Danfoss серия ERC — холодильные контроллеры Danfoss | Управление Холодом
Specifications:1599/1599868-erc_101_kit.pdf file (22 Apr 2023) |
Accompanying Data:
Danfoss ERC 101 kit Controller PDF Instruction Sheet (Updated: Saturday 22nd of April 2023 08:58:09 PM)
Rating: 4.3 (rated by 73 users)
Compatible devices: DEVIreg 850 IV, ERC 112D VSC, AME 55QM, AK-CS, EKC 102C2, AME 130H, FH-WC, MCX08M2.
Recommended Documentation:
Text Version of Manual, Instruction Sheet
(Ocr-Read Summary of Contents of some pages of the Danfoss ERC 101 kit Document (Main Content), UPD: 22 April 2023)
-
1, MAKING MODERN LIVING POSSIBLE EN-Instruction sheet ERC 101 kit Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014 DKRCC.EI.RL0.A3.02/520H8599 1 Technical highlights Dimensions mm Technical specications y Pre-programmed — ready to use y Compressor protection against instable voltage y High condensing tem…
-
2, Danfoss ERC 101 kit MAKING MODERN LIVING POSSIBLE EN-Instruction sheet ERC 101 kit Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014 DKRCC.EI.RL0.A3.02/520H8599 2 Assignments Assignments of inputs and outputs S2 Application S2A Application to be controlled with Sensor C. (nC=Not Connected, Sco= Temp control, EuA= Evap tem…
-
Danfoss ERC 101 kit User Manual
-
Danfoss ERC 101 kit User Guide
-
Danfoss ERC 101 kit PDF Manual
-
Danfoss ERC 101 kit Owner’s Manuals
Recommended: WRJ600UW, RE2-1R2X16U, BRAVIA KDL-32L5000
-
Emerson FISHER SR8
IntroductionThis installation guide provides instructions for installation, startup and adjustment. To receive a copy of the instruction manual, contact your local Sales Ofce or view a copy at www.sher.com. For further information refer to: Type SR8 Instruction Manual, D103100X012. PED CategoriesThis product may …
FISHER SR8 4
-
BIFFI RPD Series
Copyright © Bif. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.bif.it or from your nearest Bif Center: Bif Italia s.r.l. — Strada Bif 165, 29017 Fiorenzuola d’Arda (PC) – Italy PH: +39 0523 944 411 – bif_itali …
RPD Series 38
-
Linear Technology LT8609
1dc2195bfDEMO MANUAL DC2195BDESCRIPTIONLT8609/LT8609A42V, 2A Micropower SynchronousStep-Down Regulator Demonstration circuit 2195B is a 42V, 2A micropower synchronous step-down regulator featuring the LT8609/LT8609A. There are two assembly versions. DC2195B-A is for the LT8609A and DC2195B-B is for the LT8609. T …
LT8609 8
-
Viking C-250
The C-250 allows single line telephones or atelephone system to share a phone line with asingle Viking entry phone. Tenants may answeran entry phone call, converse with the visitorand let them in with a touch tone command.The C-250 also has a built in five number dialerto make an outside call if there is no ans …
C-250 8
Additional Information:
Operating Impressions, Questions and Answers:
Table of Contents for Danfoss ERC 101 kit:
-
MAKING MODERN LIVING POSSIBLE EN-Instruction sheet ERC 101 kit Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014 DKRCC.EI.RL0.A3.02/520H8599 1 Technical highlights Dimensions mm Technical specications y Pre-programmed — ready to use y Compressor protection against instable voltage y High condensing temperature protection y Compact design — total depth is only 46 mm y Real 16A power relay — up to 2.5 HP compressors y Automatically controlled brightness of larg
-
MAKING MODERN LIVING POSSIBLE EN-Instruction sheet ERC 101 kit Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014 DKRCC.EI.RL0.A3.02/520H8599 2 Assignments Assignments of inputs and outputs S2 Application S2A Application to be controlled with Sensor C. (nC=Not Connected, Sco= Temp control, EuA= Evap temp, Con=Cond temp {condenser cleaning}) nC Con — nc DO1 conguration o1C Relay output 1. compressor (CoP) 2. Heater HeT CoP HeT — CoP Password level1 PS1 Shop owner Most common parameters 0 99
Questions, Opinions and Exploitation Impressions:
You can ask a question, express your opinion or share our experience of Danfoss ERC 101 kit device using right now.
MAKING MODERN LIVING POSSIBLE
ERC 101 controller
Reference manual
This reference manual is intended to be used primarily by OEMs for the purpose of programming
ERC 101. It may also be useful for technicians. It is not intended as a user guide for end users.
www.danfoss.com/erc
Table of Content
1. INTRODUCTION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. CONTENT OF THE BOX
2.1 Main product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3. OVERVIEW OF THE PRODUCT
3.1 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Connector inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Connector outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Top label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4. MOUNTING
4.1 Rear mounting – Option 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2 Front mounting – Option 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Fully Integrated Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5. CONTROLLING/NAVIGATION AND ACCESS LEVELS
5.1 KoolProg/Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.2 Docking station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Manual operation with buttons (Direct Access) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.1 ERC Front and Button Functionallity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.2 Direct functions for access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.3.3 Operating the menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.3.4 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3.5 Password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2
ERC 101 Reference manual
6. CONFIGURATION OF INPUTS AND OUTPUTS
6.1 Changing input and output configuration settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.2 Program the buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.3 Set passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7. PARAMETERS
7.1 Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.2 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7.3 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.4 Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7.5 Pull down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
7.6 Condenser protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.7 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.8 Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.9 Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8. TECHNICAL SPECIFICATIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
APPENDIX
I Parameter quick list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
II Code numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
III Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
IV Typical applications – wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
IV.1 Typical applications – wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
V Application specificatons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
V.1 Control sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
V.2 Evaporator sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
V.3 Condenser sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
ERC 101 Application Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
ERC 101 Reference manual
3
1. INTRODUCTION
The ERC 101 is a multi-purpose electronic parametric controller dedicated to a broad range of applications.
ERC 101 meets OEM requirements for timesaving and flexible production setup.
The latest generation CPU, plenty of memory and high-end electronic components allow for uniquely versatile application use. Three separate password-protected user levels can be used to control more than
100 different parameters to accommodate any individual customer’s requirements.
The IP-rated body, advanced materials and internationally approved hardware design make the ERC 101 ideal for use in almost any climate around the world, indoors as well as outdoors. Laboratory work is easy and flexible with the ERC 101. With a USB-powered gateway, Danfoss KoolProg software reduces time spent programming. On the OEM assembly line, just one docking station can easily program up to 1,000 controllers a day – at zero inventory cost.
One relay control features three inputs and is powered by a globally compatible, lightweight, switch mode power supply. All components have been carefully selected to help reduce the CO2 footprint. The power supply uses on average just 0.4W – 50% less than today’s average controller.
4
ERC 101 Reference manual
2. CONTENT OF THE BOX
If delivered in a sample box the following content is shipped. The sample box is not available for other than sample purposes.
See Appendix II for code numbers and lengths.
For box lots (pcs per box), please contact your local
Danfoss representative.
2. 1 Main product
ERC 101 control unit without front frame.
NOTE:
The front frame is included in the sample box.
2.2 Accessories
Control temperature sensor: see Appendix II for different lengths and connector types.
Defrost temperature sensor: should be mounted on the evaporator. For detailed mounting instructions, please contact your local Danfoss representative.
Condenser temperature sensor: should be mounted on the condenser. For detailed mounting instructions, please contact your local Danfoss representative.
NOTE:
This sensor is not included in the sample box .
ERC 101 Reference manual – 2 CONTENT OF THE BOX
5
6
ERC 101 Reference manual – 2 CONTENT OF THE BOX
Power plug: for laboratory use, low quantity
OEM production or whenever spade connectors are not available.
Clips: are used to secure the ERC 101 in place in the case of rear mounting. They are not used with front mounting. There are two identical clips, one placed on either side of the ERC 101. See Chapter 4
– Mounting – for further details.
2.3 Connections
Programming an individual unit in a laboratory: the USB gateway requires KoolProg Software running on a PC. It enables parameters to be set in real time and an array of status information to be read (bidirectional connection). This method is used to determine the correct parameters during R&D.
Once the desired settings have been determined, a KoolProg ERC specific parameter file is saved to the
EKA183 USB copy key for later mass programming.
The USB Gateway is a laboratory tool, offering fast and easy programming of any ERC 101 controller.
KoolProg software installation is provided; the gateway is standard inventory for OEM labs.
Mass programming on an assembly line:
the docking station is used for high volume programming of ERC controllers, for example on an assembly line. The docking station is a write-only device.
See above (Programming an individual unit) for preparing the EKA183A USB copy key (code no.
080G9740), which is to be inserted into the docking station. The settings are then loaded into each successive controller in a matter of seconds.
KoolProg software is not required for mass programming.
Note:
please refer to the koolprog manual for more details about programming.
KoolProg: is the software from Danfoss for programming the ERC 101 via a USB cable and a PC rather than with the front panel buttons.
Please refer to the KoolProg manual for details.
ERC 101 Reference manual – 2 CONTENT OF THE BOX
7
3. OVERVIEW OF THE PRODUCT
The ERC 101 is a state-of-the-art, IP65 (front)-rated, multi-purpose electronic parametric controller for use in a variety of applications.
A single power relay (16A-rated) ERC 101 controls up to 2.5 HP compressors without auxiliary relay
(230V). The controller features unique algorithm for defrost control and compressor protection and is particularly well suited for use in areas with unreliable power supply and/or unstable voltage.
Together with the Danfoss docking station, programming of predetermined parameter sets can be achieved in just 10 seconds. There are over 100 parameters (see Section 7).
The ERC 101 can also be programmed via USB using the Danfoss KoolProg software, which means that the most suitable parameter findings can be located quickly during the application development process.
It is also possible to operate and program the controller using the control buttons (only when actually installed in a refrigerator / freezer).
3.1 Control buttons
The ERC 101 has four buttons (circled in image) on the front which can be programmed to perform different functions. See Chapter 6 – Configuration of inputs and outputs for detailed information.
3.2 Connector inputs
Connect up to three Danfoss original sensors according to your application needs.
There are two analogue inputs: S1and S2 ( a ).
Supported input options:
· Cabinet (air) temperature — analogue data [°C]
· Evaporator temperature — analogue data [°C]
· Condenser temperature — analogue data [°C]
· Digital input — binary data [on/off ]
There is one digital input: diC ( b ) for PC communication being used either with a door sensor or with the USB Gateway.
NOTE:
for detailed information refer to section 6.1.
The ambient light sensor can be used for determining shop open / closed times for economy mode switching, for determining the brightness of the LED display or both.
S1 S2 a b
8
ERC 101 Reference manual – 3 OVERVIEW OF THE PRODUCT
3.3 Connector outputs
One digitally controlled on/off relay.
Functions controlled are:
Compressor or heater.
3.4 Top label
The illustration shows an example of a top label affixed to an ERC 101. The examples show what is connected:
• Output 1 is used to switch the compressor on and off.
• Outputs 2 and 3 are power – Live and Neutral.
• Input D (a) is connected to a e.g. Control Sensor to measure temperature inside the cabinet.
• Input D (b) is used for Communications KoolProg software running on a PC.
• Input D(a) is connected to an e.g. Evaporator
Temperature Sensor.
NOTE:
Parameters depend on the code number supplied. Please refer to the code number specific technical drawing or use the KoolProg information menu. For other applications, a condenser sensor may be used.
DO
1(o1 )
2
3
Input /
Sensors
S1
S2 di
L
N
Cabinet
Sensor
DO1:
UL: 16FLA 72LRA,
IEC: 16(16)A
Evapor.
Sensor
Conden.
Sensor
Com .
1 2 3
DO & Input / Sensors
ERC 101A
MADE IN CHINA
080G3131
Blue Display
100-240Vac +/-10% 50/60Hz
OT 55
S1 S2 di
ERC 101 Reference manual – 3 OVERVIEW OF THE PRODUCT
9
4. MOUNTING
There are three options for mounting the ERC 101 in a freezer or refrigerator.
SAFETY INFO
Risk of electrocution!
For mounting: Do not connect mains power until the controller is correctly mounted.
For unmounting: Disconnect the power supply before unmounting.
4.1 Rear mounting – Option 1
1. Insert the ERC 101 into the cabinet.
2. Attach the clips to each side of the ERC 101.
3. Place the front frame on to the ERC 101 and click it into place.
4. Connect the sensors and outputs as required and then the power cable (see Chapter 6 – parameters for information about programming which inputs and outputs are applicable to your configuration).
10
ERC 101 Reference manual – 4 MOUNTING
4.1.1 Unmounting
1. Disconnect the power cable and then the sensors.
2. Use a flat head screwdriver and insert it carefully between the front frame and the controller.
3. Gently twist the screwdriver to remove the front frame.
Do this in four places next to each clip area.
4. Reach around the side to the clips.
Press the centre section of each clip to release them in turn. Push the controller carefully out of the cabinet.
ERC 101 Reference manual – 4 MOUNTING
11
4.2 Front mounting – Option 2
1. Connect all the cables as required (see Chapter 6
– parameters for information about programming which inputs and outputs are applicable to your configuration).
2. Insert the ERC 101 into place in the cabinet.
3. Press the front frame into place – this locks the
ERC 101 into position.
NOTE:
there is no need to use the clips for front mounting.
12
ERC 101 Reference manual – 4 MOUNTING
4.2.1 Unmounting
1. Use a flat head screwdriver and insert it carefully between the front frame and the controller.
NOTE:
Do not use a different type of screwdriver or a sharp item such as a knife which risks causing damage to your cabinet.
2. Gently twist the screwdriver to remove the front frame. Do this in four places next to each clip area.
3. Remove the front frame.
4. Push the controller carefully out of the cabinet.
4.3 Fully integrated design – Option 3
An option is available for OEMs wanting to use the ERC
101 in a fully-integrated design. Please contact your local Danfoss representative for more information.
ERC 101 Reference manual – 4 MOUNTING
13
5. CONTROLLING / NAVIGATION AND ACCESS LEVELS
The ERC 101 can be programmed in three ways: using KoolProg software, the Danfoss Docking
Station or manually by means of the buttons on the front panel.
5.1 KoolProg/Gateway
KoolProg is licenced Danfoss software offering easy parameter setup via a USB gateway. This software is supplied separately; for technical literature and further information, please contact your local
Danfoss representative.
5.2 Docking station
The ERC 101 controller docking station is supplied separately. For further information, please contact your local Danfoss representative.
5.3 Manual operation with buttons
(Direct Access)
Explained as follows:
5.3.1 ERC Front and Button Functionallity
1 Press: Variable direct function, e.g. defrost
Sub function: Back
1 Press: Temperature setpoint
Sub function: Up
^
^
1 Press: Variable direct function, e.g. on/off
Sub function: OK
1 Press: Temperature setpoint
Sub function: Down
14
ERC 101 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
5.3.2 Direct functions for access
Changing the Desired Temperature Setpoint (applies similarly when using Fahrenheit scale):
1.)
2.)
3.)
4.)
^
^
(Current temperature)
^
^
(Flashing: temperature setpoint)
^
^
(Flashing: temperature setpoint)
^
^
The display shows the current temperature.
Press: up/down to adjust setpoint
After 30 seconds, the display automatically reverts to showing the current temperature
Turning On/Off the defrost Function:
Press briefly to enter def mode
1.)
^
^
2.)
DEF ˚C
^
^
The green def symbol is lit when in defrost mode
ERC 101 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
15
Turn ON/Off ERC
1.)
Press the on/off button
5 seconds
^
^
To turn off ERC
Press the on/off button again
Acknowledging Alarms:
1.)
2.)
^
^
^
^
^
^
Flashing
Press any button to acknowlege
5.3.3 Operating the menu
Button assignments in this manual refer to the Glass Door Merchandiser default ERC 101.
For customised controls you may assign different shortcuts (ASI menu —> button configuration).
Use this feature only when the ERC 101 is supplied without button prints.
INFO:
Some parameters may be hidden to you.
When scrolling through menus, the parameters available will have been pre-determined using
KoolProg software. Your access level will determine which parameters you can view and edit.
16
ERC 101 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
Example of Changing a Parameter:
1.)
2.)
To select: press the lower left button (OK)
3.)
4.)
To confirm: press the lower left button (OK)
5.)
6.)
7.)
Press: OK to accept and return to parameter name
Press: upper left button (back) to return to parameter group
8.)
Press: upper left button (back) to return to the menu
9.)
^
^
Press and hold for 5 seconds to enter the menu
^
^
^
^
^
^
^
^
Press: up/down to scroll through the menu
(scroll through parameter groups)
^
^
^
^
Press: up/down to find the desired parameter
(scroll through group “dEf” parameters)
^
^
^
^
Press: up/down to enter the desired value
ERC 101 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
17
5.3.4 Menu structure
^
^
Press and hold 5 sec to access the menu
1. ) Parameter groups
^
^
Lower left button
2.) Alarm
^
^
Lower left button
3.) Parameter value
(scroll through menu group)
(scroll through parameters)
5.3.5 Password protection
^
^
Press and hold 5 sec to access the menu
^
^
Password protection on three levels
Level 1: Shop (daily use by shop personnel)
Level 2: Ser (service technician)
Level 3: OEM (OEM programming)
18
ERC 101 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
6. CONFIGURATION OF INPUTS AND OUTPUTS
The ERC 101 inputs and outputs are configurable by the customer. Before getting started it is a good idea to check if all inputs are configured correctly and match the sensors attached.
For instance: Danfoss supplies only 2-pole defrost sensors, so input S2 will most likely be used as a defrost / evaporator temperature sensor input.
Input and output configuration settings are part of the assignment menu (ASi).
Please contact your local Danfoss representative for information about default settings.
NOTE:
Coded sensors will impact on the number of possible configurations.
Assignments /
ASi
^
^
6.1 Changing input and output configuration settings
Two steps are needed to configure inputs:
1.
Define the type of sensor attached to the input:
— Temperature / digital
2. Define the application for the sensor:
— Temperature: control / condenser / evaporator
— Display / both
Input S1 can be attached to a temperature sensor. The sensor measures cabinet temperature.
Input S2 is attached a attached to a temperature sensor. The sensor measures evaporator temperature.
C
S1 S2 b a
Connector inputs: analogue ( a ), digital ( b )
Connector outputs ( c )
ERC 101 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
19
Assignments
S1 Config
S2 Config
S1 Application
S2 Application
DI Config
DO1 Config
Button 1 Short Config
Button 1 Long Config
Button 2 Short Config
Button 3 Short Config
Button 3 Long Config
Button 4 Short Config
Button 4 Long Config
Pass-word level1
Pass-word level2
Pass-word level3 b1C b1L b2C b3C b3L b4C b4L
PS1
PS2
PS3
ERC menu code
ASi
S1C
S2C
S1A
S2A diC o4C
Default noP
PoF dEF tP
ECo tn
Lig
0
0
0
SCo nC dio
Lig
Stn
Stn
Min tP tP tP tP tP
0
0 tP tP
0
Stn
Stn
nC
nC doC
0
Unit no no no no no no no no no no
Unit
Conv no no no no no no
Max noP
PoF noP noP
PoF noP
PoF
999
999
999 dig dig doo doo dio
Lig
Scale Default Access
Shop Ser OEM
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
RW RW RW
— RW RW
— — RW
20
ERC 101 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
S1 Config / S1C
S2 Config / S2C
Available options are:
Stn for a temperature sensor (values given in Celsius)
Dig for a digital sensor with simple on/off indication
S1 Application / S1A
S2 Application / S2A
Available options are: nC: Not connected
SCo: Temperature control
EuA: Evaporator temperature
Con: Condenser temperature (Condenser cleaning)
DI Config / diC
This is the digital input used for a digital sensor or bus communications.
bus: Modbus communication (used only for KoolProg) diO: One Wire Communication
D01 Config / D1C
CoP: Direct compressor control
Pil: Pilot Relay (No Zero Cross) – if using pilot relay to control a compressor, this option must be used instead of CoP
Het: Heating application, inverse output.
6.2 Program the buttons
Every button can be operated in 2 modes: long press short press
Button 1 Config (short press) / b1C
Lower left button
Button 1 config (long press) / b1L
Lower left button
Button 2 Config (short press) / b2C
Upper left button
ERC 101 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
21
Button 3 Config (short press) / b3C
Upper right button
Button 3 config (long press) / b3L
Upper right button
Button 4 Config (short press) / b4C
Lower right button
Button 4 Config (long press) / b4L
Lower right button
The buttons can be programmed as follows:
Short press function Long Press function
tP: Increase Setpoint tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light dEF: Toggle defrost
SuP: Toggle Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity tP: Increase Setpoint tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light dEF: Toggle defrost
SuP: Toggle Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity
Not operating
ERC power ON/OFF
6.3 Set passwords
Password level 1 / PS1
Password Level 2 / PS2
Password Level 3 / PS3
These assign passwords to the three levels of access. The password is a three-digit number. Access levels are Shop, Service and OEM. You may not therefore have access to change all the passwords. Passwords are entered by using the up and down arrow buttons.
Danfoss advises against using passwords which are easy to remember or enter, for example 111, 222, 123 etc.
NOTE:
When accessing the controller with 3 wrong password in a sequence ERC will automatically block access for 15 minutes.
22
ERC 101 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
7. PARAMETERS
This chapter details all user-accessible parameters in ERC 101 software 5.05.
NOTE:
Incorrect parameter settings can lead to inadequate cooling, excessive energy consumption, unnecessary alarms and in the case of temperaturesensitive food storage, breaches in food hygiene principles and regulations. Only a trained operator should make changes to parameters.
INFO!
Some parameters may be hidden to you. When scrolling through menus, the parameters available will have been pre-determined using KoolProg software.
Your access level will determine which parameters you can view and edit.
The access level can be set separately for each parameter using KoolProg software. There are three levels of access – 1, 2 and 3. Level 1 is for shop access, level 2 for technicians and level 3 for OEMs. The access levels cannot be set using the buttons. Passwords for the different levels can however be altered for the level of access you have – for example a level 2 user can change the password for level 1 and level 2 but not level 3.
7.1 Thermostat /
tHE
^
^
ERC 101 can handle both Celsius and Fahrenheit.
Changing from C to F and vice-versa is done in the Display menu and is shown in the display.
When the change is made, all temperature values are automatically re-calculated and updated in all other parameters accordingly.
Thermostat
Set point adjustment ratio
Differential
High Set Point
Low Set Point
Air Temp Adj.
ERC menu code
tHE
SPr diF
HSE
Default
0.5
Min
0.0
Max
1.0
Unit
Conv no
2.0
0.0
20.0
C/F r
50.0/122.0 -50.0/122.0 80.0/176.0
C/F a
LSE tAd
-35.0/-31.0 -35.0/-31.0 80.0/176.0
C/F a
0.0/0.0
0.0/0.0
20.0/36.0
C/F r
Unit
K
°C/°F
°C/°F
K/°R
Scale
.1
.1
.1
.1
.1
Default Access
Shop Ser OEM
— — RW
— RW RW
— RW RW
— RW RW
— — RW
ERC 101 Reference manual – 7 PARAMETERS
23
Set point / StP
StP is visible with KoolProg software only. This parameter defines the desired temperature (set point). In standard operation the set point is changed by simply pressing the “temperature up / down” buttons on ERC 101; for laboratory and assembly line you may opt for software controlled set point adjustment
(speed improvement)
Set point adjustment ratio / SPr
The default value is set to 0.5 and the parameter is hidden by default.
Spr defines the position of the setpoint in relation to cut-in and cut-out.
Spr = 0,5 sets the setpoint mid between cut-in and cut-out. Spr = 0 sets the setpoint at the cutout. Spr =1 sets the setpoint at cut-in.
Differential / diF
This defines the difference between the cut-out and the cut-in. The desired temperature is determined by SPr and diF.
High Set Point / HSE
Low Set Point / LSE
These parameters define the temperature range limit of the controller. Once set, the desired temperatue (setpoint) can not go above HSE or below LSE.
LSE Sets the minimum value for the set point
HSE Sets the maximum value for the set point
Cut-in and cut-out are automatically calculated from the desired setpoint (set bybuttons on the control) and the differential. By default, cut-out and cut-in are
0,5*DiF above or below the desired temperature.
Example: The desired average temperature in the cabinet is 5 degrees, and the differential is set to 2 degrees:
Air Temperature Adjustment / tAd
This parameter is a relative value and allows adjustment of the control sensor temperature.
For instance, at a measured temperature of 7*C and tAd set to -2K, the input from the control sensor will be 5*C instead.
24
ERC 101 Reference manual – 7 PARAMETERS
7.2 Alarms /
ALA
^
^
Alarm
High Alarm delay
Low Alarm delay
High Temp Alarm
Low Temp Alarm
Pulldown delay
Alarm Buzzer Duration*
Auto Clearance of
Alarm/Error
* Requires ERC 101 with integrated buzzer
ERC menu code
ALA
Htd
Ltd
HAt
Default Min Max Unit
Conv
30 0 240 no
0 0 240 no
15.0/59.0 -50.0/-58.0 80.0/176.0
C/Fa
LAt
Pdd
Abd
ACA
-50.0/-58.0 -50.0/-58.0 80.0/176.0
C/F a
240 0 960 no
0 yES
0 no
999 yES no no
Unit
°C/°F min min min min
°C/°F
Scale
.1
1
1
1
1
1
.1
Default Access
Shop Ser OEM
— RW RW
— RW RW
— RW RW
— RW RW
— RW RW
— RW RW
— RW RW
High Temp Alarm / HAt
Low Temp Alarm / Lat
High temperature alarm and low temperature alarm allow for individual alarm setpoints. Both are absolute values. By setting HAt to the maximum value and LAt to the minimum value, alarms will be deactivated.
High Alarm Delay / Htd
Low Alarm Delay / Ltd
These parameters express the number of minutes to wait before sounding an alarm once the High/Low Temp Alarm temperature is reached. Immediately prior to the alarm sounding, another check of the temperature is made to see if the temperature is still in the alarm zone; if it is not, the then the alarm is not sounded.
In most situations, the Low Alarm Delay will be set to 0 to warn about too low a temperature immediately.
ERC 101 Reference manual – 7 PARAMETERS
25
Pulldown Delay / Pdd
Normally, it is not necessary or desirable to sound an alarm during a pull down
(the initial phase of reaching the desired temperature).
This parameter prevents the High Temp Alarm HAt sounding during pull down and after a defrost for the number of minutes set for the parameter.
NOTE:
It does not apply to the Low Temp Alarm LAt.
Alarm Buzzer Duration / Abd
The ERC 101 alarm sounds for 10 seconds, followed by silence for 50 seconds. One alarm sequence therefore lasts 60 seconds. These values cannot be changed. This parameter determines how long in minutes an audible alarm will continue while there is still a reason to have an alarm. If set to 999, the alarm will continue to sound until the reason for the alarm is cleared – for example the temperature has dropped enough or the door closed. In some cases, it may be necessary for a user or technician to take action in order to clear the alarm. If set to 0, the alarm will never sound.
Auto Clear of Alarm / Error / ACA
If this parameter is set to nO:
The alarm status will not disappear automatically even if the condition which caused the alarm is no longer valid or present. If set to yES:
As soon as the condition which caused the alarm is no longer valid or present, the alarm status will automatically change back to inactive. There will be no trace of the alarm having occurred.
In general, Glass Door Merchandise applications will be set to yES and Commercial
Fridges and Freezers set to nO. For example, if the temperature goes too high for a period there may be food safety considerations in a freezer containing food but not in a fridge with cold drinks.
26
ERC 101 Reference manual – 7 PARAMETERS
7.3 Compressor /
CoP
^
^
Compressor
Min run time
Min Stop time
Max Off time
Error run time
Error stop time
Minimum Cutin voltage
Minimum cut-out voltage
Maximum voltage
Power On Delay
Power Factor
Initial cut in
Power-on temperature
ERC menu code
CoP
Crt
CSt
Cot
Ert
ESt uLi uLo uHi
Pod
PFA iCi
Pot
Default Min Max
0
0
0
0
0
0
0
0 30
30
480
60
1
0
0
270
0
0
0
0
60
270
270
270
300
0
0
-90
300
90 no no yes
-50.0/-58.0 -50.0/-58.0 50.0/122.0
no no no
C/F a no no no no
Unit
Conv no no no no
Unit min
Vac
Vac
Vac
Sec
Degree min min min min
°C/°F
Scale
1
1
1
.1
1
1
1
1
1
1
1
1
Default Access
Shop Ser OEM
— RW RW
— RW RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— RW RW
— — RW
— R- RW
— — RW
ERC 101 Reference manual – 7 PARAMETERS
27
Minimum Run Time / Crt
This parameter is a number of minutes from 0 to 30.
It determines the minimum number of minutes the compressor must run before a
Temperature cut-out can take effect. For example, if the temperature sensor indicated that the cut-out temperature has been reached, but the number of minutes set in this parameter have not elapsed since the compressor last started, then the compressor will continue. It will only stop once the duration given by Crt has been reached – provided the temperature is still low enough.
Crt thus overrides the cut-out.
Minimum Stop Time / CSt
This parameter is a number of minutes from 0 to 30.
It determines the minimum number of minutes the compressor must remain idle before a Temperature cut-in can take effect. For example, if the temperature sensor indicates that the cut-in temperature has been reached, but the number of minutes set in this parameter have not elapsed since the compressor last stopped, then the compressor will stay off. It will only start once the duration given by CSt has been reached – provided the temperature is still high enough.
CSt thus overrides the cut-in.
Maximum Off Time / Cot
This is the maximum time in minutes the compressor is allowed to idle – up to 480 minutes. Cot is set to zero by default (inactive). If ERC 101 is to be used on a draft beer (ice bank) application, this parameter can be used to control the ice thickness.
Error Run Time / Ert
Error Stop Time / ESt
These two parameters only become active in the unlikely event of a broken temperature sensor. They are then used to run the application in safety mode. At the same time the sensor error will be shown in the display.
Ert and ESt values are based on OEM experience and are by default inactive.
Ert and ESt define the duration the compressor will run (Ert) and be idle (ESt).
Example: Ert = 4 [min] and ESt = 16 [min] will provide an average cooling system activity of 20%.
Minimum cut-in voltage / uLi
Minimum cut-out voltage / uLo
Maximum voltage / uHi
These three parameters provide voltage protection to the compressor. Start by setting uHi, followed by uLo and uLi.
uLi: When the compressor is due to start, the voltage of the power supply will be checked and the compressor will only be allowed to start if it is at least the value given in this parameter.
28
ERC 101 Reference manual – 7 PARAMETERS
uLo: When the compressor is running, it will be switched off if the voltage goes below that given in this parameter.
uHi: When the compressor is running, it will be switched off if the voltage exceeds that given in this parameter. If the compressor is already stopped, it will remain switched off.
Power On Delay / Pod
This is the delay in seconds between power-on and the compressor being activated.
Depends on the Power on Temperature setting as explained below.
Power Factor / PFA
This value is hidden by default. The parameter is used by the Zero Cross function to optimize the switching position of the relay contact.
Warning:
Do not change without first consulting your local
Danfoss representative.
Initial Cut In / iCi
If the control temperature is between cut-in and cut-out at power up customers can determine if the compressor shall start immediatly (yes) or wait for cut-in temperature to start (no).
Power on Temperature / PoT
This parameter is used to accelerate the first application test on the OEM assembly line; if the cabinet temperature is higher than this parameter the Power On Delay is overruled and the outputs are activated without delay.
ERC 101 Reference manual – 7 PARAMETERS
29
7.4 Defrost /
dEF
^
^
Note:
ERC controllers feature Safe Defrost functionality (patents pending) by default.
This function ensures proper defrost under poor power conditions.
For more details please contact Danfoss.
Defrost
Def. type
Def terminate temp
Def reset temp
Def Min Interval
Def Max Interval
Def Min Time
Def Max time
Initial Defrost Interval
Initial Defrost Duration
Defrost on compressor time
ERC menu code
dEF
dFt dtt drt dii dAi dit dAt idi idd dCt
3
100 no
5
30
6
7
Default Min Max Unit
Conv no no Hgd no
6.0/42.8
0.0/32.0
25.0/77.0
C/F a
5 0 80 no
0
0
0
0
0
0 no
96
96
240
480
96
999 yES no no no no no no no
Unit hour hour min min hour
°C/°F
°C
Scale
1
1
1
1
.1
1
1
1
1
Default Access
Shop Ser OEM
— RW RW
— RW RW
— RW RW
— RW RW
— RW RW
— RW RW
— RW RW
— — RW
— RW RW
— — RW
30
ERC 101 Reference manual – 7 PARAMETERS
Defrost Type / dFt
When set to nO, the defrost function is disabled and no automatic defrosting will occur.
When set to EL or nAt, electrical, natural or off-cycle defrosting is used. An additional setting of Hgd (hot gas defrosting) is available.
Terminate Temperature / dtt
This parameter defines at what temperature the defrost cycle will stop.
The temperature is given by the evaporator sensor or by the cabinet temperature sensor if no evaporator sensor is used.
Tadd defrost reset temp / drt
The defrost counter is saved and restored at power-up, but if the temperature sensor, used for defrost, is higher than this value at power-up, it is assumed that the evaporator is free of ice and the defrost counter will be cleared.
Minimum Interval / dii
This parameter can be set to between 0 and 96 hours and defines the minimum time period between the start of two defrost cycles. Once the minimum interval has expired, the defrost cycle will start at the following cut-out or once the maximum interval dAi has been reached.
Maximum Interval / dAi
This parameter can be set to between 0 and 96 hours and defines the maximum time period between the start of two defrost cycles.
Minimum Time / dit
This parameter can be set to between 0 and 240 hours and defines the minimum duration of a defrost cycle. During this period, the ERC 101 will not check the temperature. Once the minimum time has expired, the temperature will be checked and if the Terminate Temperature dtt has been reached, the defrost cycle will end.
If dtt has not been reached, defrost will continue until either dtt is reached or the
Maximum Time dAt reached, whichever occurs first.
Maximum Time / dAt
This parameter can be set to between 0 and 240 minutes and defines the maximum duration of a defrost cycle.
The ERC 101 will not allow a maximum time to be entered which is less than the minimum time, or a minimum time which is more than the maximum time.
ERC 101 Reference manual – 7 PARAMETERS
31
Initial Defrost Interval / idi
This parameter defines defrost behaviour after power-on. It can be set to between
0 and 96 hours and determines when the first defrost cycle will start after powerup. Setting this parameter to a low value will force a defrost cycle to start earlier, for example for testing purposes. The timer monitoring the defrost interval will not be reset by a subsequent loss of power, but it will continue to count once power is restored.
Initial defrost duration / idd
The “initial defrost” functionality is being used for factory testing for acceleration measures. This featured may not be desired under normal operation, you may decide to deactivate this function by setting a maximum number of compressor cycles (0 — 999).
0: idi always off
1-998:number of cycles before deactivation 999: idi always on
Defrost On Compressor Time / dCt
If this parameter is set to yES, then defrost cycles are based on the total time the compressor has been running.
If this parameter is set to nO, then defrost cycles are related to elapsed time, regardless of how long and how often the compressor has been on.
32
ERC 101 Reference manual – 7 PARAMETERS
7.5 Pull Down /
Pud
^
^
Pull down (sometimes known as Super Cool) is a procedure for improving cooling performance, accelerating the time used to reach the desired temperature. Pull Down settings overrule all other settings.
Pull Down
Pull-down Initiate
Temperature
Pull-down Cycling
Pull-down defrost Interval
Pull-down duration
Pull-down limit temp
Pull-down reduction temp
ERC menu code
Pud
Pit
Default Min Max Unit
Conv
50.0/122.0 -40.0/-40.0 50.0/122.0
C/F a
PCy
Pdi
Pdd
PLt
Prt
30
15
24
0
0
0
360
48
48 no no no
0.0/32.0 -55.0/-67.0 55.0/131.0
C/F a
0.1/0.2
0,0 10.0/16.0
C/F r
Unit
°C/°F min hour hour
°C/°F
K/°R
Scale
.1
1
.1
.1
1
1
Default Access
Shop Ser OEM
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
Pull Down Initiate Temperature / Pit
This parameter indicates the temperature which causes a pull down to start. If the temperature measured inside the cabinet exceeds this value for longer than one hour, then pull down will start. The compressor will have already cut-in, so the only effect is to stop defrost cycles until the desired temperature is reached. The period of one hour is fixed and cannot be altered.
ERC 101 Reference manual – 7 PARAMETERS
33
Pull Down Cycling / PCy
This is the duration in minutes of the compressor cycling at the reduced set point temperature. Once the desired Pull Down Limit Temperature PLt has been reached during Pulldown, the compressor will continue to cycle on / off for the duration of
PCy. At the end of the period defined by PCy, the Set Point temperature will return to normal and Pulldown will cease.
Pull Down Defrost Interval / Pdi
Even though most applications do not need Defrost during Pull Down, an extended defrost during pull down can be applied. This is the time between defrost cycles during Pull Down. It is measured in hours and can be up to 48 hours.
During Pull
Down, this setting overrides the Defrost Interval and Defrost Time settings (see the
Defrost section).
Pull Down Duration / Pdd
You can choose to limit the maximum Pull Down time. Once this time value
(max. 48 hours) is reached, Pull Down will stop regardless of whether the desired pull-down temperature has been reached.
Pull Down Limit Temperature / PLt
This parameter sets the minimum allowed temperature during pull-down,
In order to protect valuable contents you must always specify the absolute minimum temperature allowed in your application.
For Glass Door Merchandisers 0°C/32°F protects bottles from freezing; for Commercial Fridges you may opt for a slightly higher temperature (e.g. 2°C)
Pull Down Reduction Temperature ∆t / Prt
ERC 101 calculates a lower set-point during Pull Down mode to increase the cooling capacity of your appliance.
For each hour the cabinet temperature is above the
Pull down initiate temperature, the set-point is reduced with the value of Prt.
34
ERC 101 Reference manual – 7 PARAMETERS
7.6 Condenser Protection /
Con
^
^
NOTE:
A condensor temperature sensor is required to use these parameters.
Condenser protection is generally used in dusty environments where the condenser may accumulate a layer of dust or dirt and therefore be at risk of overheating.
Condenser Protection
Condenser Alarm Limit
Condenser Block Limit
Condenser OK limit
Condenser Low Limit
ERC menu code
Con
CAL
CbL
CoL
CLL
Default
80/176
85/185
60/140
5
Min
0/32
0/32
0/32
-20/-4
Max
85/185
85/185
85/185
20/68
Unit
Conv
C/F a
C/F a
C/F a
C/F a
Unit
°C/°F
°C/°F
°C/°F
°C/°F
Scale
1
1
1
1
Default Access
Shop Ser OEM
— — RW
— — RW
— — RW
— — RW
Condenser Alarm Limit / CAL
This parameter sets the temperature for the condenser at which an alarm will be generated.
Condenser Block Limit / CbL
This parameter sets the temperature which if reached will cause the compressor to switch off.
Condenser OK Limit / CoL
This parameter sets the temperature at which the compressor is allowed to start again after the temperature set in CbL above has been exceeded and the compressor stopped.
Condenser Low Limit / CLL
This parameter sets the lowest (condenser) temperature at which the compressor is allowed to start.
ERC 101 Reference manual – 7 PARAMETERS
35
7.7 Display /
diS
^
^
Display
Display Unit
Display Resolution
Display Range Limit
Display Delay
Display Offset
Lock-time After defrost
Show Pull Down state
Show Defrost
Display Intensity
ERC menu code
diS
CFu rES rlt ddL doF dLt
SSC
SdF din
Default Min Max
-C
0.1
-C
0.1
-F
1 no
0 no
0 yES
10
0.0/0.0
-10.0/-18.0 10.0/18.0
15 0 60 no yES
10 no no
1 yES yES
10
Unit
Conv no no no no
C/F r no no no no
Unit
Sec
K/ o
R min
Scale
1
1
1
Default Access
Shop Ser OEM
RW RW RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
RW RW RW
This section deals with parameters for the display.
NOTE:
Some display parameters can be set in such as way that they may be illegal in some jurisdictions. Please check local legislation.
36
ERC 101 Reference manual – 7 PARAMETERS
Display Unit / CFu
This parameter sets the display to Fahrenheit or Celsius. Switching from one to the other will cause all temperature settings to be automatically updated accordingly.
Display Resolution / rES
This parameter can be set to 0.1, 0.5 or 1 and affects the way the temperature is displayed. With the parameter set to 1, the display will only ever show temperatures rounded to the nearest whole degree. At 0.5, it will round the temperature to the nearest half degree for display.
For example, 3.3 degrees will be shown in the display as 3.5 degrees and 3.9 as 4.0.
With the parameter set to 0.1, no rounding occurs.
This parameter does not affect the temperature itself, merely the display.
Display Range Limit / rLT
In some Point of Sales applications you may want to show the desired instead of the real temperature. This parameter sets whether the displayed temperature is the actual temperature or whether it is restricted to the cut-in / cut-out limits. Set to nO means that the actual temperature will de displayed.
The parameter is set to nO by default.
Display Delay/ ddL
In order to provide a realistic temperature appearance for an application, a display delay can be set.
The parameter sets the time constant τ (tau) of the moving average filter for the display.
Physically, one time constant represents the time it takes the system’s step-response to reach 66% of its final value and five time-constants the time it takes to reach 99% of its final value.
The parameter can be set from 0 to 10 minutes.
ERC 101 Reference manual – 7 PARAMETERS
37
Display Offset / doF
This parameter is a relative value and allows the temperature displayed to be different to the temperature measured. For instance, at a measured temperature of 7°C and doF set to -2K, the displayed temperature will be 5°C instead.
Lock Time After Defrost / dLt
In order not to show a rising temperature during defrosting, the displayed temperature is locked at the temperature shown at the start of the defrost cycle for the number of minutes set in this parameter.
0 = no lock.
Show Pull down state / SSC
If set to yES, this parameter causes the display to show SC when the system is in
Pull Down mode.
If set to nO, the temperature continues to be displayed.
Show Defrost / SdF
If set to yES, this parameter causes the display to show DEF when the system is in defrost mode. If set to nO, the temperature continues to be displayed.
Display Intensity / din
ERC 101 can have its display intensity (brightness) set. This requires that buttons are configured accordingly.
38
ERC 101 Reference manual – 7 PARAMETERS
Assignments
S1 Config
S2 Config
S1 Application
S2 Application
DI Config
DO1 Config
Button 1 Short Config
Button 1 Long Config
Button 2 Short Config
Button 3 Short Config
Button 3 Long Config
Button 4 Short Config
Button 4 Long Config
Pass-word level1
Pass-word level2
Pass-word level3
7.8 Assignments /
ASi
For more details on how to set parameters
— see chapter 6.
b3C b3L b4C b4L o4C b1C b1L b2C
ERC menu code
ASi
S1C
S2C
S1A
S2A diC
PS1
PS2
PS3
Default
0
0
0 tP
ECo tn
Lig
Lig noP
PoF dEF
Stn
Stn
SCo nC dio
Min
0
0
0 tP tP tP tP
0 tP tP tP
Stn
Stn
nC
nC doC
Unit no no no no no no no no no no no no
Unit
Conv no no no no
Max noP
PoF noP
PoF
999
999
999
Lig noP
PoF noP dig dig doo doo dio
Scale Default Access
Shop Ser OEM
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
— — RW
RW RW RW
— RW RW
— — RW
ERC 101 Reference manual – 7 PARAMETERS
39
7.9 Service Information /
Ser
^
^
The parameters in the following section are READ
ONLY and cannot be changed by the user. They provide information for technicians and OEM users.
Service
DI
Voltage value
DOs Status
Relay 1 counter interval Counter
Defrost time counter
SW version
HW version
OrderNoLow
OrderNoHigh
Parameter version
Last change
Manufacturing date
Copy Key ID
Set as Default
CHA
CHd
Cid
SFC
HAr
OnL
OnH
PAr
ERC menu code
SEr
Sdi uAC ouS rL1 int dnt
Fir
Default Min
—
—
—
SWVER
—
—
—
HWVER
ORNOL
-32768
-32768
ORNOH -32768
PARVER -32768
0 no
0
0
0
0
0 no oFF
0
IIII
0
0
0
-32768
Max
999
999
999 yES
32767
32767
32767
32767
999
999
999
32767 on
270
IIII no no no no no no no no no no no no
Unit
Conv no no no
Unit
1000 min min
Vac
Scale
1
1
1
1000
1
1
1
Default Access
Shop Ser OEM
— R- R-
— R- R-
— R- R-
— R- R-
— R- R-
— R- R-
R- R- R-
R- R- R-
— — —
— — —
R- R- R-
— — —
— R- R-
— — R-
RW RW RW
40
ERC 101 Reference manual – 7 PARAMETERS
8. TECHNICAL SPECIFICATIONS
Power Supply
Rated Power
Input
Output
Compressor
Probes
Connectors
Programming
Assembly
Display
Keypad
Operating Conditions
Storage Conditions
Measurement Range
Protection
Environmental
Resistance to Heat & Fire
EMC Category
Operating Cycles
* customized
Approvals
Dimensions:
100 — 240 VAC (±10%), 50-60 Hertz, switch mode power supply
Less than 0.5 W
3 Inputs: 2 Analogue & Digital, 1 Digital; user specific assignment
• Air / Evaporator / Condenser • Door sensor: All types, user specific
• DP for remote communication
• Danfoss NTC evaporator temperature probes
• Danfoss ambient light sensor
• Danfoss NTC cabinet temperature probes
• Danfoss NTC condenser temperature probes
• Danfoss PIR sensor*
EN60730 UL60730
120Vac: 16A resistive/ FLA16 / LRA72.
240Vac: 10A resistive /FLA10 /LRA60.
16(16)A
Danfoss NTC sensors and Danfoss ERC accessories
Modular connector system for OEM customers, with optional output screw terminal adapter. Input connector type:
Rast 2.5 Edge connectors. Output connector type: RAST 5 Standard
Lab programming: Danfoss USB Gateway with KoolProg Software. Assembly line programming: Danfoss ERC docking station. Offline programming: 4 push buttons
3 types (all ERC 101 controls): front mounting (patents pending); brackets; fully integrated solution (requires ’’OEM specific’’ design of mounting hole)
LED 7 inch display, 3 digits, decimal point and ’’multi functionality’’ icons; °C/F scale. Available in various colours
4 buttons (integrated IP65 design), 2 left, 2 right; user programmable
0 °C to 55 °C, 93% rH
-40 °C to 85 °C, 93% rH
-40 °C to 85 °C
Front: IP65 / Rear: water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to
IP00
Pollution degree III (can be mounted inside a refrigerated cabinet), non-condensing
Category D (UL94-V0)
Category I
Compressor relay: more than 175,000 at full load (16A (16A))
R290/R600a : EN/IEC 60079-15:2005
Glow wire according to EN/IEC 60335-1
IEC/EN 60730
UL60730
NSF
CQC
GOST R 60730
Note: These approvals are only valid when using the accessories listed in this document
IMPORTANT NOTE
The inputs are not galvanic separated and are connected directly to the mains supply!
^
^
36,5 mm
28,5 mm
71 mm
78,25 mm
47,25 mm
51,25 mm
28 mm
71 mm
30 mm
Rear mounting
ERC 101 Reference manual – 8 TECHNICAL SPECS
41
APPENDIX I: PARAMETER QUICK LIST
Thermostat
Set point adjustment ratio
Differential
High Set Point
Low Set Point
Air Temp Adj.
ERC menu code
tHE
SPr diF
HSE
LSE tAd
Description
Thermostat settings
Current setpoint adjustment value diF * SPr
Thermostat differential
Upper limit of thermostat set point
Lower limit of thermostat set point
Applies to non-Danfoss temperature sensors only
Alarm
High Alarm delay
Low Alarm delay
High Temp Alarm
Low Temp Alarm
ERC menu code
ALA
Htd
Ltd
HAt
LAt
Pulldown delay
Alarm Buzzer Duration *
Pdd
Abd
Auto Clearance of
Alarm/Error
ACA
* Requires ERC 101 with integrated buzzer
Description
Alarm settings
Alarm delay on high temperature
Alarm delay on low temperature
Alarm is activated above this temperature (Celsius)
Alarm is activated below this temperature (Celsius)
Alarm delay during pulldown (0-960 minutes) (high temperature only)
Alarm buzzer duration in minutes (0=no buzzer) yES: alarm auto-clears if system returns to normal; nO : alarm state maintained regardless
Compressor
Min run time
Min Stop time
Max Off time
Compressor door open delay
Error run time
Error stop time
Minimum Cutin voltage
Minimum cut-out voltage
Maximum voltage
Power On Delay
Power Factor
Initial cut in
Power-on temperature uLi uLo uHi
Pod
PFA iCi
ERC menu code
CoP
Crt
CSt
Cot
Cdd
Ert
ESt
Description
Pot
Compressor settings
Minimum time compressor must run 0-30 minutes
Min time compressor must idle 0-30 minutes
Max time compressor must idle 0-480 minutes
Minutes before compressor stops when door opened
Compressor run time if temperature sensor is not working (0-60 minutes)
Compressor stop time if temperature sensor is not working (0-60 minutes)
When compressor is off: Lowest compressor start voltage (0-270 V)
When compressor is on: Lowest operation voltage (0-270 V)
When compressor is on: Highest operation voltage (0-270 V)
Delay in seconds after power-on before outputs active (change with care)
Phasic angle in degrees. Changing this may give decreased relay lifetime
Control temperature is between cut-in and cut-out at power up.
YES: Compressor cuts in No: Compressor off until cut-in temperature reached.
If the temperature of compressor at power-on exceeds this then Power On Delay does not apply
42
ERC 101 Reference manual – APPENDIX I: PARAMETER QUICK LIST
Defrost
Def. type
Def terminate temp
Def reset temp
Def Min Interval
Def Max Interval
Def Min Time
Def Max time
Initial Defrost Interval
Initial Defrost Duration
Defrost on compressor time dAt idi idd dii dAi dit
ERC menu code
dEF
dFt dtt drt dCt
Description
Defrost Settings
no: Defrost function is disabled
EL: Electrical or time defrost
Hgd: Hot gas defrost (contact Danfoss for details) nat:Off-cycle defrost (natural defrost)
Temperature at which defrost cycle will stop
Temperature determines if defrost timer is reset or continued at power up.
Evaporator sensor has higher priority than control sensor
0-79: temp value upon which timer is reset
80: Disable drt function
The minimum time in hours between the start of each defrost cycle
The maximum time in hours between the start of each defrost cycle
The minimum duration of a defrost cycle in minutes
The maximum duration of a defrost cycle in minutes
The number of hours after power-up before the first defrost cycle starts
Number of cycles after which initial defrost functionality will be disabled.
0: idi always off
1-998: number of cycles before deactivation 999: idi always on
Whether the defrost cycles are measured by elapsed time (nO) or compressor run time (yES)
Pull Down
Pull-down Initiate
Temperature
Pull-down Cycling
Pull-down defrost Interval
Pull-down duration
Pull-down limit temp
Pull-down reduction temp ∆t
ERC menu code
Pud
Pit
Description
Pull down settings
If the cabinet temperature is above this temperature for >1h, pull-down mode is activated
PCy
Pdi
Pdd
PLt
Prt
Minimum duration [min] of the pull-down mode, starting at PiT
Defrost interval during pull-down. Over-rules the defrost interval in normal mode.
Maximum duration [min] of the pull-down mode, starting at PiT
A safety feature; the lowest temperature allowed during pull-down.
A calculation value for pull-down performance improvement. Instructions: See manual
Condenser Protection
Condenser Alarm Limit
Condenser Block Limit
Condenser OK limit
Condenser Low Temp.
Limit
ERC menu code
Con
CAL
CbL
CoL
CLL
Description
Condenser protection settings
If condenser sensor exceeds this temperature, alarm is activated
If this temperature is exceeded, compressor will be stopped.
Temperature at which compressor may start after a stop due to exceeding CbL
Temperature below which the compressor is not allowed to start
ERC 101 Reference manual – APPENDIX I: PARAMETER QUICK LIST
43
Display
Display Unit
Display Resolution
Display Range Limit
Display Delay
Display Offset
Lock-time After defrost
Show Pull Down state
Show Defrost
Display Intensity
ERC menu code
diS
CFu rES rlt ddL doF dLt
SSC
SdF din
Description
Display settings
F: Fahrenheit; C: Celsius
Display resolution for temp: 0.1, 0.5 or 1.0 C/F
Limits displayed temperature to actual setpoint +/- differential; may be illegal in some countries
Time period for moving average temperature display
Display a different temperature relative to measured temperature
Display lock time after defrost [0-60 min] yES: “SC “ will be displayed during Pull down; nO: “SC “ will not be displayed.
yES: display will show deF during defrost ; no: Display will show temp
Display intensity when no ambient sensor; min intensity with sensor
Assignments
S1 Config
S2 Config
S1 Application
S2 Application
DI Config
DO4 Config
ERC menu code
ASi
S1C
S2C
S1A
S2A
Description
Assignment of inputs and outputs
Sensor type input 1 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input
Sensor type input 2 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input
Application to be controlled with Sensor D. nC: Not connected
SCo: Temperature control
EuA: Evaporator temperture
Con: Condenser temperature (Condenser cleaning)
LS1: Light sensor(Ldr), Luminens, delicated for Economy detection
LS2: Light sensor(Ldr), Luminens, delicated for LED intensity scope
LS3: Light sensor(Ldr), Luminens, delicated for both Economy detection and LED intensity scope doC: Door contact, Contact closed when door closed doo: Door contact, Contact open when door closed
Application to be controlled with Sensor C. nC: Not connected
SCo: Temperature control
EuA: Evaporator temperture
Con: Condenser temperature (Condenser cleaning) doC: Door contact, Contact closed when door closed doo: Door contact, Contact open when door closed diC o4C
Sensor A (digital) doC: Door contact, Contact closed when door closed doo: Door contact, Contact open when door closed dio: One wire digital communication buS: MODBUS communication nO: Not used; ALA: Alarm output; Lig: Light control
44
ERC 101 Reference manual – APPENDIX I: PARAMETER QUICK LIST
Assignments
Button 1 Short Config
Button 1 Long Config
Button 2 Short Config
Button 3 Short Config
Button 3 Long Config
Button 4 Short Config
Button 4 Long Config
Pass-word level1
Pass-word level2
Pass-word level3 b2C b3C b3L b4C b4L
PS1
ERC menu code
ASi
b1C b1L
Description
Assignment of inputs and outputs
Config of key 1 short, lower left tP:Increase Setpoint tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light dEF: Toggle defrost
SuP: Toggle Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity noP: Not operating
Config of key 1 long, lower left tP:Increase Setpoint tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light dEF: Toggle defrost
SuP: Toggle Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity noP: Not operating
PoF: ERC power ON/OFF
PS2
PS3
Config of key 2 short, upper left, as key 1 short
Config of key 3 short, upper right, as key 1 short
Config of key 3 long, upper right, as key 1 long
Config of key 4 short. lower right, as key 1 short
Config of key 4 long. lower right, as key 1 long
Shop owner
Most common parameters for instance real time clock, day/night mode etc. (0 means disabled)”
Service technician all parameters with read permission and possibility to change a number of parameters like defrost, fan etc(0 means disabled)
“OEM Customer
All parameters read and write permission, but with some restriction to, for instance, reset statictical information. (0 means disabled)
ERC 101 Reference manual – APPENDIX I: PARAMETER QUICK LIST
45
Service
DI
Voltage value
DOs Status
Relay 1 counter interval Counter
Defrost time counter
Serial numbe
SW version
HW version
OrderNoLow
OrderNoHigh
Parameter version
Last change
Manufacturing date
Copy Key ID
Set as Default
CHA
CHd
Cid
SFC
HAr
OnL
OnH
PAr rL1 int dnt
Snu
Fir
ERC menu code
SEr
Sdi uAC ouS
Description
Service
DI: physcial DI pin state (ON; OFF)
Current main power supply voltage
Current relay open / closed status.
IIII = All Relay on (Upper bar for on, Lower bar for off )
II = DO1 On, DO2 Off, DO3 & DO4 NA (No bar if relay not mounted)
IIII = All Relay off (Upper bar for on, Lower bar for off )
Thousands of cycles of compressor relay since manufacture
Compressor run time since last defrost
Duration of last defrost cycle [min]
Serial number given at manufacturing
Danfoss software version number
Danfoss hardware version number
Danfoss order code number
Danfoss order code number
OEM parameter version number [requires EKA copy key update]
Not used
Programme date WWY: week number and year number (2010-19)
Copy key used for last program
Resets all parameters to last good OEM settings
46
ERC 101 Reference manual – APPENDIX I: PARAMETER QUICK LIST
APPENDIX II: CODE NUMBERS
Type
Code no. I-Pack
Approvals
230V, CQC/UL/CE
Controller
ERC 101 RED LED, CQC only
ERC 101 RED LED, UL, CE and CQC
ERC 101 BLUE LED, UL, CE and CQC
Evaporator/Defrost sensor
PVC Standard (C2), 1500 mm, 2-pole
PVC Standard (C2), 2000 mm, 2-pole
PVC Standard (C2), 3000 mm, 2-pole
080G3030
080G3130
080G3131
077F8790
077F8794
077F8798
Type
Programming
OEM Docking station, production line
Copy stick EKA 103A
Gateway including USB Cable for R&D
Mounting Clamps
Black (2 needed per controller)
Power-plug
Lumberg,3 pole
Other sensors
TPFE low temp (C1), 1000 mm, 3-pole
TPFE low temp (C1), 2000 mm, 3-pole
TPE precision (C1), 500 mm, 3-pole
TPE precision (C1), 1000 mm, 3-pole
TPE precision (C1), 1500 mm, 3-pole
TPE precision (C1), 2000 mm, 3-pole
TPE precision (C1), 2500 mm, 3-pole
TPE precision (C1), 3000 mm, 3-pole
077F8657
077F8665
077F8724
077F8725
077F8726
077F8727
077F8728
077F8729
(C): Connector type
* Defrost sensors can also be used as condenser sensors.
Note:
For more information about temperature sensor types and connectors, please refer to Danfoss’ technical brochure “NTC type temperature sensors for ETC & ERC controllers”
Code no. I-Pack
Approvals
230V, CQC/UL/CE
080G9701
080G9740
080G9711
080G3308
080G3364
ERC 101 Reference manual – APPENDIX II: CODE NUMBERS AND LENGHTS
47
APPENDIX III: TROUBLESHOOTING
Problem
Compressor does not start
Defrost does not start I
Defrost does not start II
Alarm does not sound
E01 or E02 is shown on display
Display alternates between Con and temperature
Display alternates between Hi and temperature
Display alternates between Lo and temperature
Display shows dEf
Probable cause
Waiting for compressor delay timer
Defrost in progress
Line voltage to compressor too low or too high
The temperature has been higher than the defrost reset temperature, which will cause the defrost counter to reset.
Note: If no evaporator sensor is attached, the air temperature in the cabinet will be used for defrost.
Controller in pull-down mode
Check parameter dEF-> drt
Alarm delayed or buzzer is not enabled.
Defrost might be delayed during pull-down
Check parameter Pud->Pdi
Check ALA->Htd, Abd
Check Pud->Pdd
Check ALA-> Abd
Replace sensor E01: Sensor S1 defective
E02: Sensor S2 defective
Condenser temperature exceeds the temperature set in condenser settings menu
Temperature too high
Clean condenser
Check Con->CAL, CbL
Check ALA->HAt
Temperature too low
Defrost in progress
Remedy
Check CoP->CSt
Check CoP->Pot /Pod
Check dEF->dit, dot
Check CoP->uLi, uLo, uHi
Check ALA-> LAt
Check diS->SdF
48
ERC 101 Reference manual – APPENDIX III: TROUBLE SHOOTING
APPENDIX IV: TYPICAL APPLICATIONS – WIRING DIAGRAMS
ERC 101A
Glass Door Merchandiser
100 – 240VAC SMPS
L N
ERC 101A Controller
ERC 101 RED LED, CQC only
ERC 101 RED LED, UL, CE and CQC
ERC 101 BLUE LED, UL, CE and CQC
Code nr.
080G3030
080G3130
080G3131
DO1
1 2 3
DO’s
ERC101A
Controller
AI/DI’s S1 S2 di
Temperature Sensor for Cabinet
Temperature Control
PVC Standard
Connector type (C1)
3-pole
470 mm
1000 mm
1500 mm
2000 mm
2200 mm
3000 mm
Code nr.
077F8751
077F8757
077F8761
077F8765
077F8767
077F8769
Temperature Sensor for Condenser
Temperature Control
PVC Standard
Connector type
(C2)
2-pole
470 mm
Code nr.
1000 mm
1500 mm
2000 mm
3000 mm
077F8780
077F8786
077F8790
077F8794
077F8798
ERC 102 Reference manual – 8 TYPICAL APPLICATIONS – WIRING DIAGRAMS
49
APPENDIX V: APPLICATION SPECIFICATON
V.1 Control sensor
The control sensor must always be connected and is used for controlling the cut-in and cut-out of the compressor according to the set-point. The sensor is also used for the displayed temperature.
Placement of sensor:
Vertical coolers with fan
Most common placement is in the return air to the evaporator. The sensor can be placed close to the fan – even when the fan is pulsed during compressor off periods: The updating of the temperature is blocked when the fan is stopped and only updated when the fan has been running for a while, so that the heat from the fan does not affect the temperature reading.
For applications sensitive to sub-zero temperatures, sensor placement in the evaporator outlet air can be considered.
Vertical freezers with fan
Placement in the return air or in the freezer compartment
Coolers without fan
the best results are normally obtained when the sensor is placed at the side-wall, 10 cm from the back and approximately at 1/3 from the bottom or where the evaporator ends.
The control sensor must always be connected and is used for controlling the cut-in and cut-out of the compressor according to the set-point. The sensor is also used for the displayed temperature.
50
ERC 101 Reference manual – APPENDIX V: APPLICATION SPECIFICATION
V.2 Evaporator sensor
The evaporator sensor is only used for de-icing of the evaporator and has no control purpose.
Placement of sensor:
Place the sensor where the ice melts last.
Please be aware of that sharp finns can damage the cable.
V.3 Condenser sensor
The condenser sensor is used to protect the compressor against high pressure when the condenser is blocked or the condenser fan fails.
Placement of sensor:
Place the sensor at the liquid side of the condenser.
Use a metal bracket or metal tape to ensure good thermal conductivity. Be sure that the cable does not pass hot spots at the compressor or condenser that exceeds 80°C.
ERC 101 Reference manual – APPENDIX V: APPLICATION SPECIFICATION
51
ERC 101 Application Matrix
Application
Standard Beverage cooler
Out-door beverage cooler
CFF Refrigerator
CFF Freezer
Static evaporator
Type
ERC101A
ERC101A
ERC101A
ERC101A
Output
DO1
Comp
Comp
Comp
Comp
S1 (C1)
Control
Control
Control
Control
Input
S2 (C2)
Defrost or
Condenser
Defrost or
Condenser
Defrost or
Condenser
Condenser
Di (C4)
—
—
—
—
NOTE:
• Select only one function per input, e.g. condenser sensor or defrost sensor.
• Make sure that the accessory you select has a matching connector to the input, e.g. a sensor for input S2 must have C2 connector
• Condenser sensor or defrost sensor are optional and can be omitted
DKRCC.PS.RL0.B2.02 / 520H8608
Copyright Danfoss A/S www.danfoss.com –
03/2014
MAKING MODERN LIVING POSSIBLE
EN-Instruction sheet ERC 101 kit
Produced by Danfoss A/S (EL—MSSM/AZ) | March 2014 DKRCC.EI.RL0.A3.02/520H8599
1
Technical highlights
Dimensions mm
Technical specications
y Pre-programmed — ready to use
y Compressor protection against instable voltage
y High condensing temperature protection
y Compact design — total depth is only 46 mm
y Real 16A power relay — up to 2.5 HP compressors
y Automatically controlled brightness of large-size LED display
y Fully compatible with ammable refrigerants (R290)
y Moisture protection (housing & coating)
y Advanced defrost algorithms
FEATURES DESCRIPTION
Power supply
100 VAC — 240 VAC 50-60 Hertz, automatic switch mode
power supply
Rated power Less than 0.5 W
2 analogue inputs
Danfoss NTC Air temperature probes
Danfoss NTC Condenser
temperature probes (optional)
Output compressor
relay
16 (16A) EN60730; 16 (16A) CQC;
16A (16A FLA/72A LRA) UL60730
Display
LED display, 3 digits, decimal point and
multi functionality icons, °C scale
Operating
conditions
0 °C to 55 °C, 93% rH
Storage conditions -40 °C to 85 °C, 93% rH
Measurement range -40 °C to 85 °C
Protection
Front: IP65/Rear: water and dust protection
corresponds to IP31, accessibility of connectors limit
rear part rating to IP00
Environmental
Pollution degree III
(can be mounted inside a refrigerated cabinet),
non-condensing
Resistance to heat
& re
Category D (UL94-V0)
EMC category Category I
Operating cycles
Compressor relay:
more than 175,000 at full load ((16A) 16A)
Approvals
R290/R600a: EN/IEC 60079-15:2005,
Glow wire according to EN/IEC 60335-1,
IEC/EN 60730, UL60730, NSF, CQC, GOST R 60730
Note: These approvals are only valid when using the
accessories listed in this document
^
^
78.25 mm
47.25 mm
rear mounting
36.5 mm
28 mm
30 mm
71 mm
Input/output
DO1:
UL: 16FLA 72LRA,
IEC: 16(16)A
100-240VAc +/-10% 50/60Hz
OT 55
DO
1(o1)
2
S1
S1 S2
S2
3
Input/
Sensors
Cabinet
Sensors
Evapor.
Sensors
Conden.
Sensors
DO & Input/Sensors
1 2 3
L
N
ERC 101
controller
Safety info
Risk of electrocution!
For mounting: do not connect mains power until the controller is correctly mounted.
For unmounting: disconnect the power supply before unmounting
Installation
Operation menu
y Insert the ERC 101 in to the cabinet
y Attach the clips to each side of the
ERC 101
Display/operation
Press BRIEFLY to defrost
Press UP/DOWN to
adjust setpoint
Flasching
Press any button to acknowlege
The green def symbol is list
when in defrost mode
Press the button
5 seconds to ON/OFF
^
^
^
^
Press: variable direct function defrost
Sub function: BACK
Press: tempearture setpoint
sub function: UP
Press: upper left button BACK
to return to parameter group
Press and hold for 5 seconds
to enter the menu
Press: UP/DOWN to scroll
through the menu
To select: press the lower
left button (OK)
Press: variable direct functionON/OFF
Sub function: OK
Press: tempearture setpoint
sub function: DOWN
Press 5 sec both right buttons
to access the menu
1) Parameter groups
Higher left button to exit
Lower left button to conrm
Scroll through the
parameters group
Scroll through the
menu group
2) Parameter name
3) Parameter value
^
^
^
^
Higher left button to exit
Lower left button to conrm
^
^
IMPORTANT NOTE
The inputs are not galvanic separated and are connected directly to
the mains supply! For that reason, door-switches, sensors as well as the cables must full the reinforced
insulation requirements.