.
Discharge pipe temperature protect
Anti-rust cabinet
Made from electrolytic zinc steel sheet and anti-rust coated components.
Valve protection cover
It protects the valves and prevents water from dripping.
www.generalclimate.com
4
Wall-Mounted Split Type
3. Dimension
3.1 Indoor unit
Dimension
Mode
5K
7K
9K
12K
18K
www.generalclimate.com
W
H
L
750
750
750
750
906
250
250
250
250
286
188
188
188
188
235
5
Wall-Mounted Split Type
3.2 Outdoor unit
Dimension
Mode
5K
7K
9K
12K
18K
www.generalclimate.com
W
H
D
L1
L2
L3
700
700
700
780
760
535
535
535
540
590
235
235
235
250
285
458
458
458
530
540
280
280
280
315
335
540
540
540
590
615
6
Wall-Mounted Split Type
4. Specification
Model
Power supply
Cooling
Heating
Capacity
Input
Rated current
EER
Capacity
Input
Rated current
COP
Max. current
Starting current
Model
Type
Brand
Capacity
Input
Compressor
Rated current(RLA)
Locked rotor Amp(LRA)
Thermal protector
Capacitor
Refrigerant oil
Model
Brand
Indoor
Input
fan motor
Capacitor
Speed(hi/mi/lo)
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Model
Brand
Outdoor
Input
fan motor
Capacitor
Speed
Outdoor air flow
Outdoor noise level
Refrigerant type R22
Design pressure
Liquid side/ Gas side
Refrigerant
Max. refrigerant pipe length
piping
Max. difference in level
Operation temp
Ambient temp
Application area
Ph-V-Hz
Btu/h
W
A
Btu/w.h
Btu/h
W
A
W/W
A
A
Btu/h
W
A
A
uF
ml
W
uF
r/min
m3/h
dB(A)
W
uF
r/min
3
m /h
dB(A)
g
MPa
mm
m
m
℃
℃
2
m
GC/GU-S05CR
1, 220-240V~,50Hz
5000
560
2,6
9
----------------3,8
16
KH104VFHC
Rotary
SHANGHAI SENLIN
5700
590
2,7
13
BF540-KB
15
MS-56 270
RPG13H
WELLING
36,5
1.2μF/450V
1020/ 960/ 900
300/270/240
32/30/28
YDK24-6T
WELLING
70
3
850
1400
49
480
2,6
6.35/
Ф
Ф9.53
10
5
17-30
18-45
8-12
GC/GU-S07HR
1, 220-240V~,50Hz
7000
760
3,6
9,2
7600
760
3,4
10
5
18
2P14C235ANA
Rotary
GD Matsushita
7500
725
3,4
15
MRA98854
25
ATOMOS M60 270
RPG13H
WELLING
36,5
1.2μF/450V
1020/ 960/ 900
380/350/320
32/30/28
YDK24-6T
WELLING
70
3
850
1400
49
620
2,6
6.35/
Ф
Ф9.53
10
5
17-30
-7 - 45
10-14
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally
somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
www.generalclimate.com
7
Wall-Mounted Split Type
Model
Power supply
Capacity
Input
Cooling
Rated current
EER
Capacity
Input
Heating
Rated current
COP
Max. current
Starting current
Model
Type
Brand
Capacity
Input
Compressor
Rated current(RLA)
Locked rotor Amp(LRA)
Thermal protector
Capacitor
Refrigerant oil
Model
Brand
Indoor
Input
fan motor
Capacitor
Speed(hi/mi/lo)
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Model
Brand
Outdoor
Input
fan motor
Capacitor
Speed
Outdoor air flow
Outdoor noise level
Refrigerant type R410A
Design pressure
Liquid side/ Gas side
Refrigerant
Max. refrigerant pipe length
piping
Max. difference in level
Operation temp
Ambient temp
Application area
GC/GU-S09HR
GC/GU-S12HR
GC/GU-S18HR
Ph-V-Hz 1, 220-240V~,50Hz 1, 220-240V~,50Hz 1, 220-240V~,50Hz
Btu/h
9000
12000
18000
W
960
1230
1920
A
4,5
5,7
9
Btu/w.h
9,4
9,8
9,4
Btu/h
10000
13000
20000
W
980
1290
1980
A
4,4
6
9,2
W/W
10,2
9,8
10,1
A
7
9,1
10
36
A
25
26
SHY33MC2-U
2P18S225ANK
PH225X2C-4FT
rotary
Rotary
Rotary
Hitachi
GD Matsushita
GD Toshiba
Btu/h
9920
13610
17620
W
970
1305
1725
A
4,5
6,1
8,1
A
24
26
36
External(MRA98745)
External
Internal
50
uF
30
35
600
ml
SUNISO 350
430
RPG13H
RPG25
RPG13H
WELLING
Welling
WELLING
36,5
53
W
36,5
1.2μF/450V
1.5uF/450V
uF
1,2
r/min
1100/1020/950
1350
1180
450/420/390
750/710/650
m3/h
550/500/460
37/34/31
41/38/35
dB(A)
41/ 38 /34
YDK24-6T
YDK24-6
YDK25-6H
WELLING
WELLING
WELLING
96
W
55
72
2.5μF/450V
2.5μF/450V
2.5μF/450V
uF
900
r/min
800
850
3
1500
1800
2000
m /h
dB(A)
50
52
54
1370
g
650
820
2,6
2,6
MPa
2,6
mm
Ф6.35/Ф9.53
Ф6.35/Ф12.7
Ф6.35/Ф12.7
m
10
10
15
m
5
5
8
17-30
17-30
17-30
℃
-7 - 45
-7 - 45
-7 - 45
℃
2
14-21
18-26
25-35
m
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally
somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
www.generalclimate.com
8
Wall-Mounted Split Type
5. Refrigerant cycle diagram
Ø Cooling only
Ø Heat pump mode
www.generalclimate.com
9
Wall-Mounted Split Type
6. Operation limits
6.1 Cooling operation
Outdoor unit air temp.℃ DB
Indoor air temp. ℃ DB
Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the
initial pull-down stage.
6.2 Heating operation
Indoor air temp. ℃ DB
Outdoor unit air temp.℃ DB
Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the
initial pull-down stage.
www.generalclimate.com
10
Wall-Mounted Split Type
7. Schematic diagram and Wiring diagram
7.1
Schematic diagram
www.generalclimate.com
11
Wall-Mounted Split Type
7.2
Wiring diagram
7.2.1
Cooling mode
GC/GU-S05CR
I NDOOR UNI T
OUTDOOR UNI T
1 2︵N︶
Y&G
BLACK
BLACK
OVERLOAD
RELAY
RED
RED
BLACK
COMPRESSOR C
RED
Y&G
R
S
BLUE
FAN RED
MOTOR
Y&G
COMPRESSOR
CAPACI TOR
www.generalclimate.com
BLUE
FAN
CAPACI TOR
12
Wall-Mounted Split Type
7.2.2
GC/GU-S07HR , GC/GU-S 09HR, GC/GU-S12HR
www.generalclimate.com
13
Wall-Mounted Split Type
MSG-18HR
www.generalclimate.com
14
Wall-Mounted Split Type
8. Installation details
8.1
Wrench torque sheet for installation
Outside diameter
mm
φ6.35
φ9.52
φ12.7
φ15.88
φ19.05
8.2
Torque
Kg.m
1.8
4.2
5.5
6.6
6.6
inch
1/4
3/8
1/2
5/8
3/4
Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
mm2
8.3
7K
1,0
12K
1,5
18K
2,5
Pipe length and the elevation
Capacity
Btu/h
7k~12K
18K
9K
1,0
Pipe size
GAS
3/8’’ (φ9.52)
1/2’’ (φ12.7)
1/2’’ (φ12.7)
LIQUID
1/4’’ (φ6.35)
1/4’’ (φ6.35)
1/4’’ (φ6.35)
Standard
length
Max.
Max.
Additional
(m)
Elevation
Elevation
refrigerant
5
5
5
B (m)
5
5
8
A (m)
10
10
15
(g/m)
30
30
30
In case that more
than 5m.
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be install per 5-7 meters.
www.generalclimate.com
15
Wall-Mounted Split Type
8.4
Air purging of the piping and indoor unit
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect the compressor,
reduce the cooling capacity, and could lead to a malfunction of unit.
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage
from the refrigeration cycle.
Procedure
6. Set the 3-way valve to the opened position.
1. Recheck the piping connections.
7. Mounted the valve stem nuts to the 2-way and 3-way valves.
2. Open the valve stem of the 2-way valve counterclockwise
8. Check for gas leakage.
§ At this time, especially check for gas leakage from the
approximately 90’, wait 10 seconds, and then set it to closed
position.
2-way and 3-way stem nuts, and from the service port.
§ Be sure to use a hexagonal wrench to operate the valve
stem
Caution:
3. Check for gas leakage.
If gas leakage is discovered in step (3) above, take the
§ Check the flare connection for gas leakage
following measures.
4. Purge the air from the system.
If the leaks stop when the piping connections are tightened
§ Set the 2-way valve to the open position and remove the
further, continue working from step (4).
cap from the 3-way valve’s service port.
If the gas leaks do not stop when the connections are
§ Using the hexagonal wrench to press the valve core pin,
retightened, repair the location of the leak, discharge all of
discharge for three seconds and then wait for one
the gas through the service port, and then recharge with the
minute.
specified amount of gas from a gas cylinder.
5. Use torque wrench to tighten the service port cap to a torque
of 1.8 kg.m. (18n.m)
www.generalclimate.com
16
Wall-Mounted Split Type
8.5
Pumping down (Re-installation)
Procedure
1. Confirm that both the 2-way and 3-way valves are set to the opened position.
§ Remove the valve stem caps and confirm that the valve stems are in the opened position.
§ Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve.
§ Connect the charge hose with the push pin to the gas service port.
4. Air purging of the charge hose.
§ Open the low-pressure valve on the charge set slightly to purge air from the charge hose.
5. Set the 2-way valve to the close position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
7. Immediately set the 3-way valve to the closed position.
§ Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
8. Disconnect the charge set, and amount the 2-way and 3-way valve’s stem nuts and service port caps.
§ Use a torque wrench to tighten the service port cap to a torque of 1.8 kg.m.
§ Be sure to check for gas leakage.
www.generalclimate.com
17
Wall-Mounted Split Type
8.6
Re-air purging (Re-installation)
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the closed position.
2. Connect the charge set and a charging cylinder to the service port of the 3-way valve.
§ Leave the valve on the charging cylinder closed.
3. Air purging.
§ Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve
approximately 45’ for 3 seconds then closing it for 1 minutes; repeat 3 times.
§ After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve.
4. Check the gas leakage.
§ Check the flare connections for gas leakage.
5. Discharge the refrigerant.
§ Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicate 0.3 to 0.5 Mpa.
6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position.
§ Be sure to use a hexagonal wrench to operate the valve stems.
7. Mount the valve stems nuts and the service port cap.
§ Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
§ Be sure to check the gas leakage.
www.generalclimate.com
18
Wall-Mounted Split Type
8.7
Balance refrigerant of the 2-way, 3-way valves
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valve’s service port.
§ Leave the valve on the charge set closed.
§ Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa.
§ If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than 0.1Mpa,
discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will not be necessary to apply a
evacuation.
§ Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be discharged.
www.generalclimate.com
19
Wall-Mounted Split Type
8.8
Evacuation
Procedure:
1. Connect the vacuum pump to the charge set’s centre hose.
2. Evacuation for approximately one hour.
§ Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move
(approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
§ Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
www.generalclimate.com
20
Wall-Mounted Split Type
8.9
Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
§ Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
2. Purge the air from the charge hose.
§ Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the
liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
§ If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a time
(approximately 150g each time0 while operating the air conditioner in the cooling cycle; however, one time is not sufficient,
wait approximately 1 minute and then repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valve’s service port.
§ Stopping partway will allow the refrigerant to be discharged.
§ If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before
disconnecting the hose.
5. Mounted the valve stem caps and the service port
§ Use torque wrench to tighten the service port cap to a torque of 18N.m.
§ Be sure to check for gas leakage.
www.generalclimate.com
21
Wall-Mounted Split Type
9. Capacity table
9.1
GC/GU-S05CR
SUMMER Cooling mode
Indoor
Conditions
21ºC D
Total capacity kW
15ºC W
Sensitive capacity kW
Input kW.
24ºC D
Total capacity kW
17ºC W
Sensitive capacity kW
Input kW.
27ºC D
Total capacity kW
19ºC W
Sensitive capacity kW
Input kW.
32ºC D
Total capacity kW
23ºC W
Sensitive capacity kW
Input kW.
9.2
WINTER
Indoor
Conditions
18ºC
20ºC
22ºC
25ºC
30ºC
35ºC
40ºC
45ºC
50ºC
1.41
1.03
0.48
1.53
1.12
0.49
1.63
1.24
0.51
1.81
1.40
0.53
1.33
0.99
0.51
1.46
1.09
0.52
1.56
1.20
0.54
1.74
1.36
0.56
1.23
0.93
0.53
1.37
1.04
0.54
1.47
1.15
0.56
1.68
1.32
0.58
1.13
0.86
0.57
1.29
0.99
0.59
1.39
1.09
0.60
1.57
1.24
0.63
1.06
0.81
0.63
1.20
0.93
0.65
1.30
1.02
0.67
1.43
1.14
0.70
0.98
0.76
0.65
1.11
0.86
0.67
1.19
0.94
0.69
1.35
1.09
0.72
GC/GU-S07HR
SUMMER Cooling mode
Indoor
Conditions
21ºC D
Total capacity kW
15ºC W
Sensitive capacity kW
Input kW.
24ºC D
Total capacity kW
17ºC W
Sensitive capacity kW
Input kW.
27ºC D
Total capacity kW
19ºC W
Sensitive capacity kW
Input kW.
32ºC D
Total capacity kW
23ºC W
Sensitive capacity kW
Input kW.
15ºC
OUTDOOR TEMPERATURE DRY
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
www.generalclimate.com
OUTDOOR TEMPERATURE DRY
25ºC
30ºC
35ºC
40ºC
45ºC
50ºC
1.97
1.44
0.65
2.13
1.57
0.67
2.27
1.73
0.69
2.53
1.95
0.72
1.85
1.38
0.69
2.04
1.52
0.71
2.17
1.67
0.73
2.43
1.89
0.76
1.71
1.29
0.71
1.90
1.45
0.74
2.05
1.60
0.76
2.35
1.84
0.79
1.58
1.20
0.77
1.80
1.38
0.80
1.94
1.52
0.82
2.18
1.72
0.85
1.47
1.13
0.86
1.68
1.29
0.88
1.81
1.42
0.91
2.00
1.60
0.95
1.37
1.05
0.89
1.55
1.20
0.91
1.66
1.32
0.94
1.88
1.52
0.98
0ºC D
-1ºC W
1.85
0.61
1.78
0.63
1.74
0.64
1.71
0.67
-4ºC D
-6ºC W
1.59
0.53
1.51
0.55
1.43
0.57
1.41
0.60
-7ºC D
-8ºC W
1.40
0.48
1.31
0.49
1.19
0.52
1.16
0.54
OUTDOOR CONDITIONS
12ºC D
7ºC D
4ºC D
11ºC W
6ºC W
3ºC W
2.62
2.30
2.10
0.78
0.71
0.66
2.57
2.26
2.05
0.80
0.72
0.67
2.22
2.55
2.03
0.73
0.83
0.69
2.52
2.20
2.00
0.86
0.74
0.70
22
Wall-Mounted Split Type
9.3
GC/GU-S09HR
SUMMER Cooling mode
Indoor
Conditions
21ºC D
Total capacity kW
15ºC W
Sensitive capacity kW
Input kW.
24ºC D
Total capacity kW
17ºC W
Sensitive capacity kW
Input kW.
27ºC D
Total capacity kW
19ºC W
Sensitive capacity kW
Input kW.
32ºC D
Total capacity kW
23ºC W
Sensitive capacity kW
Input kW.
WINTER
Indoor
Conditions
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
15ºC
18ºC
20ºC
22ºC
9.4
WINTER
Indoor
Conditions
18ºC
20ºC
22ºC
25ºC
30ºC
35ºC
40ºC
45ºC
50ºC
2.50
1.82
0.86
2.71
1.99
0.88
2.88
2.19
0.91
3.21
2.47
0.95
2.35
1.75
0.90
2.58
1.93
0.93
2.75
2.12
0.96
3.08
2.40
1.00
2.17
1.64
0.94
2.42
1.84
0.97
2.60
2.03
1.00
2.98
2.34
1.04
2.00
1.52
1.02
2.28
1.75
1.05
2.46
1.93
1.08
2.77
2.19
1.12
1.87
1.43
1.13
2.13
1.64
1.16
2.29
1.80
1.20
2.53
2.02
1.25
1.73
1.34
1.17
1.96
1.52
1.20
2.11
1.67
1.24
2.38
1.93
1.29
0ºC D
-1ºC W
2,44
0,82
2,35
0,84
2,29
0,86
2,26
0,90
-4ºC D
-6ºC W
2,10
0,72
1,99
0,74
1,89
0,76
1,85
0,81
-7ºC D
-8ºC W
1,84
0,65
1,73
0,66
1,56
0,70
1,54
0,72
OUTDOOR CONDITIONS
12ºC D
7ºC D
4ºC D
11ºC W
6ºC W
3ºC W
3,46
3,03
2,78
1,05
0,96
0,89
3,39
2,98
2,71
1,08
0,97
0,90
2,93
2,68
3,36
0,98
1,11
0,93
3,33
2,90
2,64
1,15
0,99
0,95
GC/GU-S12HR
SUMMER Cooling mode
Indoor
Conditions
21ºC D
Total capacity kW
15ºC W
Sensitive capacity kW
Input kW.
24ºC D
Total capacity kW
17ºC W
Sensitive capacity kW
Input kW.
27ºC D
Total capacity kW
19ºC W
Sensitive capacity kW
Input kW.
32ºC D
Total capacity kW
23ºC W
Sensitive capacity kW
Input kW.
15ºC
OUTDOOR TEMPERATURE DRY
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
www.generalclimate.com
OUTDOOR TEMPERATURE DRY
25ºC
30ºC
35ºC
40ºC
45ºC
50ºC
3.36
2.46
1.05
3.64
2.68
1.09
3.88
2.95
1.12
4.32
3.33
1.16
3.16
2.36
1.11
3.48
2.59
1.15
3.71
2.85
1.18
4.14
3.23
1.23
2.93
2.21
1.16
3.25
2.47
1.19
3.50
2.73
1.23
4.01
3.15
1.28
2.69
2.05
1.25
3.07
2.35
1.29
3.31
2.60
1.33
3.73
2.94
1.38
2.52
1.92
1.39
2.86
2.21
1.43
3.08
2.43
1.48
3.41
2.73
1.54
2.33
1.80
1.43
2.64
2.05
1.48
2.84
2.25
1.53
3.21
2.60
1.59
0ºC D
-1ºC W
3.17
1.08
3.06
1.11
2.98
1.14
2.94
1.18
-4ºC D
-6ºC W
2.73
0.94
2.59
0.97
2.45
1.00
2.41
1.06
-7ºC D
-8ºC W
2.40
0.86
2.25
0.87
2.03
0.92
2.00
0.95
OUTDOOR CONDITIONS
12ºC D
7ºC D
4ºC D
11ºC W
6ºC W
3ºC W
4.50
3.94
3.61
1.38
1.26
1.17
4.41
3.87
3.52
1.42
1.28
1.19
3.81
4.37
3.48
1.29
1.46
1.23
4.33
3.77
3.43
1.51
1.30
1.24
23
Wall-Mounted Split Type
9.5
GC/GU-S18HR
SUMMER Cooling mode
Indoor
Conditions
21ºC D
Total capacity kW
15ºC W
Sensitive capacity kW
Input kW.
24ºC D
Total capacity kW
17ºC W
Sensitive capacity kW
Input kW.
27ºC D
Total capacity kW
19ºC W
Sensitive capacity kW
Input kW.
32ºC D
Total capacity kW
23ºC W
Sensitive capacity kW
Input kW.
WINTER
Indoor
Conditions
15ºC
18ºC
20ºC
22ºC
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
www.generalclimate.com
OUTDOOR TEMPERATURE DRY
25ºC
30ºC
35ºC
40ºC
45ºC
50ºC
5.08
3.71
1.56
5.49
4.04
1.61
5.85
4.45
1.66
6.52
5.02
1.72
4.77
3.56
1.64
5.25
3.91
1.69
5.59
4.31
1.75
6.25
4.88
1.82
4.41
3.33
1.71
4.91
3.73
1.77
5.28
4.12
1.82
6.05
4.75
1.89
4.06
3.09
1.85
4.64
3.55
1.91
4.99
3.92
1.97
5.62
4.44
2.04
3.80
2.90
2.05
4.32
3.33
2.12
4.65
3.67
2.18
5.14
4.11
2.27
3.52
2.71
2.12
3.98
3.09
2.19
4.29
3.39
2.26
4.84
3.92
2.35
0ºC D
-1ºC W
4.64
1.51
4.47
1.55
4.36
1.58
4.30
1.65
-4ºC D
-6ºC W
3.99
1.32
3.79
1.36
3.59
1.40
3.53
1.48
-7ºC D
-8ºC W
3.51
1.19
3.28
1.21
2.97
1.28
2.92
1.33
OUTDOOR CONDITIONS
12ºC D
7ºC D
4ºC D
11ºC W
6ºC W
3ºC W
6.57
5.76
5.28
1.93
1.76
1.63
6.45
5.66
5.15
1.98
1.78
1.66
5.57
5.09
6.39
1.80
2.04
1.71
6.34
5.51
5.01
2.11
1.82
1.74
24
Wall-Mounted Split Type
10. Electronic function
(Just for the 5K, 7K, 9K, 12K, 16K, 18K cooling and heating mode)
10.1 Electronic control working environment
Input voltage: 175~253V
Input power frequency:50HZ
Ambient temperature: -7°C+43°C
Indoor fan normal working amp is less than 1A
Outdoor fan normal working amp is less than 1.5A
Four-way valve normal working amp is less than 1A
Swing motor: DC12V
Compressor: single-phase power supply. Its normal working amp is less than 15A
10.2 Proper symbols and their meaning
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I3sec: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I5MIN: Self-protection amp of compressor, continue five minutes until turns off the compressor.
IFAN: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
IRESTORE: Amp self-protection return value
THDEFROST: High wind, defrosting temperature difference
TM DEFROST: Middle wind, defrosting temperature difference
TLDEFROST: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
10.3 Function
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
www.generalclimate.com
25
Wall-Mounted Split Type
Anti frozen at cooling mode
10.4 Protection
10.4.1
3 minutes delay at restart for compressor.
10.4.2
Sensor protection at open circuit and breaking disconnection
10.4.3
Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than
400RPM), the unit stops and LED displays failure information and can’t returns to normal operation automatically.
10.4.4
Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED displays
failure information and can’t returns to normal operation automatically.
10.4.5
The current protection of the compressor
If compressor turns off for continuously 4 times due to current protection in 5 minutes from Compressor On, the unit stops and
LED displays failure information and can’t returns to normal operation automatically.
10.5 Fan-only mode
Fan speed is high/mid/low/ Auto
10.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:(T=indoor temperature)
www.generalclimate.com
26
Wall-Mounted Split Type
Auto fan at cooling mode:
Anti-freezing control to indoor evaporator at cooling mode ( T: evaporator temp. )
10.7 Dehumidifying mode
10.7.1 The 4-way valve is off in dehumidifying mode
10.7.2 Compressor and Indoor Fan actions in dehumidifying mode
Block
A
B
C
Indoor
Fan
LOW
BREEZE
LOW
BREEZE
LOW
BREEZE
Compressor and Outdoor Fan
ON 6minutes
OFF 4minutes
ON 5minutes
OFF 5minutes
ON 4minutes
OFF 6minutes
Repeat on and off cycle.
10.7.3 Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan is Breeze). Dehumidifying
operation will be resumed when room temperature restores to over 13℃.
www.generalclimate.com
27
Wall-Mounted Split Type
10.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the
same as that of cooling mode.
10.7.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
10.8 Heating mode
10.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.
4-way valve must delay 2 minutes compared with compressor if the compressor changed
into non-heating mode or turned off. 4-way valve doesn't delay in dehumidifying mode
10.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating
mode, except for the defrosting mode or the end of defrost
10.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for
7 minutes after starting and then judge temperature. Meanwhile other protections are still
valid.
* This parameter can be changed from 0 to 3
10.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails.
Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
10.8.5 Auto wind at heating mode (T=indoor temp.)
www.generalclimate.com
28
Wall-Mounted Split Type
10.8.6 Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)
10.8.7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time
10.9 Defrosting mode(available for heating mode)
Defrosting condition: Defrosting starts when either of the following ①&②:
① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
② Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan with the compressor still
running. Add up to 90 minutes.
Defrosting time
At condition ①, If item B is satisfied before item A, it would be regarded as severe frosting and the defrosting time is 10
minutes. If item B is satisfied after item A, the defrosting time is 6minutes.
At condition ②, the defrosting time is 10 minutes.
After three times continuous 6-minute defrost, the fourth defrost time should be 10 minutes.
The circulation is as following:
www.generalclimate.com
29
Wall-Mounted Split Type
Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 6 or 10 minutes.
B. The compressor current has reached to IDEFROST or above, IDEROST differs in different models
Defrosting Actions
Defrost 10 or 6 minutes
Compressor
25s
5s
4-way valve
2s
Outdoor fan
Indoor fan
10s
10.10 Auto mode
10.10.1
The air conditioner automatically selects one of the following operation modes:
cooling, heating or fan only according to the temperature difference between room
temperature (TA) and set temperature (TS).
10.10.2
The indoor fan blows automatically in corresponding selected mode
10.10.3
The motion of indoor fan’s blade should accord with the selected operation mode
10.10.4
One mode should be carried out for at least 15 minutes once selected. If the
compressor cannot start for 15 minutes, reselect the operation mode according to the room
temp. and set temp., or reselect when the set temp. varies
10.11 Force cooling function
10.11.1
10.11.2
Select forced cooling function with the forced cooling button or the switch
The compressor is unconditionally turned on, after 30 minutes cooling operation
whose fan mode is set as low, the A/C operates at the DRY mode with a set temp. of 24℃
10.11.3
All protections of remote control cooling are available at forced cooling operation
www.generalclimate.com
30
Wall-Mounted Split Type
10.11.4
Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24℃
10.12 Sleep mode
10.12.1
10.12.2
The sleep function is available at cooling, heating or auto mode
Cooling:
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a constant and the fan speed is kept
at low speed.
10.12.3
Heating:
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a constant and the air
circulation is kept at low speed (Anti-cold function takes precedence over all).
10.12.4
Auto:
After an hour running under economic mode, the set temp will rise 1℃,if it is under cooling mode; the set temp will decrease 1
℃,if it is under heating mode; the set temp will be changeless, if it is under fan-only mode; the condition will be the same after
the air conditioner running under economic mode after 2 hours, and during the next time the set temp do not change. The total
time is 7 hours, after 7 hours the unit stops.
10.13 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure when
power returns
10.14 Anion (optional)
Starts with indoor fan.
www.generalclimate.com
31
Wall-Mounted Split Type
www.generalclimate.com
32
Wall-Mounted Split Type
11. Model and Parameters
Model
I3SEC [A]
I5MIN [A]
IFAN [A]
IRESTORE [A]
IDEFROST [A]
TE1 ['C]
TE2 ['C]
TE3 ['C]
TE4 ['C]
TE5 ['C]
TE6 ['C]
TE7 ['C]
TE8 ['C]
TE9 ['C]
ANGLCOOL [']
ANGLHEAT [']
ANGLOFF [']
THDEFROST [']
TMDEFROST
TLDEFROST
GC/GU-S05CR GC/GU-S07HR GC/GU-S09HR GC/GU-S12HR GC/GU-S18HR
8,5
8,5
10
11
16
6,2
6,2
7,5
10
13
5,2
5,2
5,5
8
11
4,2
4,2
4.5A
6
9,5
3,2
3,5
5,5
6,5
28
28
28
34
32
32
32
36
30
30
30
30
26
26
20
20
2
2
2
3
3
7
7
7
8
10
60
60
60
60
53
53
53
52
50
50
50
50
200°
200°
200°
200°
50°
0°
0°
0°
105°
124°
124°
124°
124°
0°
16°C
14°C
14°C
17°C
[']
17°C
15°C
15°C
18°C
[']
18°C
16°C
16°C
19°C
www.generalclimate.com
33
Wall-Mounted Split Type
12. Troubleshooting
12.1 Display board
§ Operation
The indicator flashes once every second after power is on and illuminates when the air conditioner is in operation.
§ Timer indicator:
The indicator illuminates then TIMER is set ON.
§ PRE-DEF. indicator (For cooling & heating mode only)
The air conditioner starts defrosting automatically if outdoor unit frosts in heating operating.
At this time, PRE-DEF. indicator illuminates.
§ Auto indicator:
This indicator flashes when the air conditioner is in AUTO operation.
§ ECON indicator
This indicator illuminates while the air conditioner is in economic operation.
12.2 Troubleshooting
For cooling mode:
Operation
lamp
Failure phenomenon
☆
☆
X
On
Indoor fan speed has been out of control for over 1 minute
Indoor room temp. or evaporator sensor is open circuit or short circuit
Over current protection of the compressor occurs 4 times
EEROM error
No over-zero signal
r Extinguish
☆ Flash at 5Hz
☆
Timer
lamp
X
On
☆
☆
☆
For heat pump mode:
Operation
lamp
Failure phenomenon
Over current protection of the compressor occurs 4 times
Indoor fan speed has been out of control for over 1 minute
No over-zero signal
Temp. sensor on indoor evaporator is open circuit or short circuit
Indoor room temp. sensor is open circuit or short circuit
EEROM error
r Extinguish
☆ Flash at 5Hz
www.generalclimate.com
34
☆
X
☆
X
X
On
Timer
lamp
X
☆
☆
X
☆
☆
Defrosting
lamp
☆
☆
☆
☆
X
X
Wall-Mounted Split Type
12.3 Diagnostic chart
After energizing, no indicator is lighted and the air conditioner can’t be operated.
www.generalclimate.com
35
Wall-Mounted Split Type
12.4 Resetting phenomenon often occurs during operation.
(That is automatically entering to the status when power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:
Resetting phenomenon often occurs during operation.
Yes
After changing indoor PCB, check if the failure realease.
Yes
Yes
Indoor PCB is defective.
After changing indoor fan motor, check if the failure realease.
YES
Power supply circuit has problems.
12.5 Operation lamp flashes and Timer lamp off.
12.6 Operation lamp flashes and Timer lamp on.
www.generalclimate.com
36
Wall-Mounted Split Type
12.7 Operation lamp off and Timer lamp flashes
12.8 Operation lamp on and Timer lamp flashes
EEROM error, indoor PCB is defective.
12.9 Operation lamp flashes, Timer lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main control board must
have fault.
www.generalclimate.com
37
Wall-Mounted Split Type
13. Characteristic of temperature sensor
Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ
-10
62.2756
17
14.6181
44
4.3874
-9
58.7079
18
13.918
45
4.2126
-8
56.3694
19
13.2631
46
4.0459
-7
52.2438
20
12.6431
47
3.8867
-6
49.3161
21
12.0561
48
3.7348
-5
46.5725
22
11.5
49
3.5896
-4
44
23
10.9731
50
3.451
-3
41.5878
24
10.4736
51
3.3185
-2
39.8239
25
10
52
3.1918
-1
37.1988
26
9.5507
53
3.0707
0
35.2024
27
9.1245
54
2.959
1
33.3269
28
8.7198
55
2.8442
2
31.5635
29
8.3357
56
2.7382
3
29.9058
30
7.9708
57
2.6368
4
28.3459
31
7.6241
58
2.5397
5
26.8778
32
7.2946
59
2.4468
6
25.4954
33
6.9814
60
2.3577
7
24.1932
34
6.6835
61
2.2725
8
22.5662
35
6.4002
62
2.1907
9
21.8094
36
6.1306
63
2.1124
10
20.7184
37
5.8736
64
2.0373
11
19.6891
38
5.6296
65
1.9653
12
18.7177
39
5.3969
66
1.8963
13
17.8005
40
5.1752
67
1.83
14
16.9341
41
4.9639
68
1.7665
15
16.1156
42
4.7625
69
1.7055
16
15.3418
43
4.5705
70
1.6469
www.generalclimate.com
38
Wall-Mounted Split Type
Exploded View Parts for Model : GC-S05CR 220-240V~,50Hz :Indoor unit
No.
Part
1
Front
2
Name
Quantity
Sale code
1
10309121201
Air Filter
2
10309121202
3
Screw cap
3
10309121203
4
Panel frame
1
10309121204
5
Air cleaner
1
10109121226
6
Air cleaner holder
1
10109121225
7
Window for receiver
1
10309121207
8
Indicator for LED
1
10309121208
9
Horizontal louver
1
10309121209
10
Vertical louver
12
10309121210
11
Air out frame
1
10309121211
12
Louver holder
1
10309121212
Louver rocker
1
10309121213
Rocker gasket
1
10309121214
14
Louver motor
1
10121121218
15
Drain hose
1
10109121215
16
Indoor temp sensor
1
10109121243
17
Evaporator temp sensor
1
10109121242
Panel
13
www.generalclimate.com
39
Wall-Mounted Split Type
18
Left holder for evaporator
1
10307111202
19
Evaporator
1
10305111201
20
Bearing holder
1
10309121220
21
Cross flow fan, assy
1
10309121221
22
Chassis
1
10309121222
23
Back cover for chassis
1
10309121223
24
Installation Plate
1
10909121002
25
Connecting pipe clamp
1
10309121225
26
Fan motor
1
10309121226
27
Motor cover
1
10309121227
28
E-part box cover
1
10309121228
29
Indicator holder
1
10309121229
30
Display board,Ass'y
1
10407111002
31
Display board enclosure
1
10309121231
32
Main control board
1
10305111001
33
Transformer
1
10718121006
34
E-Parts box
1
10718121007
35
Wire clamp
1
10112121234
36
Wire joint, 5p
1
10407111004
37
Remote Controller
1
10109111203
38
Holder, Remote Controller
1
10109121208
39
Copper nut, TLM-A01
1
10909121012
40
Copper nut, TLM-B02
1
10909121013
www.generalclimate.com
40
Wall-Mounted Split Type
Exploded View Parts for Model
No.
Part
1
GU-S05HR
Name
220--240V,50Hz : Outdoor Unit
Quantity
Sale code
Clamp for front net
6
10112121801
2
Front net
1
10109121801
3
Small Handle
1
10109121802
4
Front clapboard
1
10107121801
5
Propeller fan
1
10109121804
6
Fan
1
10109121805
7
Holder for fan motor
1
10109121806
8
Chassis
1
10105121802
9
Compressor
1
10105121801
10
Installation plate for valves
1
10309121809
11
Gas pipe valve
1
10309121810
12
Liquid pipe valve
1
10309121811
13
Fan motor capacitor
1
10109121819
14
Installation board for E-parts
1
10109121820
15
Compressor capacitor
1
10105121803
16
Capacitor
1
10109121822
17
Wire joint
1
10109111802
Motor
clamp
www.generalclimate.com
41
Wall-Mounted Split Type
18
Separating board
1
10109121813
19
Condenser
1
10107111803
20
Water collector
1
10109121815
21
Right clapboard
1
10109121816
22
Big Handle
1
10109121817
23
Cover
1
10109121818
24
Rear
1
10109121824
Net
Exploded View Parts for Model : GC-S07HR
No.
Part
1
Front
2
Name
220-240V~,50Hz :Indoor Unit
Quantity
Sale code
1
10309121201
Air Filter
2
10309121202
3
Screw cap
3
10309121203
4
Panel frame
1
10309121204
5
Air cleaner
1
10109121226
6
Air cleaner holder
1
10109121225
7
Window for receiver
1
10309121207
8
Indicator for LED
1
10309121208
9
Horizontal louver
1
10309121209
Panel
www.generalclimate.com
42
Wall-Mounted Split Type
10
Vertical louver
12
10309121210
11
Air out frame
1
10309121211
12
Louver holder
1
10309121212
Louver rocker
1
10309121213
Rocker gasket
1
10309121214
14
Louver motor
1
10121121218
15
Drain hose
1
10109121215
16
Indoor temp sensor
1
10109121243
17
Evaporator temp sensor
1
10109121242
18
Left holder for evaporator
1
13008111007
19
Evaporator
1
13008111008
20
Bearing holder
1
10309121220
21
Cross flow fan, assy
1
10309121221
22
Chassis
1
10309121222
23
Back cover for chassis
1
10309121223
24
Installation Plate
1
10909121002
25
Connecting pipe clamp
1
10309121225
26
Fan motor
1
10309121226
27
Motor cover
1
10309121227
28
E-part box cover
1
10309121228
29
Indicator holder
1
10309121229
30
Display board,Ass'y
1
10309121240
31
Display board enclosure
1
10309121231
32
Main control board
1
10307121001
33
Transformer
1
10718121006
34
E-Parts box
1
10718121007
35
Wire clamp
1
10112121234
36
Wire joint, 5p
1
10309121242
37
Remote Controller
1
10109121207
38
Holder, Remote Controller
1
10109121208
39
Copper nut, TLM-A01
1
10909121012
40
Copper nut, TLM-B02
1
10909121013
13
www.generalclimate.com
43
Wall-Mounted Split Type
Exploded View Parts for Model
No.
Part
1
GU-S07HR
220--240V,50Hz : Outdoor Unit
Name
Quantity
Sale code
Clamp for front net
6
10112121801
2
Front net
1
10109121801
3
Small Handle
1
10109121802
4
Front clapboard
1
10107121801
5
Propeller fan
1
10109121804
6
Fan
1
10109121805
7
Holder for fan motor
1
10109121806
8
Chassis
1
10107121803
9
Compressor
1
10107121802
10
Installation plate for valves
1
10309121809
Gas pipe valve
1
10309121810
4-way valve
1
10109121812
12
Liquid pipe valve
1
10309121811
13
Fan motor capacitor
1
10109121819
14
Installation board for E-parts
1
13009111005
15
Compressor capacitor
1
10309121820
16
Capacitor
1
10109121822
Motor
11
clamp
www.generalclimate.com
44
Wall-Mounted Split Type
17
Wire joint
1
10109121823
18
Separating board
1
10109121813
19
Condenser
1
10107121804
20
Water collector
1
10109121815
21
Right clapboard
1
10109121816
22
Big Handle
1
10109121817
23
Cover
1
10109121818
24
Rear
1
10109121824
Net
Exploded View Parts for Model :
GC-S09HR
220-240V~,50Hz :Indoor Unit
No.
Part
Name
1
Front
2
Air Filter
3
Screw cap
4
Panel frame
1
10309121204
5
Air cleaner
1
10109121226
6
Air cleaner holder
1
10109121225
7
Window for receiver
1
10309121207
8
Indicator for LED
1
10309121208
9
Horizontal louver
1
10309121209
Panel
www.generalclimate.com
Quantity
Sale code
1
10309121201
2
10309121202
3
45
10309121203
Wall-Mounted Split Type
10
Vertical louver
12
10309121210
11
Air out frame
1
10309121211
12
Louver holder
1
10309121212
Louver rocker
1
10309121213
Rocker gasket
1
10309121214
14
Louver motor
1
10121121218
15
Drain hose
1
10109121215
16
Indoor temp sensor
1
10109121243
17
Evaporator temp sensor
1
10109121242
18
Left holder for evaporator
1
13008111007
19
Evaporator
1
13009111002
20
Bearing holder
1
10309121220
21
Cross flow fan, assy
1
10309121221
22
Chassis
1
10309121222
23
Back cover for chassis
1
10309121223
24
Installation Plate
1
10909121002
25
Connecting pipe clamp
1
10309121225
26
Fan motor
1
10309121226
27
Motor cover
1
10309121227
28
E-part box cover
1
10309121228
29
Indicator holder
1
10309121229
30
Display board,Ass'y
1
10309121240
31
Display board enclosure
1
10309121231
32
Main control board
1
10309121241
33
Transformer
1
10718121006
34
E-Parts box
1
10718121007
35
Wire clamp
1
10112121234
36
Wire joint, 5p
1
10309121242
37
Remote Controller
1
10109121207
38
Holder, Remote Controller
1
10109121208
39
Copper nut, TLM-A01
1
10909121012
40
Copper nut, TLM-B02
1
10909121013
13
www.generalclimate.com
46
Wall-Mounted Split Type
Exploded View Parts for Model
No.
Part
1
GU-S09HR
220-240V~,50Hz :Outdoor Unit
Name
Quantity
SALE Code
Clamp for front net
6
10112121801
2
Front net
1
10109121801
3
Front clapboard
1
10109113801
4
Propeller fan
1
10109121804
5
Fan
1
20407111802
6
Holder for fan motor
1
10109121806
7
Chassis
1
10107123802
8
Compressor
1
50309121805
9
Separating board
1
13008111803
10
Cover
1
11609121807
11
Condenser
1
11609121801
12
Installation board ,Left
1
11609121804
13
Rear
Net
1
11609121808
14
Right clapboard
1
11607111801
15
Big Handle
1
10109121817
16
Installation plate for valves
1
10309121809
17
Water collector
1
10109121815
18
Capacitor
1
10109121822
19
Compressor capacitor
1
11812113811
20
Fan motor capacitor
1
10112121815
21
Wire joint
1
10109121823
Motor
www.generalclimate.com
Clamp
47
Wall-Mounted Split Type
22
Washer for wire joint
1
10112121817
23
Wire
1
10112121816
24
Installation board for E-parts
1
13009111005
25
Low Pressure Valve Ass'y
1
11608121806
26
4-Ways valve
1
10109121812
27
Gas pipe valve
1
10309121810
28
High Pressure Valve Ass'y
1
10309121821
29
Liquid pipe valve
1
10309121811
30
Copper nut, TLM-A01
1
10909121012
31
Copper nut, TLM-B02
1
10909121013
Clamp
Exploded View Parts for Model :
No.
Part
1
Front
2
GC-S12HR
220-240V~,50Hz :Indoor Unit
Quantity
Sale code
1
10309121201
Air Filter
2
10309121202
3
Screw cap
3
10309121203
4
Panel frame
1
10309121204
5
Air cleaner
1
10109121226
6
Air cleaner holder
1
10109121225
7
Window for receiver
1
10309121207
8
Indicator for LED
1
10309121208
www.generalclimate.com
Name
Panel
48
Wall-Mounted Split Type
9
Horizontal louver
1
10309121209
10
Vertical louver
12
10309121210
11
Air out frame
1
10309121211
12
Louver holder
1
10309121212
Louver rocker
1
10309121213
Rocker gasket
1
10309121214
14
Louver motor
1
10121121218
15
Drain hose
1
10109121215
16
Indoor temp sensor
1
10109121243
17
Evaporator temp sensor
1
10109121242
18
Left holder for evaporator
1
13008111007
19
Evaporator
1
13012111001
20
Bearing holder
1
10309121220
21
Cross flow fan, assy
1
10309121221
22
Chassis
1
10309121222
23
Back cover for chassis
1
10309121223
24
Installation Plate
1
10909121002
25
Connecting pipe clamp
1
10309121225
26
Fan motor
1
10309121226
27
Motor cover
1
10309121227
28
E-part box cover
1
10309121228
29
Indicator holder
1
10309121229
30
Display board,Ass'y
1
10309121240
31
Display board enclosure
1
10309121231
32
Main control board
1
10312121254
33
Transformer
1
10718121006
34
E-Parts box
1
10718121007
35
Wire clamp
1
10112121234
36
Wire joint, 5p
1
10309121242
37
Remote Controller
1
10109121207
38
Holder, Remote Controller
1
10109121208
39
Copper nut, TLM-A01
1
10909121012
40
Copper nut, TLM-C03
1
10912121019
13
www.generalclimate.com
49
Wall-Mounted Split Type
Exploded View Parts for Model
No.
Part
1
GU-S12HR
Name
220--240V,50Hz : Outdoor Unit
Quantity
Sale code
Clamp for front net
6
10112121801
2
Front net
1
10109121801
3
Front clapboard
1
13012111801
4
Propeller fan
1
10112121803
5
Fan motor
1
10112111801
6
Holder for fan motor
1
50312121801
7
Chassis
1
11612121801
8
Compressor
1
10112121821
9
Separating board
1
10116113813
10
Small Handle
1
10830121811
11
Cover
1
13012111805
12
Condenser
1
11612121803
13
Installation board,left
1
13012111803
14
Rear net
1
13012111806
15
Right clapboard
1
13012111808
16
Big handle
1
10112121808
17
Installation plate for valves
1
10118113805
18
Water collector
1
10118121832
19
Capacitor clamp
1
10112121814
20
Compressor capacitor
1
30324313020
www.generalclimate.com
50
Wall-Mounted Split Type
21
Fan motor capacitor
1
10112121815
22
Wire joint
1
10109121823
23
Washer for wire joint
1
10112121817
24
Clamp for wiring
1
10112121816
25
Installation board for E-parts
1
15009111801
26
High Pressure Valve Ass'y
1
13012121801
27
Liquid pipe valve
1
10118121830
28
Low pressure Valve Ass'y
1
13012121802
29
4-ways valve
1
10312121852
30
Low-pressure Valve
1
10312121858
31
Copper nut, TLM-A01
1
10909121012
32
Copper nut, TLM-B02
1
10912121019
Exploded View Parts for Model
No.
Part
1
2
GC-S18HR
220-240V~,50Hz : Indoor Unit
Name
Quantity
Sale code
Front panel
1
10318121201
Air filter
2
10318121202
Air cleaner
1
10109121226
Air cleaner holder
1
10109121225
Panel frame
1
10318121203
3
4
www.generalclimate.com
51
Wall-Mounted Split Type
5
Display panel
1
10318121204
6
Protector for temp sensor
1
10112121224
7
Clamp for temp sensor
1
10109121231
8
Horizontal louver,up
1
10318121205
9
Horizontal louver,down
1
10318121206
10
Louver motor
1
10316121202
11
Air out frame
1
10318121208
12
Left holder for evaporator
1
10318121210
13
Evaporator
1
10316121203
14
Bearing holder
1
10318121212
15
Cross flow fan, ass'y
1
10318121213
16
Left cover for chassis
1
10318121214
17
Chassis
1
10318121215
18
Installation plate
1
10318121216
19
Connecting pipe clamp
1
10318121217
20
Underlay for relay
1
10318121218
21
Right cover for chassis
1
10318121219
22
Protection box for relay
1
10318121220
23
Fan motor
1
10318121221
24
Motor cover
1
10318121222
25
Evaporator temp sensor
1
10109121242
26
Indoor temp sensor
1
10109121243
27
Drain
1
10318121223
28
Bush
2
10318121224
29
Louver
12
10318121225
30
Louver holder
2
10318121226
31
Connecting bar for louver
1
10318121227
32
E-part box cover
1
10318121228
33
Transformer
1
10109121204
34
E-parts box
1
10318121230
35
Main control board
1
10316121204
36
Display board,ass'y
1
10316121205
37
Display board enclosure
1
10318121233
38
Wire clamp for power cord
1
10318121234
39
Wire joint, 5p
1
10318121235
40
Wire clamp
1
10112121234
41
Holder, remote controller
1
10109121208
www.generalclimate.com
hose
52
Wall-Mounted Split Type
42
Remote controller
1
10109121207
43
Relay
1
10118121238
44
Switch board
1
10109121205
45
Connection pipe for drainage
1
11609121003
46
Sealing ring
1
31009321021
47
Copper nut, TLM-A01
1
10909121012
48
Copper nut, TLM-C03
1
10912121019
Exploded View Parts for Model
No.
Part
1
GU-S18HR
220-240V~,50Hz : Outdoor Unit
Name
Quantity
Sale code
Clamp for front net
6
10112121801
2
Front net
1
10109121801
3
Front clapboard
1
13012111801
4
Propeller fan
1
10112121803
5
Fan motor
1
20412111801
6
Holder for fan motor
1
10312121002
7
Chassis
1
10116113806
8
Compressor
1
10116113807
9
Separating board
1
10116113813
10
Small Handle
1
10830121811
11
Cover
1
13012111805
12
Condenser
1
10116123801
www.generalclimate.com
53
Wall-Mounted Split Type
13
Installation board,left
1
13012111803
14
Rear net
1
13012111806
15
Right clapboard
1
13012111808
16
Big handle
1
10112121808
17
Installation plate for valves
1
10118113805
18
Water collector
1
10118121832
19
Capacitor clamp
1
10118121823
20
Compressor capacitor
1
30324313020
21
Fan motor capacitor
1
10112121815
22
Wire joint
1
10109121823
23
Washer for wire joint
1
10112121817
24
Clamp for wiring
1
10718121809
25
Installation board for E-parts
1
15009111801
26
High Pressure Valve Ass'y
1
10116123802
27
Liquid pipe valve
1
10118121830
28
Low pressure Valve Ass'y
1
10116123803
29
4-way valve
1
10312121852
30
Low-pressure Valve
1
10312121858
31
Copper nut, TLM-A01
1
10909121012
32
Copper nut, TLM-B02
1
10912121019
Climatic Control Corpоration. LLP
29-30 Margaret Street,
London W1R 6HH, UK
Tel./fax: +44 20 7016 9133
www.generalclimate.com
54
Wall-Mounted Split Type

Title

File Size

Download Links

General Climate AC-N9KRH Instruction Manual.pdf

777.3kb

Download

General Climate CU-S05CR Service Manual.pdf

1.4Mb

Download

General Climate CU-S09HR, CU-S18HR, CU-S12HR, GC-S05CR, CU-S07HR, GC-S07HR, GC-S09HR, GC-S12HR Service Manual.pdf

1.4Mb

Download

General Climate GC/CU-S24HR Service Manual.pdf

1.3Mb

Download

General Climate GC/CU-S30HR, GC/CU-S36HR, GC-S24HR, CU-S24HR Service Manual.pdf

1.3Mb

Download

General Climate GC-S05CR Service Manual.pdf

2.1Mb

Download

General Climate GC-S07CR, GU-S05CR, GU-S07CR, GC-S09CR, GU-S09CR Service Manual.pdf

2.1Mb

Download

General Climate GC-S12CR, GU-S12CR, GC-S18CR, GU-S18CR Service Manual.pdf

2.1Mb

Download

General Climate GC-S18HR, GC/CU-S07HR, GC/CU-S09HR, GC/CU-S12HR, GC/CU-S18HR Service Manual.pdf

1.4Mb

Download

General Climate GC-S30HR, CU-S30HR, GC-S36HR, CU-S36HR Service Manual.pdf

1.3Mb

Download

General Climate is the brand name for HVAC equipment.

General Climate was founded in 2002 in London. This is the Russian-British Association (RBA), which is founded to produce competitive climate technology and is being developed at
the expense of Russian investors.

In the 90s, a Russian businessman Leonid Kiryakov imported General Electric brand air conditioners into Russia and promoted them in the domestic market. But before these air conditioners had time
to gain popularity in Russia, as General Electric Corporation decided to curtail the climatic direction. And in 2002, Leonid Kiryakov decided to promote a new brand — General Climate.

The production and quality control in the General Climate group is carried out by the British company Climatic Control Corporation (headquarters in London).

Today, under the brand name General Climate, a wide range of climatic equipment is produced: household air conditioners, ventilation and heating equipment, chillers and fan
coils, large refrigeration systems and household air humidifiers.

General Climate Air Conditioners Service Manuals PDF
General Climate GC/GU-A36HR

Описание

Неинверторная сплит-система General Climate GC/GU-S12HRIN1 отличается надежностью  при интенсивном использовании в условиях высоких нагрузок.
В кондиционере General Climate GC/GU-S12HRIN1 установлен ионизатор, благодаря которому он имеет несколько неоспоримых преимуществ:

Ионизация воздуха оказывает антибактериальный эффект. 
Анионы, перемещаясь в помещении, сталкиваются бактериями и спорами. При этом они превращаются в гидроксигруппы (ОН) и разрушают  оболочки бактерий. Воздух очищается во всем помещении от бактерий, грибов, плесени. Возможно с этим и связана целебная сила ионов по защите человека от болезней.

Ионизация воздуха помогает устранить неприятные запахи и табачный дым. 
Сталкиваясь с молекулами загрязнений и неприятных запахов, анионы расщепляют их на безвредные вещества. Различные стойкие запахи и табачный дым удаляются без следа за 5-6 минут работы ионизатора. Учитывая объем воздуха захватываемого кондиционером — ионизация с его помощью идеальное средство для борьбы с дымом в доме курильщика.

Ионизация удаляет из воздуха некоторые нежелательные и опасные химические соединения. 
В помещении могут находиться источники нежелательных химических соединений, которые проникают в воздух: предметы, обработанные химическими средствами, вредные материалы и аэрозоли. 


Отличительные особенности:

Режим «Турбо»
В режиме «Турбо» (форсированном режиме) кондиционер работает после включения некоторое время с повышенной мощностью. Это позволяет быстрее достичь желаемой температуры в помещении. 


Оптимальная форма теплообменника

Во всех настенных кондиционерах General Climate установлен специальный трех> или четырехсекционный теплообменник. Конструкция теплообменника внутреннего блока позволила увеличить площадь теплообмена на 32% при сохранении компактных размеров теплообменника. 
В результате производительность настенных кондиционеров возросла, а размеры внутренних блоков меньше, чем у аналогичных кондиционеров других марок.

Специальная конструкция вентиляторов
Во внутренних блоках кондиционеров General Climate установлены тангенциальные вентиляторы большого диаметра. Их конструкция позволяет снизить скорость вращения и, соответственно, уменьшить шум, без снижения мощности кондиционера и потока воздуха. Во внешних блоках кондиционеров General Climate установлены экономичные вентиляторы осевого типа с высокими аэродинамическими показателями.

Медные трубки с повышенной площадью теплообмена
На внутренних поверхностях медных трубок теплообменников кондиционеров General Climate имеются канавки и выступы с сечением в форме трапеций. При таком оребрении улучшается теплообмен между протекающим по трубкам хладагентом и пластинами теплообменника. 

Легко смачиваемые теплообменники
Теплообменник внутреннего блока состоит из медных трубок с алюминиевым оребрением.
Оребрение легко смачивается водой, поэтому конденсат свободно стекает по алюминиевым пластинам, а не скапливается на поверхности теплообменника. Благодаря этому повышается эффективность теплообмена.

Автоматический перезапуск
Настенные кондиционеры General Climate автоматически возобновляют работу в прежнем режиме после перерыва в подаче электропитания (функция Auto>Restart). 

Режим SLEEP
Во время сна человек меньше двигается, поэтому ему требуется менее интенсивное охлаждение. «Sleep Mode», или режим «СОН», создает идеальные условия для отдыха – оптимальную температуру и низкий уровень шума вентилятора. Продолжительность режима – 7 часов (обычная длительность ночного сна). В режиме «СОН» вентилятор внутреннего блока переключается на малые обороты, чтобы снизить шум. Температура постепенно меняется.

Оптимальное направление потока воздуха
Как говорилось выше, под действием естественной конвекции теплый воздух поднимается к потолку, а холодный – опускается вниз, к полу. Это создает «неудобную» разницу температур между потолком и полом. Жалюзи настенных кондиционеров General Climate могут изменять направление воздушного потока в зависимости от режима работы. В режиме охлаждения холодный воздух подается вверх, в режиме обогрева – теплый воздух подается вниз. Таким образом, обеспечивается правильная циркуляция и равномерное перемешивание воздуха в помещении.

Самодиагностика кондиционера и защита от поломок
Микросхема, встроенная в настенные кондиционеры General Climate, самостоятельно выполняет диагностику неполадок. Сигналы о возникших неисправностях отображаются на световых индикаторах внутреннего блока сплит>системы. При необходимости автоматически включается система защиты от поломок. Новая технология позволяет вовремя обнаружить утечку хладагента и предотвратить выход оборудования из строя.


Антикоррозионный корпус внешнего блока кондиционера

Металлические поверхности внешнего блока кондиционеров General Climate надежно защищены от коррозии. Корпус внешнего блока изготовлен из оцинкованной стали и имеет дополнительное антикоррозионное покрытие. Это защищает кондиционер даже в самых сложных погодный условиях, при высокой влажности и больших перепадах температур.

Функция «таймер»
Кондиционер позволяет осуществить программирование включения / выключения системы по таймеру в диапазоне до 24 часов.

Функция «следуй за мной»
Кондиционер создает комфортную температуру именно в том месте помещения, где находится пульт ДУ. Кондиционер реагирует на показания температурного датчика встроенного в пульт дистанционного управления, автоматически настраиваясь на комфортный режим.

Функция «самоочистки»
При нажатии кнопки «Clean» на пульте дистанционного управления, внутренний блок начинает самоочистку испарителя, борется с размножением бактерий в блоке, сохранить свежесть воздуха.

Характеристики

Общие характеристики


Тип

настенная сплит-система


Обслуживаемая площадь, м²

27


Основные режимы

охлаждение/обогрев


Инверторный тип двигателя

нет


Гарантия

3 года

Мощность охлаждения/обогрева


Мощность в режиме охлаждения, Вт

3500


Мощность в режиме обогрева, Вт

3800


Потребляемая мощность при охлаждении, Вт

1100


Потребляемая мощность при обогреве, Вт

1000


Охлаждающая способность, BTU/ч

12000

Технические характеристики


Фаза

однофазный


Максимальный воздушный поток, м3/мин

8.0


Уровень шума внутреннего блока (мин / макс), дБ

33/39


Уровень шума внешнего блока (мин / макс), дБ

52


Диапазон наружных температур (охлаждение), C

от +18 до +43 °C


Диапазон наружных температур (обогрев), C

от -7 до +24 °C


Максимальная длина коммуникаций, м

20


Максимальный перепад высот, м

8


Диаметр трубок (жидкость), мм

1/4″ (6.35мм)


Диаметр трубок (газ), мм

1/2″ (12.7мм)


Тип хладагента

R 410A


Электропитание, Гц/В

50/220-240

Управление


Пульт дистанционного управления

беспроводной


Таймер включения /выключения

есть


Возможность программировать таймер

есть


Дисплей

есть


Контроль работы

индикаторы режимов работы на корпусе / дисплей с режимами работы на пульте


Управление по WiFi со смартфона

нет

Режимы и функции


Дополнительные режимы

ночной режим / турбо режим / режим вентиляции / автоматический режим / ионизация воздуха / режим осушения


Режим приточной вентиляции

нет


Текущая температура в помещении

нет

Конструкция


Фильтры тонкой очистки воздуха

есть

Размеры, вес, цвет


Габариты внутреннего блока (ШхВхГ), мм

750x250x198


Габариты внешнего блока (ШхВхГ), мм

750х250х198


Вес внутреннего блока, кг

8


Вес внешнего блока, кг

26
Цвет белый

Артикул

62747

Подберите похожие по характеристикам товары, выбрав одно или несколько свойств

Выбрано: 0
Подобрать

Доставка (450 р.)

Бренд General Climate
Охлаждающая способность (BTU) 12000
Минимальный уровень шума внутреннего блока (дБ) 35
Максимальный уровень шума внутреннего блока (дБ) 41
Тип хладагента R 410A
Мощность в режиме охлаждения (Вт) 3500
Потребляемая мощность при охлаждении (Вт) 1230
Тип конструкции настенная сплит-система
Основные режимы охлаждение / обогрев
Максимальный воздушный поток (куб. м/мин) 9.167
Количество скоростей вентилятора 3
Регулировка скорости вращения вентилятора есть
Таймер включения/выключения есть
Ночной режим есть
Функция запоминания настроек есть
Генератор анионов есть
Фильтры тонкой очистки воздуха есть
Пульт дистанционного управления есть
Самодиагностика неисправностей есть
Фаза однофазный
Высота внутреннего блока (см) 25
Ширина внутреннего блока (см) 75
Глубина внутреннего блока (см) 18.8
Высота внешнего блока (см) 54
Ширина внешнего блока (см) 78
Глубина внешнего блока (см) 25
Мощность в режиме обогрева (Вт) 3800
Потребляемая мощность при обогреве (Вт) 1290
Дезодорирующий фильтр есть

Понравилась статья? Поделить с друзьями:
  • General climate gc es09hri инструкция
  • General climate gc eaf09hrn1 инструкция
  • Genefinder covid 19 ag rapid test инструкция
  • Gene электронная сигарета инструкция по применению на русском
  • Gene voopoo инструкция по применению на русском