-
Haier
HSU-09HJ03
No.001050Installation Manual of Room Air ConditionerRead this manual before installation1.Driver2.Hacksaw3.Hole core drill4.Spanner(17,19 and 26mm)5.Torque wrench(17mm,22mm,26mm)6.Pipe cutter7.Flaring tool8.Knife9.Nipper 12.Reamer10.Gas leakage detector or soap-and-water solution11.Measuring tapeExplain sufficientl …
HSU-09HJ03 Air Conditioner, 10
-
LG
I24TTP
www.lg.comOWNER’S MANUALAIR CONDITIONERCopyright © 2018 — 2020 LG Electronics Inc. All Rights ReservedTYPE: WALL MOUNTEDMFL69781606Rev.04_120720Read this owner’s manual thoroughly before operating the appliance and keep it handy for reference at all times.EN ENGLISH …
I24TTP Air Conditioner, 39
-
DeLonghi
PAC 260
Use and maintenance manual . . . . . . . . . . .page 4Mode d’emploi et d’entretien . . . . . . . . . . .page 13Instrucciones de uso . . . . . . . . . . . . . . . .página 22Istruzioni per l’uso . . . . . . . . . . . . . . . . . . .pagina 31GB 19-05-2003 16:32 Pagina 1 …
PAC 260 Air Conditioner, 17
-
York
SINGLE PACKAGE AIR CONDITIONING CU060
INSTALLATIONINSTRUCTIONCAUTION: READ ALL SAFETY GUIDES BEFORE YOUSTART TO INSTALL THE UNIT.SAVE THIS MANUALWATERCOOLEDAIRCONDITIONING UNITSMODELS: CU060 — 096 — 120 -180240 — 300® 036-33072-001 Rev. A (0601)CONTENTSGENERAL ………………………………3INSTALLATION …………………………..4GENERALDATA.. …
SINGLE PACKAGE AIR CONDITIONING CU060 Air Conditioner, 20
Recommended Documentation:
Гость.
Огромное спасибо менеджеру Богомолов Александру за его профессиональный подход. Установка кондиционера была в согласованные время, быстро и качественно. Надеюсь работать будет кондиционер качественно.
Подробнее→
- 14 апреля 2023 12:18:37
- Запись: Отзывы о кондиционерах и сплит системах
Марина
Гость.
Благодарю компанию Фреоникс за установку и демонтаж старого кондиционера, все было сделано быстро, аккуратно, в срок , очень довольна работой мастеров и менеджера !
Подробнее→
- 10 апреля 2023 09:46:25
- Запись: Отзывы о кондиционерах и сплит системах
Гость
Гость.
30.03.2023г. мне поставиили кондициионер,куд я только не обращалась, растроилась ,думаю больше звонить не буду,и вдрук сайт ФРИОНИКС .ДУМАЮ ЭТО ПОСЛЕДНИЙ ЗВОНОК,И НЕ ОШИБЛАСЬ, Как это здорово, что в мире есть такие люди, как менеджер ВАСИЛИЙ,МОНТАЖНИКИ АЛЕКСАНДР и ЮРИЙ− люди, которые обладают добрым и чутким сердцем. Спасибо за искренность и понимание. Я хочу пожелать ВАМ здоровья, любви близких и уважения окружающих. Пусть в вашей жизни не будет трудностей, а только успех и достаток!От души благодарю Вас за прекрасную работу, за ответственность и творческий подход к любой сложной задаче. Спасибо вам за старательность, любовь и преданность делу, честный и эффективный труд. Желаю, чтобы вы и дальше работали с энтузиазмом, пусть каждый день приносит вам успех и радость. Будьте здоровы и энергичны, пусть финансы текут в ваш дом рекой! СПАСИБО ОГРОМНОЕ,ВСЕМ СОВЕТУЮ НЕ ПОЖАЛЕЕТЕ
Подробнее→
- 30 марта 2023 18:25:39
- Запись: Благодарности
Александр
Гость.
Хотел поблагодарить менеджера Александра и отдельно установщика Алексей!
Алексей профессионал с большой буквы очень быстро и самое главное качественно установил кондиционер
и проконсультировал по использованию его. Я остался доволен и решил поблагодарить тут)
работу выполнял в пиковских домах.
Подробнее→
- 24 марта 2023 12:48:26
- Запись: Контакты
Гость
Гость.
Хочу поблагодарить компанию Фреоникс в лице менеджера Александра и монтажника Александра за профессионализм. Алескандр быстро и четко дал рекомендации по схеме монтажа и комплектации, организовал на удобное мне время монтаж. Александр четко произвёл установку кондиционера: быстро , без лишней суеты и строительного мусора, аккуратно . Спасибо — приятно иметь дело с настоящими профессионалами ! Монтаж 18 марта 2023 года , заказ №145844
Подробнее→
- 19 марта 2023 11:18:53
- Запись: Отзывы о кондиционерах и сплит системах
Виктор Глыва
Зарегистрирован.
Хочу поблагодарить компанию Фреоникс в лице менеджера Сергея и монтажника Александра в первую очередь за профессиональное четкое исполнение своей работы ! Сергей быстро и конкретно дал свои рекомендации , организовал на удобное мне время монтаж. Александр как по нотам четко исполнил установку кондиционера с учетом моих пожеланий. Быстро , без лишней суеты , качественные расходные материалы, инструмент, аккуратность . Спасибо — приятно иметь дело с добросовестными людьми , настоящими профессионалами ! Монтаж 13 февраля 2023 года , Ивантеевка.
Подробнее→
- 14 февраля 2023 09:28:36
- Запись: Отзывы о кондиционерах и сплит системах
Сергей
Гость.
Хочу выразить огромную благодарность сотрудникам компании: менеджер Александр проконсультировал как надо, всё рассказал, помог подобрать нужную сплит-систему. Монтажник Евгений установил всё чётко и в срок. Качественная работа, спасибо!
Подробнее→
- 08 февраля 2023 19:33:27
- Запись: Отзывы о кондиционерах и сплит системах
Игорь
Гость.
Замечательные ребята монтажники Сергей и Яков. Работают профессионально, слаженно, очень аккуратно, по ходу решают возникающие проблемы установки. Спасибо им за работу. Также благодарность менеджеру Василию.
Подробнее→
- 26 декабря 2022 14:05:52
- Запись: Отзывы о кондиционерах и сплит системах
Ирина
Гость.
Из-за нестандартного монтажа долго сомневалась, переживала, но как это было напрасно!
Менеджер Игорь, монтажники Владимир и Николай — спасибо вам за ваше трепетное и внимательное отношение к клиентам, за ваш профессиональный подход к делу! Хочу сказать спасибо за слаженную работу, 10 из 10 баллов!
Подробнее→
- 08 декабря 2022 21:05:04
- Запись: Отзывы о кондиционерах и сплит системах
Анжелика
Гость.
Очень редко пишу отзывы, ограничиваюсь звездами, но тут не могу удержаться. Ребята вы лучшие! Спасибо Кириллу, отдельное ооогромное спасибо монтажникам Сергею и молодому человеку, имени которого, к сожалению, не знаю. Быстро, профессионально,чисто. Кондиционер ( совсем недорогой) супер! Рекомендовал Кирилл. Спасибо! Буду обращаться исключительно к вам.
Подробнее→
- 16 августа 2022 12:29:37
- Запись: Отзывы о кондиционерах и сплит системах
Лилиана Лушкова
Зарегистрирован.
Хочу выразить Вам благодарность и признательность за качественную и своевременную помощь всей компании и сервисному центру.Спасибо вы лучшие!!! ..
Подробнее→
- 19 июня 2022 13:00:25
- Запись: Отзывы о кондиционерах и сплит системах
Владимир
Гость.
Выражаю огромную благодарность компании Фреоникс, менеджеру Александру и мастерам установщикам Александру и Дмитрию! Все было выполнено очень оперативно, квалифицированный отподбор, доставка и установка мульти сплит системы. Цены очень демократичные. Установщики — профессионалы. Работы выполнили быстро и аккуратно. Впечатления, самые положительные, превзошли все ожидания. Рекомендую компанию Фреоникс, всем желающим создать свой микроклимат.
Подробнее→
- 18 июня 2022 23:33:12
- Запись: Отзывы о кондиционерах и сплит системах
Код: 49121
Извините, товара сейчас нет в наличии
Бесплатная доставка
по Красноярску
Извините, товара сейчас нет в наличии
Услуги:
Новости интернет-магазина «Лаукар»:
Дополнительная информация в категории Кондиционер:
В интернет-магазине бытовой техники «Лаукар» Вы можете скачать инструкцию к товару Кондиционер Galanz AUS-12H53R150L75 совершенно бесплатно.
Все инструкции, представленные на сайте интернет-магазина бытовой техники «Лаукар», предоставляются производителем товара.
Перед началом использования товара рекомендуем Вам ознакомиться с инструкцией по применению.
Для того чтобы скачать инструкцию, Вам необходимо нажать на ссылку «скачать инструкцию», расположенную ниже, а в случае, если ссылки нет,
Вы можете попробовать обратиться к данной странице позднее,
возможно специалисты интернет-магазина бытовой техники «Лаукар» еще не успели загрузить для скачивания инструкцию к товару:
Кондиционер Galanz AUS-12H53R150L75.
Фирма-производитель оставляет за собой право на внесение изменений в конструкцию, дизайн и комплектацию товара: Кондиционер Galanz AUS-12H53R150L75. Пожалуйста, сверяйте информацию о товаре с информацией на
официальном сайте компании производителя.
Split air conditioner
Wall mounted Type
Service manual
AUS-07C(H)53R010Lx
AUS-07C(H)53R150Lx
AUS-09C(H)53R150Lx
AUS-09C(H)53R010Lx
AUS-12C(H)53R150Lx
AUS-12C(H)53R130Lx
(X=1,2,3,4,5,6,14,15,16,……..)
CONTENTS
Contents
Safety precautions
Installation
Block diagram
Trouble shooting
Fault diagnosis by symptom
Control specification
To disassemble mechanical parts
Exploded views and parts list
Wiring diagrams
1
SAFETY PRECAUTIONS
The following safety precautions must be taken when using your air conditioner.
1. Warning: Prior to repair, disconnect the power cord.
2. Use proper parts: use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.)
3. Use the proper tools: use the proper tools and test equipment, and know how to use them. Using defective tools or test equipment may cause problems later-intermittent contact, for example.
4. Power cord: prior to repair, check the power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire.
6. After completing repairs and reassembly, check the insulation resistance.
Procedure: prior to applying power, measure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megohms.
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions are satisfactory. Relocate the unit if necessary.
9. Keep children away from the unit while it is being repaired.
10. Be sure to clean the unit and its surrounding area.
INSTALLATION
Selecting area for installation
Select an area for installation that is suitable to the customer’s needs.
1
Location of indoor unit
Keep the air inlet and outlet at a far distance from the blockage.
Keep the height distance between the indoor and outdoor unit at most 5m.
Mount on the wall solid enough to bear the weight of the unit and not cause any shake.
Avoid direct sunshine.
A place easy for condensate drain and easy for connecting with the outdoor unit.
Keep a far distance away from the fluorescent lamp, it may influence the operation of remote controller.
Keep at least 1m away from the TV radio and other home appliances.
2
Location of outdoor unit
A place solid enough to bear the weight of the unit and not cause any shake.
Good ventilation, less dust, far from direct rain and sunshine.
A place where the air discharged out of the outdoor unit or the operation noise will not annoy your neighbours.
No blockage near the outdoor unit.
Caution:
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including area near machines). Salty area such as coastal areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
2
INSTALLATION
Installation diagram of indoor unit and outdoor unit
Confirm the installation position by the mark of the indoor mounting plate.
or above 105mm above 155mm or or
The copper pipe can be led from back, right, underside, or left-back side.
back front right back left
Underside Left-back
Notice: do not elevate the drain hose.
While installing the pipeline on the thin armor plate or on the wall of metal mesh, you should use the wooden board to clamp between the wall and the pipeline, or wrap up the pipeline with 7-8 layers of insulating plastic tape.
Cover connecting pipe with
adiabatic material.
Sponge plastic adiabatic material with the thickness of 8mm.
above 300 mm above
500mm
100 mm above
300m m above
500m m
3
INSTALLATION
1
Securing the mounting plate and drill on the wall
Secure the mounting plate
The mounting plate should be attached to the structural part of wall (post etc).
105mm or more from sidewall fasten string at the central hole at least 24mm mounting plate
Tapping screw
ST4 25(5) at least 250mm
155mm or more from sidewall plumb
105mm or more from sidewall
Tapping screw
ST4 25(5)
Fasten string at the central hole plumb mounting plate at least 250mm
455mm or more from sidewall
NOTICE:
The holes at solid arrow position must be secured to avoid the shake of mounting plate.
When the expansion bolts are used, two holes ( 11 20 or 11 26 ) that the distance between them is 450mm should be adopted.
Drill on the wall
40mm fasten string at the central hole
105mm plumb
45mm
Center of hole( 65mm)
NOTICE:
Confirm the position of holes, and drill holes on the wall.
at least 140mm fasten string at the central hole at least 250mm at least 180mm
Center of hole( 65mm) at least 120mm fasten string at the central hole
440mm 440mm at least250mm at least 120mm
Center of hole( 65mm) plumb
120mm
Pipe hole
Center of hole( 65mm)
90mm plumb
90mm
Pipe hole
NOTICE:
The holes at solid arrow position must be secured to avoid the shake of mounting plate.
When the expansion bolts are used, two holes ( 11 20 or 11 26 ) that the distance between them is 450mm should be adopted.
Confirm the position of holes, and drill holes on the wall.
4
INSTALLATION
2
Wiring
Open the front grille;
Remove the screw from electrical box cover, pull the electrical box cover away from the unit and set aside.
Screw
Remove the screw from fastener, pull the fastener away from the unit and set aside.
Connect the cable.
Replace the fastener and electrical box cover.
Indoor unit terminal
Diagram
Connecting cable
NOTE:
The appliance shall be installed in accordance with national wiring regulations.
The appliance must not be installed in the laundry.
The appliance must be installed 2.3m above the floor.
The appliance must be positioned so that the plug is accessible.
For some models whose cooling capacity are above 4600W (17000BTU/h), an all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current device(RCD)with the rating of above 10mA shall
be incorporated in the fixed wiring according to the national rule.
3
Installation of the drain hose
Liquid pipe
NOTE:
The drain hose must be arranged beneath the copper pipe.
The drain hose must not be hunched or twisted.
While wrapping up the drain hose, do not pull it.
The drain hose through the room must be wrapped up by the
thermal insulation materials.
The copper pipe and the drain hose must be wrapped up by felt strip. Adiabatic pad should be used at where the pipe contacts the wall.
Drain hose felt
ROUTE OF PIPE
If pipe comes out of the right side of the indoor unit, cut part
1 of the unit;
If pipe comes out of the lower-right side of the indoor unit, cut part 2 of the unit;
If pipe comes out of the left side of the indoor unit, cut part 3 of the unit.
1
2 gas pipe
Adiabatic underlay
REFIT OF DRAIN HOSE
If pipe comes out of the left side of the indoor unit, the drain hose must be refitted, otherwise water leakage may occur.
Refit methods: Interchange the position of drain hose and drain rubber plug.
Clearance is not allowed after refit, it would lead to water leakage.
drain hose
Drain rubber plug
3
5
INSTALLATION
Arrangement of the drain hose
To drain the condensate water easily, the drain hose should be declined downwards.
The following 5 arrangement methods are incorrect.
Decline downward
(Fig. 1)
Water leak
Decline downward
Water leak
(Fig. 2)
Standing water
Dip hose
into water air
(Fig. 3)
Water leak
(Fig. 4)
50mm or less above floor
(Fig. 5)
Drain hose
If you find the drain hose not long enough to connect with the indoor unit, you can extend it with the hoses in the accessory box.
The drain hose through the room must be wrapped up with the special adiabatic material.
Hose(ID 15cm)
PVC hard
4
Installation of the indoor unit
Indoor unit
Let pipe go through the wall hole and attach the indoor unit to the mounting plate.(Press the rib of indoor unit inside the hook of the mounting plate.)
5
Pipe Connection
Bottom the mounting plate the rib of indoor unit
The number of bent position of the pipe in the indoor unit should not exceed 10.
The number of bent position of the pipe in the indoor unit and the outdoor unit should not exceed 15.
The radius of bent position should be more than 10cm.
Please break the evaporator craft tube with pincers before connecting. After exhausting the inside air, use the wrench to twist down the nut of connecting tube of the evaporator.
Put some seal oil to cover the joint and the flare.
Align the centre of joint in line with that of flare and tighten the nut of connecting pipe with wrench.
Attention:
Do not exhaust the inside air just by loosing the nut since there is the air of certain pressure inside the tube of indoor unit. Please do not make extra effort for fear of damaging the flare.
DIAMETER OF PIPE
6.35mm ( 1/4 )
9.52mm ( 3/8 )
12.7mm ( 1/2 )
15.88mm ( 5/8 )
TORQUE(N m)
13.7—17.6
34.3—41.2
49.0—56.4
73.0—78.0
Evaporator craft tube
6
Wall sealing and Pipe fastening
Use putty to seal the wall hole.
Use clamp (pipe fastener) to secure the pipe at specified position. seal with putty secure the connecting pipe with clamp get rid of unwanted part clamp
Indoor unit screw
6
INSTALLATION
Installation diagram of indoor unit and outdoor unit
1
Wiring
Outdoor unit terminal
Connecting cable or
Outdoor unit terminal
Connecting cable
Wiring For
Above 6000W Model (Above 21000BTU/h Model)
1 Remove the self-tapping screws (2 pcs) on the maintenance board and take out the maintenance board.
The cable wire can be led from the back hole
of the piping hole or ejecting hole.
Please utilize outdoor pipe support when
the cable wire is led from the backside.
Terminal board
Fix the cable wire with anchor cable
Maintenance board
Piping cover
Outdoor pipe support
(Outdoor pipe support is not required when leading the cable wire from other places).
2 Loosen the self-tapping screws (2 pcs) on the fixing clip to loosen the fixing clip.
3 Loosen the fixing screw of the wire terminal board, pass the power wire and signal wire through the fixing clip. Then firmly fix the power wire and signal wire on the terminal board with the fixing screw. (Earth wire must be connected firmly.)
4 Tighten the self-tapping screw on the fixing clip.
5 Install the maintenance board. After the pipes and cable wire are installed, please seal the sponge block as per drawing indication.
Maintenance board
Back wiring
Right wiring
Piping cover Ejecting hole
7
Sponge
Piping cover
INSTALLATION
Notice:
If the interconnection cord for power supply has to be replaced, please see the following table for reference.
MODEL SPECS (Interconnection cord)
2700W(10000BTU/h)
1.0mm
2
3000W(11000BTU/h) -4000W(15000BTU/h)
4500W(18000BTU/h) -8000W(28000BTU/h)
1.5mm
2
2.5mm
2
WARNING:
Please take the electric circuit diagram attached to the indoor/outdoor units as major reference while installing.
The power wire and signal wire between the indoor/outdoor units must be connected one by one as per corresponding number on the wiring terminal board.
The connecting cables must be clipped together.
Special cable must be used to connect indoor unit and outdoor unit. It should be ensured
that the terminals are not influenced by external force. Poor connection may cause fire.
The electric box cover must be mounted and secured in position, otherwise fire or electrical
shock may occur because of dust or moisture.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
All the models shall be connected with the mains which has system impedance limitations.
While installing the unit, please see the following table for impedance information or consult with the supply authority.
R410A
series
3500W (12000BTU/h)
5100W (18000BTU/h)
6800W (18000BTU/h)
0.219
0.186
0.124
8
INSTALLATION
2
Installation of the drain joint(only for heat pump type)
Insert the outdoor double-channel drain joint in one of the
bottom holes of the suitable size then connect drain hose
and joint together.
Bottom
Double-channel drain joint
3
Joint of the connecting pipe
Put some seal oil to cover the joint and the flare.
Drain hose
Align the centre of joint in line with that of flare and tighten the nut of connecting pipe with wrench. ( Adjust the torque by the same method of connecting pipe for indoor unit.)
4
Air exhausting
Screw down the cap of both gas shut-off valve and liquid shut-off valve as well as the nut of service port.
Use Allen wrench to turn the valve cork of liquid side at 90 counter-clockwise, and close it after 10 seconds.
Use soapy water to check the gas leakage especially at all joint. If there is no gas leakage, please turn the valve cork of liquid side at 90 counter-clockwise again.
liquid connecting pipe liquid shut-off valve allen wrench gas connecting pipe gas shut-off valve valve nuts
Press the cork of service port at gas shut-off valve, 10 seconds later, when you see foggy gas discharged, that means inner air is exhausted out.
service port service port cap
Use Allen wrench to turn the valve cork of both liquid shut-off valve and gas shut-off valve counter-clockwise until they are completely open and then replace the valve caps and tighten them.
5
Process of flared tube
Use the pipe cutter to cut off the broken part of flare.
Remove burrs at the cut of the flare.
Insert a nut into the connecting pipe and do flaring with specified flaring tools, reamers for example.
Remove burrs at the cut of the flare.
Outer diameter
6.35mm ( 1/4 )
9.52mm ( 3/8 )
12.7mm ( 1/2 )
15.88mm(5/8 )
A(mm)
2.0—2.5
3.0—3.5
3.5—4.0
4.0—4.5
Check the quality of flaring technique.
Copper pipe
90
Burr
Oblique Roughness Burr
Reamer
9
INSTALLATION
6
Adding refrigerant
If the connecting pipe is longer than 7 metres, add refrigerant as needed. (Cool only type) added amount A=(Lm-7m) 15g/m ; (Heat pump type)added amount A= (Lm-7m) 50g/m. ( A: amount of added refrigerant, L: the length of connecting pipe)
The length of connecting pipe (m)
(Cool only type)added amount (g)
(Heat pump type)added amount (g)
7
0
0
8
15
50
9
30
100
10
45
150
Exhaust the air as the above-mentioned method.
Screw the gas shut-off valve to close, connect charging hose(low pressure) to the service valve and then open gas shut-off valve again.
Set the unit to cool operation mode.
Connect the refrigerant bottle to the charging hose and then convert it.
Fill in liquid refrigerant as the above table.
Stop operation of the air conditioner.
Disconnect the manifold gauge after turning off the shut-off valve, and then open gas shut-off valve again.
Tighten nuts and caps of each valve.
Manifold gauge
Low pressure valve
Service port
Pressure meter
High pressure valve
Charging line
7
Relocation of the air conditioner.
Refer to this procedure when the unit is relocated.
1. Carry out the pump down procedure.
2. Remove the power cord.
3. Disconnect the assembly cable from the indoor and outdoor units.
4. Remove the flare nut connecting the indoor unit and the pipe.
At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign
material entering.
5. Disconnect the pipe connected to the outdoor unit.
6. Make sure you do not bend the connection pipes in the middle and store together with the cables.
7. Move the indoor and outdoor units to a new location.
8. Remove the mounting plate for the indoor unit and move it to a new location.
10
INSTALLATION
8
Operation test
Before test operation, wiring safety inspection must be carried out carefully again.
1. Emergency switch operation: Every press of emergency switch, the air conditioner runs as in the following order:
Cool only type: Cool
Shut off
Heat pump type: Cool
Heat Shut off
2. Remote controller operation: If the indoor unit sounds like Di, Di when pressing I/O button,
that indicates the air conditioner is under the operation of remote controller. After that, press
every button to test their functions.
3.
Check switch operation: Open the front grille and press the check button. Switch on the power
source and then the operation test is activated. If the indicator lamps light up at first and then
go out in succession or the LED window of the indoor unit illuminates at first and then goes out,
the system is under normal operation. If one of the indicator lamps is flashing at all times, or
failure codes are displayed on the LED window of the indoor unit, the system has something
wrong and please check malfunction immediately.
BLOCK DIAGRAM
Refrigerant Cycle Block Diagram
INDOOR UNIT OUTDOOR UNIT
Capillary tube
2-way valve
Liquid side
Check valve
Heat exchanger
(Evaporator)
Capillary tube
Heat exchanger
(Condenser)
Gas side
3-way valve
Accumulator
Compressor
4-way valve
Cooling
Heating
Gas leak check point
11
TROUBLE SHOOTING
Items to be checked first
1. Is the voltage of the power correct?
The input voltage shall be rating voltage 10%.
The air conditioner may not operate properly if the voltage is out of this range.
2. Is the link cable connecting the indoor unit and the outdoor unit linked properly?
Please refer to the “wiring diagram”
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
3. When a problem occurs due to the contents illustrated in the table below, it is symptom not related to the malfunction of the air conditioner.
Operation of air conditioner Explanation
In COOL operation mode, the compressor does not operate at a room temperature higher than the setting temperature that the indoor fan should operate.
In a HEAT operation mode, the compressor does not operate at a room temperature lower than the setting temperature that indoor fan should operate.
It happens after a delay of 3 minutes when the compressor is reoperated. The same phenomenon occurs when a power is on.
As a phenomenon that the compressor is reoperated after a delay of 3 minutes, the indoor fan is adjusted automatically with reference to a temperature of the air blow.
Fan speed setting is not allowed in AUTO or DRY mode.
The speed of the indoor fan is set to low in DRY mode.
Fan speed of 3 steps is selected automatically in AUTO mode.
Compressor stops operation intermittently in DRY mode.
Compressor operation is automatically controlled in DRY mode depending on the room temperature and humidity.
Compressor of the outdoor unit is operating although it is turned off in HEAT mode.
When the unit is turned off while de-ice is activated, the compressor continues operation for up to 10 minutes(maximum) until the deice is completed.
Timer is being activated and the unit is in ready mode.
The unit operates normally if the timer operation is cancelled.
Timer indicator lamp lights up and the air conditioner does not operate.
The compressor and indoor fan stop intermittently in HEAT mode.
The compressor and indoor fan stop intermittently if room temperature exceeds a setting temperature in order to protect the compressor from overheated air in HEAT mode.
Indoor fan and outdoor fan stop intermittently in HEAT mode.
The compressor stops intermittently in COOL mode or DRY mode, and fan speed of the indoor unit decreases.
The compressor operates in a reverse cycle to remove exterior ice in HEAT mode, and indoor fan and outdoor fan do not operate intermittently for within 20% of the total heat operation.
The compressor stops intermittently or the fan speed of the indoor unit decreases to prevent inside/outside air frozen depending on the inside/outside air temperature.
SELF DIAGNOSIS FUNCTION
Our company provides the end-users with thoughtful services by installing various diagnostic systems to
indicate the following irregular performances.
Check code
Diagnosis of malfunction
FAULT F6 PG motor faults
FAULT F7
FAULT F8
FAULT F9
Indoor TEMP sensor faults
Indoor coil pipe TEMP sensor faults
Outdoor coil pipe TEMP sensor faults
Note: When the outdoor coil pipe TEMP sensor is out of order or removed, the air conditioner will set to
defrost automatically in order to prevent it not working normally while the outdoor coil pipe TEMP sensor
is malfunction.
12
FAULT DIAGNOSIS BY SYMPTOM
No cooling
No cooling effect at all
Poor cooling
efficiency
Fan motor error compressor does not operate
Fan motor or its capacitor faults.
Loose connection or badly contact.
Control circuit error.
Voltage may appear a little lower or higher.
Loose or wrong connection.
Compressor faults or jumps for overloading.
Control circuit error.
Recharge the refrigerant at leaking place.
The capillary, pipeline are blocked or the valve is not open or the connecting tube is folded flat.
Leakage of refrigerant
Block of the cooling system
Insufficient refrigerant
Air filter is blocked
Poor efficiency of heat dissipating on the outdoor unit
Too high ambient temperature
Some leakage in the valve.
Some cracks, welding failure in the system.
Extra fluorin is added during mounting.
No periodical cleaning.
Accumulated lampblack, dust or contaminated ambient environment.
Mounting location is not suitable, such as near the wall.
Air outlet is blocked or accumulated lampblack or dust is attached to the vane.
The outdoor unit gets exposed to the sun for too long period.
Not for residential use.
Air conditioning burden is not adequate for the room
Low airflow volume
The four-way valve error
Blockage in the system
The doors and windows are not closed well; too weak of input cooling power or too many heat resources in the room.
Low fan motor frequency or capacitor is not functional.
Low fan speed or the fan motor faults.
The distributing air of the four-way valve may have mixed together; the valve core or solenoid valve faults.
The valve is not completely open; the capillary or
Pipeline is half blocked.
Connecting tube is folded flat.
13
FAULT DIAGNOSIS BY SYMPTOM
Fan motor or its capacitor faults.
Fan motor error
Loose connection or badly contact.
No heating
Control circuit error.
No heating effect at all compressor does not operate
Leakage of refrigerant
Voltage may appear a little lower or higher.
Loose or wrong connection.
Compressor faults or jumps for overloading.
Control circuit error.
Recharge the refrigerant at leaking place.
Block of the cooling system
The capillary, pipeline are blocked or the valve is not open or the connecting tube is folded flat.
The four-way valve or solenoid valve faults.
The four-way valve did not commutate or the distributing air of the four-way valve may have mixed together.
Poor heating
efficiency
Insufficient refrigerant
Air filter is blocked
Some leakage in the valve.
Some cracks, welding failure in the system.
Extra fluorin is added during mounting.
No periodical cleaning.
contaminated ambient environment.
Too low ambient temperature
Below 0 .
Too thick frost generated on the condenser.
Extra refrigerant or mixing air in the system
The condenser does not defrost, no smooth air circulation.
Discharge the redundant refrigerator recharge the refrigerant after vacuum extraction.
Air conditioning burden is not adequate for the room
The condenser is too dirty
The electric heater is not working
Low airflow volume
The four-way valve error
Blockage in the system
The doors and windows are not closed well; too weak of input cooling/heating power.
Accumulated lampblack or dust is attached to the vane.
Not satisfy the conditions for electric heater running.
Plug cords may be loose.
Low fan motor frequency or capacitor is not functional.
Low fan speed or the fan motor faults.
The distributing air of the four-way valve may have mixed together; the valve core or solenoid valve faults.
The valve is not completely open; the capillary or
Pipeline is half blocked.
Connecting tube is folded flat.
14
FAULT DIAGNOSIS BY SYMPTOM
Collision sound of the machine
Fixing bolts somewhere may loose or rub, some spare parts may not match very well.
Noisy
Flowing sound of the liquid
Refrigerant circulation or pressure change of refrigerant while switch on/off.
Noise from indoor unit
Sound of the running fan motor
Vane imbalance or distortion, rupture; loose screw of vane.
Sound of plastic pieces rubbing or deforming
Plastic pieces deform due to expansion when hot and shrink when cold. Or some spare parts may not match very well.
Collision sound of the machine
Collision of the pipeline, fixing screws loose or deform caused by rubbing.
Noise from
Outdoor unit
Oscillation sound
Sound of running fan motor
Sound made by cooling operation
Sound of running compressor
Inappropriate installation method; the unit does not match with the installation kit very well or the compressor quivers acutely.
Vane imbalance or distortion.
Refrigerant circulation or vane distortion.
Something wrong with the compressor, such as oil shortage, valve slice distortion.
Noise from the whole unit
Resonance sound
Sound made by compressor or motor
Flowing sound of condensed water
The unit does not match with the installation kit very well
The whole unit resonates thedoor and window.
Collision sound of the machine
Collision of the pipeline, fixing screws loose or plastic pieces deform.
The compressor or motor makes abnormal noise.
Condensed water is attached to the vane.
Sound of running fan motor
15
Vane imbalance or distortion.
FAULT DIAGNOSIS BY SYMPTOM
Switching on the air conditioner
The current leakage switch jumps to turn off
Junction wire looses and collides with the outer cover.
Degraded capability of wire insulation.
Insulation capability of some components has lowered.
Check the resistance of every component by multimeter
Water comes into the plug or electric components.
The fuse is blown or air limit switch jumps to turn off
Without any response
Is the voltage of power supply lower than 15% of rated voltage
(220V)?
Yes The voltage is low, please add manostat. somewhere.
Short circuit in the electric wire or connection wire.
Partially short circuit in some components.
Fuse capacity is adequate or not?
Check whether the receptacle has power or not.
Check as the above
-mentioned method.
fuse.
Strong circuit breaks the circulation.
The transformer faults.
The main control board faults.
Power supply error
16
CONTROL SPECIFICATION
ABBREVIATION
ST: Setting Temperature
PT: Indoor coil Pipe Temperature
RT: Room Temperature
OT: Outdoor coil pipe temperature
OFAN: Outdoor fan
IFAN: Indoor fan
COMP: Compressor
OPERATION OF MAIN BOARD
COOL MODE
The ST at cool mode is adjustable within16 -31 .
When RT ST, both the compressor and the outdoor fan start;
When RT<ST-1 , the compressor stops and 18 seconds later, the outdoor fan will stop.
But the indoor fan keeps running at predetermined speed.
Once turning on the unit while set at cool mode, the indoor fan immediately runs at predetermined speed; if all the conditions meet with the requirement of compressor operation, both the outdoor fan and compressor start running. If not, either the outdoor fan or compressor could start.
The four-way valve keeps being off all the time at cool mode.
Condensate dew prevention
If the horizontal air flow louver is set at low angle on COOL mode, after a while, it will auto swing to its maximum angel for system protection. 3 minutes later, the horizontal air flow louver will resume to its original position.
Anti-ice function
When PT=2 , the compressor does not stop and indoor fan runs at high speed.
When PT -1 for 1 minute, the compressor and outdoor fan stop and indoor fan runs at high speed.
When PT 8 for 5 minutes, anti-ice protection deactivates, both the compressor and the outdoor fan start operation.
8
2
-1
OFAN
COMP
ON
IFAN
Set speed
OFF
3 mins
OFF
High speed
5 mins
ON
ON
Set speed
17
CONTROL SPECIFICATION
HEAT MODE
If the air conditioner is off and then turned on while set at COOL ,HEAT or DRY mode, it will take approximately 3 minutes for the compressor to start.
The ST at heat mode is adjustable within16 -31 .
When RT ST, the compressor stops; when RT<ST-1 , the compressor starts.
Once turning on the unit while set at heat mode, if all the conditions meet with the requirement of compressor operation, the four-way valve gets charged and 8 seconds later, the compressor and outdoor fan start running.
Strong-wing prevention :
A.PT<27,the indoor fan stops running, the swing louver cannot be controlled by the remote controller.
B.34>PT 27,the indoor fan runs at low speed, the sweep louver erects.
C.PT
34,the indoor fan and the swing louver can be controlled normally.
Heat overload protection:
For 7000 BTU/h Model , when PT 47 , the outdoor fan stops; when PT 42 , the outdoor fan starts; when PT 60 , the compressor stops.
For 9000 BTU/h Model , when PT 50 , the outdoor fan stops; when PT 47 , the outdoor fan starts; when PT 63 , the compressor stops.
For 9000 BTU/h Model , when PT 55 , the outdoor fan stops; when Pt 50 , the outdoor fan starts; when PT 63 , the compressor stops.
Deice control:
Conditions for activating deice: a. The working hours of compressor accumulates to be 40 minutes.
b. When OT -4 for 1 minute.
Conditions for terminating deice: a. When OT 15 for 1 minute.
b. Over 10 minutes of deicing operation.
Electric-heat control:
Conditions for initiating electric-heat function: a. RT 23 ; b. RT+3 ST; c. The indoor fan runs; d. Turn on the electric-heat key; e. PT<50
Conditions for terminating electric-heat function: a. PT 50 ; b. RT 26 ; c. The indoor fan stops running; d. Turn off the electric-heat key; e. Mode change.
Conditions for terminating electric-heat function: a. PT 50 ; b. RT 26 ; c. The indoor fan stops running; d. Turn off the electric-heat key; e. Mode change.
15
OT
-4
COMP
OFAN
4-way valve
ON
OFF
ON
OFF
ON
OFF
TIME
30S 15S
10 minutes at most
18
30S 15S
CONTROL SPECIFICATION
DRY MODE
In this mode, the air conditioner automatically sets the room temperature and this temperature is incontrollable by remote controller. The initial ST =RT-2 .
Control during dry mode: a. When RT<15 , dry mode is not available; when RT 15 , the compressor intermittently runs under the influence of TS and RT. b. When RT 23 , if RT ST, the compressor runs intermittently as this:
Run for 8 minutes Stop for 3 minutes
If RT<ST, the compressor runs intermittently as this:
Stop for 4 minutes Run for 1 minute c. When RT<23 , if RT ST, the compressor runs intermittently as this:
Run for 2 minutes Stop for 3 minutes
If RT<ST, the compressor runs intermittently as this:
Stop for 4 minutes Run for 1 minute d. In this mode, the indoor fan keeps running at low speed with the same pace as the compressor, and this speed can not be controlled by remote controller.
AUTO MODE
In this mode, the air conditioner can automatically adjust the room temperature to decide the most suitable temperature. At the start of operation, the unit will automatically select the operation mode according to the room temperature. The following table shows the conditions which are set at start up.
Room
Temperature (RT)
26
RT 26
RT 25
25 RT 23
RT 23
Mode
Cool
Dry
Cool only type
Initial Setting Temperature Mode
24
RT-2
RT-2
21
Cool
Dry
Heat
Heat pump type
Initial Setting Temperature
24
RT-2
RT-2
26
Auto mode entering a. Once some operation mode is determined, it can not be changed even if the RT has altered.
b. You can change the operation mode by remote controller.
If restart within 2 hours, the unit will resume the same operation mode as before.
If restart after 2 hours, the unit will select the operation mode according to the initial room temperature.
At auto mode the ST can only be set + or — 2 of the RT.
19
CONTROL SPECIFICATION
FAN MODE
Indoor fan runs at the set speed while compressor and outdoor fan are turned off.
Indoor fan speed can be adjusted for low, medium and high.
SLEEP MODE
Sleep mode in cooling and drying running.
A. The indoor fan runs at low speed.
B. After one hour of operation the set temperature will increase by 1 . One hour later, the set temperature will increase by 1 once more. The unit will then continue operating at 2 above the set temperature.
Sleep mode in heating running.
A. The indoor fan runs at low speed.
B. After one hour of operation the set temperature will decrease by 2 . One hour later, the set temperature will decrease by 2 once more. The unit will then continue operating at 4 below the set temperature.
20
TO DISASSEMBLE MECHANICAL PARTS
Stop operation of the air conditioner and remove the power cord before repairing the unit.
The following pictures taking L1 series as an example are presented just for the purpose of illustration.
Indoor unit
No Parts Procedure Remark
1 Front grille 1.Stop the air conditioner
operation and block the
main power.
2.Contract the second finger
to the left ,and right handle
and pull to open the inlet
grille.
3.Draw away signal line.
4.Take the left and right filter
out.
5. Loosen two fixing screw of
front grille.
6.Put hands at the two ruts
of the body, then pull the
front panel out .
21
TO DISASSEMBLE MECHANICAL PARTS
No
2
Parts
Electrical parts
Procedure
1.Loosen the earth screw in
evaporator.
Remark
2.Loosen the s tepping motor
line, and p ull softly the indoor
pipe temperature sensor out
from the pipe casing.
3.Push the hook outside to take
the electrical box out easily.
4.Separate the electrical box
from the indoor unit.
3 Ass’y tray
drain
1.Push the left and right hooks
to make the ass’y pulled out.
22
TO DISASSEMBLE MECHANICAL PARTS
No Parts Procedure
2.Separete the ass’y tray drain
from the body.
Remark
1.Push the left hook and
separate the left part out of
evaporator.
4
Evaporator
2.Push the right hook and
separate the right part out
of evaporator.
3.Separate the evaporator
from the indoor unit.
5
Fan motor and cross fan
1.Separate the fan motor
from the fan.
23
TO DISASSEMBLE MECHANICAL PARTS
Outdoor unit
No Parts
1 Cabinet
Procedure
1.Turn off the unit and remove
the power cable.
Remark
2.Remove the upper cabinet,
the front cabinet and back
cabinet.
2
Fan motor & propeller fan
1.Remove the nut flange.
(Turn to the right to remove
as it a left turned screw )
2.separate the propeller fan
from fan motor.
3.Loosen the fixed screw of
fan motor,separate the fan
motor from outdoor unit
3
Ass’y control out
1.Loosen the fixing screw of
the base-electrical control .
2.separate the connector.
3.Separate the ass’ y control
out from the outdoor unit.
24
Exploded Views and Parts List
Indoor unit
AUS-07C(H)53R010Lx AUS-09C(H)53R010Lx
AUS-12C(H)53R130Lx AUS-12C(H)53R150Lx
AUS-07C(H)53R150Lx
AUS-09C(H)53R150Lx
25
Exploded Views and Parts List
Indoor unit
AUS-07C(H)53R010Lx
AUS-12C(H)53R130Lx
No. English Part Name
1
2
3
4 air filter
Front panel
LED
Electrical control box
5 Enclosure
6 Swing louver
7 Water collecting tray
8 Evaporator
9 Indoor unit fan
10 Oil bearing
11 Rubber bear support
12 Bottom enclosure
13 Power supply cord clip
14 Electrical control box
15
Indoor unit terminal block
16 Transformer
17 Mounting plate
18 Main control board
19 Power supply cord
20 Room temperature sensor 1
21
Pipe temperature sensor
1
22 Pipe fixing plate
23 fan motor
24 Electrical holder
25 Stepping motor
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
qty.
2
1
remark
left and right are sameness
L14 L15 L16 parted as upper panel and lower panel
1
1
L14(control box)
L15(display box)
L16 without
L17without
AUS-09C(H)53R010Lx
AUS-12C(H)53R150Lx
AUS-07C(H)53R150Lx
AUS-09C(H)53R150Lx
remark No.
English Part Name qty.
26 Drain hose 1
27 Electrical control cover
28
29
Indoor display panel
Decorate ring
1
1
L1 L17(display piece)
L15(transparency piece)
L15without
1
L1 L3 L16 L18 without
L15(decorate tape),
L17(decorate board)
26
Exploded Views and Parts List
Outdoor unit
AUS-07C53R010Lx AUS-09C53R010Lx
27
Exploded Views and Parts List
Outdoor unit
AUS-07C53R010Lx AUS-09C53R010Lx
No. English Part Name
1 Air outlet grille
2 Front panel
3 Left handle
4 Top cover
5 Outdoor unit fan
6 Outdoor fan motor
7 Outdoor fan motor supporter
8 Condenser
9 Partition
10
Electrical install board supporter
11 Left back side plate
12 Back cover
13 right back side plate
14 Electrical install board
15 Capacitor fixing clip
16 Outdoor unit terminal block
17 power supply cord clip
18 capacitor for Compressor
Quantity No. English Part Name Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
19 Fan motor capacitor
20 Capillary assembly
21 High pressure valve
22 Low pressure valve
23 valve board
24 Compressor screw
25 Compressor
26 Bottom board
27 Right handle
3
1
1
1
1
1
1
1
1
28
Exploded Views and Parts List
Outdoor unit
AUS-07H53R010Lx AUS-09H53R010Lx
29
Exploded Views and Parts List
Outdoor unit
AUS-07H53R010Lx AUS-09H53R010Lx
Number Name
1 Air outlet grille
2 Front panel
3 Left handle
4 Top cover
5 Outdoor unit fan
6 Outdoor fan motor
7
Outdoor fan motor supporter
8 Condenser
9 Partition
10 Four way valve
11
Electrical install board supporter
12 Left back side plate
13 Back cover
14 Right back side plate
15 Electrical install board
16 Capacitor fixing clip
17
Outdoor unit terminal block
18 Power supply cord clip
19 Capacitor for Compressor 1
20 Fan motor capacitor 1
21 Capillary assembly
22 High pressure valve
1
1
23 Low pressure valve
24 Valve board
1
1
1
1
1
1
25 Compressor screw
26 Compressor
27 Bottom board
3
1
1
Quantity Number Name
1
1
1
28
29
Right handle
Outdoor pipe sensor
1
1
1
1
1
1
1
1
1
1
1
Quantity
1
1
30
Exploded Views and Parts List
Outdoor unit
AUS-12C53R150Lx AUS-07C53R150Lx AUS-09C53R150Lx
31
Exploded Views and Parts List
Outdoor unit
AUS-12C53R150Lx AUS-07C53R150Lx AUS-09C53R150Lx
No English Part Name
1 Air outlet grille
2 Front panel
3 Outdoor unit fan
4 Partition
5 Valve board
6 Compressor screw
7 Power supply cord fixing
8 Power supply cord clip
9 Capacitor for compressor
10 Electrical install board
11 Right side board
12 Top cover
13 Fan motor capacitor
14 Outdoor unit terminal block
15 High pressure valve
16 Capillary assembly
17 Low pressure valve
18 Compressor
19 Bottom board
20 Condenser
21 Uphold board
22 Capacitor fixing clip
23 Fan motor (out door)
24 Fan screw nut M8
25 Right handle
1
1
1
1
1
1
1
1
1
3
1
1
1
1
1
1
3
1
1
1
Quantity No.
1 26
English Part Name
Outdoor fan motor supporter
1
1
1
1
Quantity
1
Exploded Views and Parts List
Outdoor unit
AUS-12H53R150Lx AUS-07H53R150Lx AUS-09H53R150Lx
33
Exploded Views and Parts List
Outdoor unit
AUS-12H53R150Lx AUS-07H53R150Lx AUS-09H53R150Lx
No.
English Part Name
1 Air outlet grille
2 Front panel
3 Outdoor unit fan
4 Partition
5 Valve board
6 Compressor screw
7 Power supply cord fixs
8 Power supply cord clip
9 Capacitor for compressor
10 Electrical install board
11 Right side board
12 Top cover
13 fan motor capacitor
14 Outdoor unit terminal block
15 High pressure valve
16 Capillary assembly
17 Low pressure valve
18 Four way valve
19 Compressor
20 Bottom board
21 Condenser
22 Uphold board
23 Capacitor fixing clip
24 Fan screw nut M6
25 Fan screw nut M8
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Quantity No.
1 26
English Part Name
Right handle
1
1
27 Outdoor fan motor supporter
1
1
3
Quantity
1
1
Exploded Views and Parts List
Outdoor unit
AUS-12C53R130Lx
35
Exploded Views and Parts List
Outdoor unit
AUS-12C53R130Lx
No. English Part Name
1 Air outlet grille
2 Front panel
3 Outdoor unit fan
4 Outdoor fan motor
5 Outdoor fan motor supporter
6 Left handle
7 Left back side board
8 Condenser
9 Back cover
10 Fixed board
11 Top cover
12 Fan motor capacitor
13 Capacitor for Compressor
14 Electrical install board
15 Capacitor fixing clip
16 Outdoor unit terminal block
17 Power supply cord clip
18 Right handle
19 Right back side board
20 Capillary assembly
21 High pressure valve
22 Low pressure valve
23 Valve board
24 Compressor
25 Bottom board
26 Partition
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Quantity No. English Part Name Quantity
1
1
1
1
36
Exploded Views and Parts List
Outdoor unit
AUS-12H53R130Lx
37
Exploded Views and Parts List
Outdoor unit
AUS-12H53R130Lx
No. English Part Name
1 Air outlet grille
2 Left handle
3 Front panel
4 Outdoor unit fan
5 Partition
6 Top cover
7 Left back side plate
8 Condenser
9 Right back side plate
10 Right handle
11 Fan motor capacitor
12 Capacitor for Compressor
13 Electrical install board
14 Outdoor unit terminal block
15 Power supply cord clip
16 Outdoor fan motor supporter
17 Outdoor fan motor
18 Four way valve
19 Capillary assembly
20 High pressure valve
21 Valve board
22 Low pressure valve
23 Compressor
24 Back board
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Quantity No. English Part Name Quantity
1
1
1
1
1
38
Wiring Diagrams
Indoor unit
AUS-07C53R010Lx
AUS-12C53R130Lx
AUS-09C53R010Lx
AUS-12C53R150Lx
AUS-07C53R150Lx
AUS-09C53R150Lx
IFAN
Outdoor unit
AUS-07C53R010Lx
AUS-12C53R130Lx
AUS-09C53R010Lx
AUS-12C53R150Lx
AUS-07C53R150Lx
AUS-09C53R150Lx
39
Wiring Diagrams
Indoor unit
AUS-07H53R010Lx
AUS-12H53R130Lx
AUS-09H53R010Lx
IFAN
Outdoor unit
AUS-07H53R010Lx AUS-12H53R130Lx
AUS-09H53R010Lx
40
Wiring Diagrams
Indoor unit
AUS-12H53R150Lx
AUS-07H53R150Lx AUS-09H53R150Lx
IFAN
Outdoor unit
AUS-12H53R150Lx AUS-07H53R150Lx
AUS-09H53R150Lx
41