MAKING MODERN LIVING POSSIBLE ERC 102 refrigeration controller Reference manual This reference manual is intended to be used primarily by OEMs for the purposes of programming ERC 102. It may also be useful for technicians. It is not intended as a user guide for end users. www.danfoss.com/erc Table of Content 1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2. CONTENT OF THE BOX 2.1 Main product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3. OVERVIEW OF THE PRODUCT 3.1 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3.2 Connector inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3.3 Connector outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.4 Top label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 4. MOUNTING 4.1 Rear mounting – Option 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Front mounting – Option 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Fully-integrated design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 11 12 13 13 5. CONTROLLING/NAVIGATION 5.1 KoolProg and Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Docking station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Manual operation with buttons (Direct Access) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.1 ERC Front and Button Functionallity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.2 Direct functions for access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.3 Operating the menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.4 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.5 Password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 14 14 14 15 16 18 18 6. CONFIGURATION OF INPUTS AND OUTPUTS 6.1 Changing input and output configuration settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Program the buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3 Set passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 Set lighting function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 22 23 23 2 ERC 102 Reference manual 7. PARAMETERS 7.1 Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4 Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.6 Energy management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.7 Pull down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.8 Automatic heater control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.9 Condenser protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.10 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.11 Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.12 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 26 28 31 35 35 37 38 39 40 42 43 8. TECHNICAL SPECS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 APPENDIX I Parameter quick list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II Code numbers and lenghts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . III Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IV Typical applications – wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IV.1 Typical Wiring Diagram, ERC 102D, Glass Door Merchandiser, No-frost freezer / sub-zero cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IV.2 Typical Wiring Diagram, ERC 102C, Glass Door Merchandiser . . . . . . . . . . . . . . . . . . . . . IV.3 Typical Wiring Diagram, ERC 102D, Gastro No-frost freezer . . . . . . . . . . . . . . . . . . . . . . IV.4 Typical Wiring Diagram, ERC 102C, Gastro Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Application specificatons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V.1 Control sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V.2 Evaporator sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V.3 Condenser sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V.4 Ambient light sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V.5 Door sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ERC102 Application Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ERC 102 Reference manual 45 51 52 53 53 54 55 56 57 57 58 58 59 59 60 3 1. INTRODUCTION The ERC 102 is an electronic refrigeration controller with an LED display especially developed for bottle coolers and commercial fridges and freezers. It is particularly suited for OEM customers where time, easy and reliable installation and high quality need to go hand in hand with flexibility. The latest generation CPU, plenty of memory and high-end electronic components allow for a uniquely versatile software. Three separate password-protected user levels can be used to control more than 200 different parameters to fit all individual requirements. ERC 102’s IP rated body, advanced materials and internationally approved hardware design open it up for use in almost any climate globally, indoors as well as outdoors. Laboratory work with ERC 102 is rendered easy and flexible. Danfoss KoolProg software with a USB-powered gateway accelerate programming; on the OEM assembly line, just one Danfoss unique Docking station can easily program up to 3,000 controllers a day – at zero inventory cost. It uses a globally-compatible, lightweight, switch mode power supply. All components have been carefully selected to help reduce the CO2 footprint. The globally-compatible internal power supply uses an average of just 0.7W – 4 times less than an average controller today. Sensors include ambient light for display brightness, which also detect shop opening hours for energy-saving routines. Door and temperature sensors provide input for controlling the compressor, the light, the fan and automatic defrosting. 4 ERC 102 Reference manual 2. CONTENT OF THE BOX If delivered in a sample box the following content is shipped. The sample box is not available for other than sample purposes. See Appendix II for code numbers and lengths. For box lots (pcs per box), please contact your local Danfoss representative. 2. 1 Main product ERC 102 control unit without front frame. NOTE: The front frame is included in the sample box. 2.2 Accessories Control temperature sensor: see Appendix II for different lengths and connector types. Defrost temperature sensor: should be mounted on the evaporator. For detailed mounting instructions, please contact your local Danfoss representative. NOTE: Defrost sensors can also be used as condenser sensors. Condenser temperature sensor: should be mounted on the condenser. For detailed mounting instructions, please contact your local Danfoss representative. NOTE: This sensor is not included in the sample box . Defrost sensors can also be used as condenser sensors. ERC 102 Reference manual – 2 CONTENT OF THE BOX 5 Door sensor connector cable: please see Appendix II for lengths and code numbers. NOTE: Door sensor: is optional and is a connector and cable with spade terminals compatible with door contacts used in refrigeration applications. Light sensor: is optional and is used to measure the level of ambient light around the cabinet so that night and day (Economy / Normal) modes of operation can automatically be set, as well as the brightness of the display. Power plug: for laboratory use, low quantity OEM production or whenever spade connectors are not available. Clips: are used to secure the ERC 102 in place in the case of rear mounting. They are not used with front mounting. There are two identical clips, one placed on either side of the ERC 102. See Chapter 4 – Mounting – for further details. 6 ERC 102 Reference manual – 2 CONTENT OF THE BOX 2.3 Connections Programming an individual unit in a laboratory: the USB gateway requires KoolProg Software running on a PC. It enables parameters to be set in real time and an array of status information to be read (bidirectional connection). This method is used to determine the correct parameters during R&D. Once the desired settings have been determined, a KoolProg ERC specific parameter file is saved to the EKA183 USB copy key for later mass programming. The USB Gateway is a laboratory tool, offering fast and easy programming of any ERC102 controller. KoolProg software installation is provided; the gateway is standard inventory for OEM labs. Mass programming on an assembly line: the docking station is used for high volume programming of ERC controllers, for example on an assembly line. The docking station is a write-only device. See above (Programming an individual unit) for preparing the EKA183 USB copy key, which is to be inserted into the docking station. The settings are then loaded into each successive controller in a matter of seconds. KoolProg software is not required for mass programming. Note: please refer to the koolprog manual for more details about programming. KoolProg: is the software from Danfoss for programming the ERC 102 via a USB cable and a PC rather than with the front panel buttons. Please refer to the KoolProg manual for details. ERC 102 Reference manual – 2 CONTENT OF THE BOX 7 3. OVERVIEW OF THE PRODUCT The ERC 102 is a state-of-the art, IP65 (front)-rated refrigeration controller for use in both Glass Door Merchandising and Commercial Fridges and Freezer applications. With four inputs and four outputs, powerful algorithms and input from multiple sensors, the ERC 102 delivers both energy-saving routines and compressor, light, fan and defrost control. Together with the Danfoss docking station, programming of pre-prepared parameter sets can be achieved in just five seconds. There are over 200 parameters (see Chapter 7) including innovative features such as night mode detection, store opening detection, door open alarm control and display dimming for restaurants. The ERC 102 can also be programmed via USB using the Danfoss KoolProg software, allowing the most suitable parameter findings to be found quickly during the application development process. It is also possible to operate and program the controller using the control buttons (only when actually installed in a refrigerator / freezer). Overview of ERC 102 models: Model: Digital outputs: ERC 102A 1 relay ERC 102C 3 relays ERC 102D 4 relays 3.1 Control buttons The ERC 102 has four buttons (circled in image) on the front which can be programmed to perform different functions. See Chapter 6 – Configuration of inputs and outputs for detailed information. 3.2 Connector inputs Connect up to four Danfoss original sensors according to your application needs. There are three analogue inputs: S1, S2 and S3 ( a ). The ambient light sensor can be used for determining shop open / closed times for economy mode switching, for determining the brightness of the LED display or both. Supported input options: · Ambient light - analogue data [luminens] · Cabinet (air) temperature - analogue data [°C] · Evaporator temperature - analogue data [°C] · Condenser temperature - analogue data [°C] · Digital input - binary data [on/off ] There is one digital input: diC ( b ) for PC communication being used either with a door sensor or with the USB Gateway. NOTE: for detailed information refer to section 6.1. 8 ERC 102 Reference manual – 3 OVERVIEW OF THE PRODUCT S1 S2 a S3 b 3.3 Connector outputs All four outputs ( c ) are digitally controlled on/off relays. Functions controlled are: • Compressor • Pilot Relay • Heater • Defrost heater / valve for hot gas • Alarm • Fan • Light C 3.4 Top label The illustration shows an example of a top label affixed to an ERC 102D. The examples show what is connected: • Output 1 is used to switch the compressor on and off. • Outputs 2 and 3 are power – Live and Neutral. • Output 4 is used to switch the heater on and off. • Output 5 is used to switch the fan on and off. • Output 6 is used to switch the light on and off. • Input D (S1) is connected to a Cabinet Sensor to measure temperature inside the cabinet. • Input C(di) is used for Communications – a docking station or KoolProg software running on a PC. • Input B(S2) is connected to an Evaporator Temperature Sensor. • Input A(S3) is connected to an Ambient Light Sensor. NOTE: Parameters depend on the code number supplied. Please refer to the code number specific technical drawing or use the KoolProg information menu. For other applications, a condenser sensor and a door sensor may be used. ERC 102 Reference manual – 3 OVERVIEW OF THE PRODUCT 9 4. MOUNTING There are three options for mounting the ERC 102 in a freezer or refrigerator. SAFETY INFO Risk of electrocution! For mounting: Do not connect mains power until the controller is correctly mounted. For unmounting: Disconnect the power supply before unmounting. 4.1 Rear mounting – Option 1 1. Insert the ERC 102 into the cabinet. 2. Attach the clips to each side of the ERC 102. 3.Place the front frame on to the ERC 102 and click it into place. 4.Connect the sensors and outputs as required and then the power cable (see Chapter 6 – parameters for information about programming which inputs and outputs are applicable to your configuration). 10 ERC 102 Reference manual – 4 MOUNTING 4.1.1 Unmounting 1. Disconnect the power cable and then the sensors. 2.Use a flat head screwdriver (ideally the one supplied with the ERC 102 sample package) and insert it carefully between the front frame and the controller. 3.Gently twist the screwdriver to remove the front frame. Do this in four places next to each clip area. 5.Reach around the side to the clips. ERC 102 Reference manual – 4 MOUNTING 11 6.Press the centre section of each clip to release them in turn. Push the controller carefully out of the cabinet. 4.2 Front mounting – Option 2 1.Connect all the cables as required (see Chapter 6 – parameters for information about programming which inputs and outputs are applicable to your configuration). 2.Insert the ERC 102 into place in the cabinet. 3.Press the front frame into place – this locks the ERC 102 into position. NOTE: there is no need to use the clips for front mounting. 12 ERC 102 Reference manual – 4 MOUNTING 4.2.1 Unmounting 1.Use a flat head screwdriver (ideally the one supplied with the ERC 102 sample package) and insert it carefully between the front frame and the controller. 2.Gently twist the screwdriver to remove the front frame. Do this in four places next to each clip area. 3.Cabinet. Do not use a different type of screwdriver or a sharp item such as a knife which risks causing damage. 4.3 Fully integrated design – Option 3 An option is available for OEMs wanting to use the ERC 102 in a fully-integrated design. Please contact your local Danfoss representative for more information. ERC 102 Reference manual – 4 MOUNTING 13 5. CONTROLLING / NAVIGATION AND ACCESS LEVELS The ERC 102 can be controlled in three ways: using KoolProg software, the Danfoss Docking Station or manually by means of the buttons on the front panel. 5.1 KoolProg/Gateway KoolProg is licenced Danfoss software offering easy parameter setup via a USB gateway. This software is supplied separately; for technical literature and further information, please contact your local Danfoss representative. 5.2 Docking station The ERC 102 controller docking station is supplied separately. For further information, please contact your local Danfoss representative. 5.3 Manual operation with buttons (Direct Access) Danfoss ERC 102 Explained as follows: ERC Front and Button Functionallity: 5.3.1 ERC Front and Button Functionallity 1 Press: Variable direct function, e.g.ECO/Night mode function: Up setpoint 1Sub Click: Temperature Sub function: Up 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint Sub function: Down setpoint 1 Press: Temperature 3 sec: Menu direct function, e.g. light 1Hold Press: Variable Sub function: OK Sub function: OK 14 1 Press: Temperature setpoint 1Sub Click: VariableBack direct function, e.g.ECO/Night mode function: Sub function: Back Sub function: Down ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS C 102 5.3.2 Direct functions for access on Functionallity: C 102Changing the Desired Temperature Setpoint (applies similarly when using Fahrenheit scale): g.ECO/Night mode 1 Click: Temperature setpoint Sub function: Up on Functionallity: 1.) C 102 The display shows the current temperature. 1 Click: Temperature setpoint g.ECO/Night mode Sub function: Up (Current temperature) on Functionallity: 2.) g. light 1 Click: Temperature setpoint C 102 Sub function:toDown Press: up/down adjust setpoint g.ECO/Night mode on Functionallity: 1 Click: Temperature setpoint Sub function: Up (Flashing: temperature setpoint) 3.) After 30 seconds, the display automatically reverts to showing the current temperature g. light 1 Click: Temperature setpoint Sub function: Down g.ECO/Night mode 1 Click: Temperature setpoint Sub function: Up (Flashing: temperature setpoint) 4.) g. light 1 Click: Temperature setpoint Sub function: Down ss ERC 102 g. light 1 Click: Temperature setpoint Sub function: Down and Button Functionallity: ss ERC 102 Turning On/Off the ECO Function: irect function, e.g.ECO/Night mode k 1 Click: Temperature setpoint Sub function: Up and Button Functionallity: 1.) Press briefly to enter rect function, e.g.ECO/Night mode ECO mode 1 Click: Temperature setpoint Sub function: Up k rect function, e.g. light rect function, e.g. light 2.) ECO ˚C 1 Click: Temperature setpoint Sub function: Down The green ECO symbol is lit when in ECO mode 1 Click: Temperature setpoint Sub function: Down ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS 15 oss ERC 102 t and Button Functionallity: direct function, e.g.ECO/Night mode ck 1 Click: Temperature setpoint Sub function: Up Turn ON/Off the Light 1.) Press the Light button briefly oss ERC 102 Danfoss ERC 102 To turn off the Light Press the light button again t and Button Functionallity: ERC Front and Button Functionallity: direct function, e.g. light u K oss ERC 102 Alarms: Acknowledging direct function, e.g.ECO/Night mode 1 Click: Variable direct function, e.g.ECO/Night mode ck Sub function: Back 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Up 1 Click: Temperature setpoint Sub function: Up t and Button Functionallity: 1.) direct function, e.g.ECO/Night mode ck 1 Click: Temperature setpoint Sub function: Up Flashing Press any button to acknowlege 2.) direct function, e.g. light u K 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu Sub function: OK direct function, e.g. light u K 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Down 5.3.3 Operating the menu Button assignments in this manual refer to the Glass Door Merchandiser default ERC 102. For customised controls you may assign different shortcuts (ASI menu --> button configuration). Use this feature only when the ERC 102 is supplied without button prints. INFO: Some parameters may be hidden to you. When scrolling through menus, the parameters available will have been pre-determined using KoolProg software. Your access level will determine which parameters you can view and edit. 16 ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS Danfoss ERC 102 ERC Front and Button Functionallity: Danfoss ERC 102 Example of Changing a Parameter: 1 Click: Variable direct function, e.g.ECO/Night mode Sub function: Back 1 Click: Temperature setpoint Sub function: Up ERC Front and Button Functionallity: 1.) Danfoss ERC 102 1 Click: Variable direct function, e.g.ECO/Night mode Sub function: Back Press and hold for 5 seconds to enter the menu 1 Click: Temperature setpoint Sub function: Up ERC Front and Button Functionallity: 2.) 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu Sub function: OK 1 Click: Variable direct function, e.g.ECO/Night mode Sub function: Back Danfoss ERC 102 ERC Front and Button Functionallity: 3.) 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu function: OKdirect function, e.g.ECO/Night mode 1Sub Click: Variable Danfoss ERC 102 To select: press the lower left button (OK) Sub function: Back 1 Click: Temperature setpoint Sub function:toDown Press: up/down scroll through the menu 1 Click: Temperature setpoint Sub function: Up (scroll through parameter groups) 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Up ERC Front and Button Functionallity: 4.) 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu function: OKdirect function, e.g.ECO/Night mode 1Sub Click: Variable Sub function: Back Danfoss ERC 102 ERC Front and Button Functionallity: 1 Click: Temperature Press: up/down to find setpoint Sub function: Down the desired parameter 1 Click: Temperature setpoint Sub function: Up (scroll through group “dEf” parameters) 5.) 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu Sub function: OK 1 Click: Variable direct function, e.g.ECO/Night mode To confirm: press the lower left button (OK) Sub function: Back Danfoss ERC 102 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Up ERC Front and Button Functionallity: 6.) 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu 1Sub Click: Variable function: OKdirect function, e.g.ECO/Night mode Sub function: Back Danfoss ERC 102 1 Click: Temperature setpoint Press: up/down enter Sub function:toDown the desired value 1 Click: Temperature setpoint Sub function: Up ERC Front and Button Functionallity: 7.) Danfoss ERC 102 1 Click: Variable direct function, e.g. light Hold 3 sec:Press: MenuOK to accept 1Sub Click: Variable direct function, e.g.ECO/Night mode function: andOK return to parameter name Sub function: Back 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Up ERC Front and Button Functionallity: 8.) 1 Click: Variable e.g. light Press:direct upperfunction, left button (back) 3 sec: toMenu return to function, parameter group 1Hold Click: Variable direct e.g.ECO/Night mode Sub function: OK Sub function: Back 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Up 9.) Press:direct upperfunction, left button (back) 1 Click: Variable e.g. light return to the menu Hold 3 sec:toMenu Sub function: OK 1 Click: Temperature setpoint Sub function: Down 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu Sub function: OK 1 Click: Temperature setpoint Sub function: Down ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS 17 102 Danfoss ERC 102 Danfoss ERC 102 Functionallity: ERC Front and Button Functionallity: O/Night mode ERC Front and ERC Button Functionallity: Danfoss 102 1 Click: Temperature setpoint Sub function: Up ERC Front and ERC Button Functionallity: Danfoss 102 1 Click: Temperature setpoint Sub function: Up 1 Click: Variable direct function, e.g.ECO/Night mode1 Click: Temperature setpoint Sub function: Back 5.3.4 Menu structure Sub function: Up 1 Click: Variable direct function, e.g.ECO/Night mode Press and hold 5 1. ) Parameter groups Sub function: Back sec to access the menu ERC Front and ERC Button Functionallity: Danfoss 102Danfoss ERC 102 1 Click: Variable direct function, e.g.ECO/Night mode Sub function: Back 1 Click: Temperature setpoint Sub function: Up Lower left button ERC Front and ERC Button Functionallity: ERC Front and ERC Button Functionallity: Danfoss 102Danfoss 102Danfoss ERC 102 1 Click: Variable direct function, e.g.ECO/Night mode 1 Click: Temperature setpoint Sub function: Back function: Up 1 Click: Variable direct function, e.g. light 1Sub Click: Temperature setpoint 1 Click: Temperature setpoint Hold 3 sec: Menu Sub function: Down Sub function: Down Sub function: OK 1 ERC Click: Variable function, e.g.ECO/Night mode1 Click: Variable direct function, e.g.ECO/Night mode ERC Front and Button Functionallity: Frontdirect and Button Functionallity: ERC Front and Button Functionallity:1 Click: Temperature setpoint 1 Click: Temperature setpoint Sub function: Back Sub function: Back Sub function: Up Sub function: Up 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint Hold 3 sec: Menu Sub function: Down Sub function: OK 1 ERC Click: Variable function, e.g.ECO/Night mode1 Click: Variable direct function, e.g.ECO/Night mode 1 Click: Variable direct function, e.g.ECO/Night mode Frontdirect and Button Functionallity: 1 Click: Temperature setpoint ERC Front and Button Functionallity: 1 Click: Temperature setpoint Sub function: Back 2.) Parameter names Sub function: Back Sub function: Back Sub function: Up Sub function: Up 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint Hold 3 sec: Menu Sub function: Down Lower left button Sub function: OK 1 ERC Click: Variable function, e.g.ECO/Night mode1 Click: Variable direct function, e.g.ECO/Night mode Frontdirect and Button Functionallity: ERC Front and Button Functionallity:1 Click: Temperature setpoint 1 3.) Click: Temperature setpoint Parameter value Sub function: Back Sub function: Back Sub function: Up Sub function: Up 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint Hold 3 sec: Menu Sub function: Down Sub function: OK 1 ERC Click: Variable function, e.g.ECO/Night mode1 Click: Variable direct function, e.g.ECO/Night mode Frontdirect and Button Functionallity: 1 Click: Temperature setpoint ERC Front and Button Functionallity: 1 Click: Temperature setpoint Sub function: Back Sub function: Back Sub function: Up Sub function: Up 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down Sub function: OK Sub function: OK 1 ERC Click: Variable function, e.g.ECO/Night mode1 Click: Variable direct function, e.g.ECO/Night mode Frontdirect and Button Functionallity: 1 Click: Temperature setpoint 1 Click: Temperature setpoint Sub function: Back Sub function: Back Sub function:function, Up Sub function: Up 1 Click: Variable e.g. light 1 Click: Variable direct function, e.g. light 1 Click: direct Temperature setpoint 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint Hold 3 sec: Menu Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down Sub function: OK Sub function: OK Sub function: OK 1 ERC Click: Variable function, e.g.ECO/Night mode Frontdirect and Button Functionallity: 1 Click: Temperature setpoint Sub function: Back Sub function: Up 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down Sub function: OK Sub function: OK 1 ERC Click: Variable direct function, e.g.ECO/Night mode Front and Button Functionallity: 1 Click: Temperature setpoint Sub function: Back Sub function: Up 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint (scroll through parameters) Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down Sub function: OK Sub function: OK 1 Click: Variable direct function, e.g.ECO/Night mode 1 Click: Temperature setpoint Sub function: Back Sub function: Up 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down Sub function: OK Sub function: OK ht Danfoss ERC 102Danfoss ERC 102 Danfoss ERC 102Danfoss ERC 102 Danfoss ERC 102Danfoss ERC 102 Danfoss ERC 102 Danfoss ERC 102 Danfoss ERC 102 102 Danfoss ERC 102Danfoss ERC 102 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu Sub function: OK 1 Click: Temperature setpoint Sub function: Down Functionallity: 1 Click: Variable directand function, e.g. light Functionallity: ERC Front Button ERC Front and Button (scroll throughFunctionallity: menu group) 1 Click: Temperature setpoint O/Night mode Hold 3 sec: Menu Sub function: OK Sub function: Down 1 Click: Variable direct function, mode Click: Variablesetpoint direct function, e.g.ECO/Night mode 1 Click: Variable direct function, e.g.e.g.ECO/Night light 1 Click:1 Temperature Sub function: Sub function: Up Back 1 Click: Temperature setpoint 1 Click: Temperature setpoint SubSub function: Down function: Up Sub function: Hold 3 sec: MenuBack 5.3.5 Password protection Sub function: OK 1 Click: Temperature setpoint Sub function: Up Press and hold 5 sec to access the menu 1 Click: Variable direct function, e.g. light Hold 3 sec: Menu Sub function: OK ht 18 Click: Variablesetpoint direct function, e.g. light 1 Click:1 Temperature Hold 3 sec: Menu Sub function: Down Sub function: OK Password protection on three levels Level 1: Shop (daily use by shop personnel) Level 2: Ser (service technician) 1 Click: Temperature setpoint 1 Click: Temperature setpoint Level 3: OEM (OEM programming) Sub function: Down ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS Sub function: Down 02 6. CONFIGURATION OF INPUTS AND OUTPUTS The ERC 102 inputs and outputs are configurable by tionallity: the customer. Before getting started it is a good idea to check if all inputs are configured correctly and match the sensors attached. mode Input and output configuration settings are part of the assignment menu (ASi). For instance: Danfoss supplies only 2-pole defrost sensors, so input S3 will most likely be used as a defrost / evaporator temperature sensor input. Please contact your local Danfoss representative for information about default settings. 1 Click: Temperature setpoint Sub function: Up NOTE: Coded sensors will impact on the number of possible configurations. Assignments / ASi 6.1 Changing input and output configuration settings There are two steps to inputting the configuration: 1. Define the type of sensor attached to the input: - Temperature / light / digital 1 Click: Temperature setpoint Subapplication function: for Down 2. Define the the sensor: - Temperature: control / condenser / evaporator - Light: ECO / display / both - Digital: door sensor Example: Input S1 is attached to a temperature sensor. The sensor measures cabinet temperature. Example: Input S2 is attached a digital on/off sensor which is a door open / closed switch. C S1 S2 S3 b a Connector inputs: analogue ( a ), digital ( b ) Connector outputs ( c ) ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS 19 ERC menu code Default Min Max Unit Conv Unit Scale Default Access Shop Ser OEM Assignments ASi S1 Config S1C Stn Stn dig no -- -- RW S2 Config S2C Stn Stn dig no -- -- RW S3 Config S3C Stn Stn dig no -- -- RW S1 Application S1A SCo nC doo no -- -- RW S2 Application S2A nC nC doo no -- -- RW S3 Application S3A nC nC doo no -- -- RW DI Config diC dio doC dio no -- -- RW DO1 Config 01C CoP CoP HEt no -- -- RW DO2 Config o2C dEF 0 Lig no -- -- RW DO3 Config o3C FAn 0 Lig no -- -- RW DO4 Config o4C dEF 0 Lig no -- -- RW Button 1 Short Config b1C noP tP noP no -- -- RW Button 1 Long Config b1L PoF tP PoF no -- -- RW Button 2 Short Config b2C dEF tP noP no -- -- RW Button 3 Short Config b3C tP tP noP no -- -- RW Button 3 Long Config b3L ECo tP PoF no -- -- RW Button 4 Short Config b4C tn tP noP no -- -- RW Button 4 Long Config b4L Lig tP PoF no -- -- RW Password level1 PS1 0 0 999 no RW RW RW Password level2 PS2 0 0 999 no -- -- RW Password level3 PS3 0 0 999 no -- -- RW Cabinet Light Control Source CLC Lig Lig LEC no -- -- RW Light off delay Lod 0 0 300 no 20 ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS Sec 1 -- -- RW 2nallity: e e nallity: 2 e 2nallity: 2nallity: e e nallity: e 2 nallity: e 2 nallity: e 1 Click: Temperature setpoint Sub function: Up 1 Click: Temperature setpoint Sub /function: S1 Config S1C Up S2 Config / S2C S3 Config / S3C Temperature Available1 Click: options are: setpoint Sub function: Up Stn for a temperature sensor (values given in Celsius) Ldr for a light sensor (values given in Luminens) Dig for a digital sensor with simple on/off indication 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Up 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: S1 Application / Up S1A 1 Click: Temperature S2 Application / S2A setpoint Sub function: Down S3 Application / S3A 1 Temperature AvailableClick: options are: setpoint Sub function: Up nC:Not connected SCo:Temperature control EuA:Evaporator temperature 1 Click: Temperature setpoint Con:Condenser temperature (Condenser cleaning) Sub function: Down LS1:Light sensor (Ldr), Luminens, dedicated to Eco mode switching detection LS2:Light sensor (Ldr), Luminens, dedicated to determining LED intensity LS3:Light sensor(Ldr), Luminens, used for both Eco mode detection and 1 Click: Temperature setpoint Sub function: Down determining LED intensity doC:Door contact, contact closed when door closed 1 Click: Temperature setpoint doo:Door contact, contact open when door closed Sub function: Up 1 Click: Temperature setpoint Sub function: Down DI Config / diC This is the digital input used for a digital sensor or bus communications. doC:Door contact, contact closed when door closed doo:Door contact, contact open when door closed bus:Modbus communication (used only for KoolProg) 1 Click: Temperature setpoint diO:One Communication SubWire function: Up 1 Click: Temperature setpoint Sub function: Down D01 Config / D1C CoP:Direct compressor control Pil:Pilot Relay (No Zero Cross) – if using pilot relay to control a compressor, this option must be used instead of CoP Het:Heating application, inverse output. 1 Click: Temperature setpoint Sub function: Down ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS 21 e 2nallity: 1 Click: Temperature setpoint Sub function: Up e nallity: 1 Click: Temperature setpoint Sub function: D02 Config / o2CUp D03 Config / o3C D04 Config / o4C e 1 Click: Temperature setpoint Sub function: Up nO: not used dEF: Electric Defrost Heater / Valve for hot gas ALA: Alamr Output 1 Click: Temperature setpoint Fan: FanSub control function: Down LIG: Light control 2 2nallity: 1 Click: Temperature setpoint Sub function: Down 2nallity: 6.2 Program the buttons Click: Temperature Temperature setpoint setpoint 11 Click: Sub Subfunction: function:Up Down e e 2nallity: 1 Click: Temperature setpoint function: (short Up Button Sub 1 Config press) / b1C Lower left button Button 1 config (long press) / b1L 1 Click: Temperature setpoint Lower left button Sub function: Up Button 2 Config (short press) / b2C Upper left button Button 3 Config (short press) / b3C 1 Click: Temperature setpoint Upper right button Sub Subfunction: function:Up Down Button 3 config (long press) / b3L Upper right button Button 141 Click: Config (short press) / b4C Click: Temperature Temperature setpoint setpoint Subfunction: function: Down Lower right button Sub Up Button 4 Config (long press) / b4L Lower right button e 2 nallity: e 2nallity: e 2 nallity: 1 Click: Temperature setpoint 1Sub Click: Temperature function: Down setpoint e nallity: Sub function: Up programmed as follows: The buttons can be e Short press function Long Press function 1 Click: Temperature setpoint tP: Increase Setpoint 1Sub Click: Temperature function: Down setpoint tn: Decrease setpoint Sub function: Up ECo: Toggle Eco mode Lig: Toggle light dEF: Toggle defrost 1 Click: Temperature setpoint SubSuper-Cool function: Down SuP: Toggle /Pull-down diP : Increase display intensity din : Decrease display intensity tP: Increase Setpoint tn: Decrease setpoint ECo: Toggle Eco mode Lig: Toggle light dEF: Toggle defrost SuP: Toggle Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity Not operating ERC power ON/OFF 1 Click: Temperature setpoint Sub function: Down NOTE: Buttons 1, 3 and 4 can be assigned to operate with 2 functions (short press or long press). 1 Click: Temperature setpoint NOTE: Your assignments may notSub befunction: shownDown on the printed buttons. We advice to use this functionality together with the fully integrated mounting model only. 22 ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS 2nallity: 2nallity: 6.3 Set passwords e 1 Click: Temperature setpoint Sub function: Up e nallity: e 2 nallity: 1 Click: Temperature setpoint Sub level function:1Up Password / PS1 Password Level 2 / PS2 Password Level 3 / PS3 1 Click: Temperature setpoint These assign passwords to the three levels of access. The password is a three-digit Sub function: Up number. Access levels are Shop, Service and OEM. You may not therefore have access to change all the passwords. Passwords are entered by using the up and down arrow buttons. 1 Click: Temperature setpoint Danfoss Sub advises against using passwords which are easy to remember or enter, for function: Down example 111, 222, 123 etc. NOTE: When the controller with 3 wrong password in a sequence ERC will 1 Click: accessing Temperature setpoint Sub function: Down automatically block access for 15 minutes. e 2 nallity: 6.4 Set lighting function 1 Click: Temperature setpoint Sub Subfunction: function:Up Down Cabinet Light Source Control / CLC This parameter can be set to one of these alternatives to control the light in the cabinet: Lig:button only – the light will only come on when the light button on the ERC 102 is pressed (toggle functionality). Ldo:door (and button if defined) only LEC:economy (and button if defined) only 1 Click: Temperature setpoint Sub function: Down Light off delay / Lod Number of seconds the light will stay on after the door has been closed. ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS 23 02 7. PARAMETERS This chapter details all user-accessible parameters in ERC 102 software 5.05. The access level can be set separately for each parameter using KoolProg software. There are three levels of access – 1, 2 and 3. Level 1 is for shop access, level 2 for technicians and level 3 for OEMs. The access levels cannot be set using the buttons. Passwords for the different levels can however be altered for the level of access you have – for example a level 2 user can change the password for level 1 and level 2 but not level 3. NOTE: Incorrect parameter settings can lead to inadequate cooling, excessive energy consumption, unnecessary alarms and in the case of temperaturesensitive food storage, breaches in food hygiene principles and regulations. Only a trained operator should make changes to parameters. tionallity: INFO! Some parameters may be hidden to you. When scrolling through menus, the parameters available will mode have been pre-determined using KoolProg software. Your access level will determine which parameters you can view and edit. 1 Click: Temperature setpoint Sub function: Up 7.1 Thermostat / tHE ERC 102 can handle both Celsius and Fahrenheit. Changing from C to F and vice-versa is done in the Display menu. When the change is made, all temperature values are automatically re-calculated and updated in all other parameters accordingly. ERC menu code Default Min 1 Click: Temperature setpoint Sub function: Down Max Unit Conv Unit Scale Default Access Shop Ser OEM Thermostat tHE Set point adjustment ratio SPr 0.5 0.0 1.0 no .1 -- -- RW Differential diF 2.0 0.0 20.0 C/F r K .1 -- RW RW High Set Point HSE 50.0/122.0 -50.0/122.0 80.0/176.0 C/F a °C/°F .1 -- RW RW Low Set Point LSE -35.0/-31.0 -35.0/-31.0 80.0/176.0 C/F a °C/°F .1 -- RW RW Air Temp Adj. tAd C/F r K/°R .1 -- -- RW 24 0.0/0.0 ERC 102 Reference manual – 7 PARAMETERS 0.0/0.0 20.0/36.0 e 2 nallity: 2 e nallity: 2 e 1 Click: Temperature setpoint Sub function: Up Set point / StP StP is visible with KoolProg software only. This parameter defines the desired temperature (set point). In standard operation the set point is changed by simply pressing the “temperature up / down” buttons on ERC102; for laboratory 1 Click: Temperature and assembly line yousetpoint may opt for software controlled set point adjustment Sub function: Up (speed improvement) 1 Click: Temperature setpoint Sub function: Down Set point adjustment ratio / SPr The default value is set to 0.5 and the parameter is hidden by default. Spr defines the position of the setpoint in relation to cut-in and cut-out. setpointmid between cut-in and cut-out. Spr = 0 sets Spr = 0,51 Click: setsTemperature the setpoint Sub function: Up the setpoint at the cutout. Spr =1 sets the setpoint at cut-in. nallity: 2 e 1 Click: Temperature setpoint Differential / diF Down Sub function: This defines the difference between the cut-out and the cut-in. The desired 1 Click: is Temperature setpointby SPr and diF. temperature determined Sub function: Up nallity: e 2 High Set Point / HSE 11 Click: Click: Temperature Temperature setpoint setpoint Low SetSub Point / LSE Sub function: Down function: Up These parameters define the temperature range limit of the controller. Once set, the desired temperatue (setpoint) can not go above HSE or below LSE. LSE Sets the minimum value for the set point HSE Sets the maximum value for the set point 1 Click: Temperature setpoint Sub function: Down Cut-in and cut-out are automatically calculated from the desired setpoint (set bybuttons on the control) and the differential. By default, cut-out and cut-in are 0,5*DiF above or below the desired temperature. 1 Click: setpoint temperature in the cabinet is 5 degrees, and the Example: TheTemperature desired average Sub function: Down differential is set to 2 degrees: nallity: e 1 Click: Temperature setpoint Sub function: Up Air Temperature Adjustment / tAd This parameter is a relative value and allows adjustment of the control sensor temperature. For instance, at a measured temperature of 7*C and tAd set to -2K, the input from the control sensor will be 5*C instead. 1 Click: Temperature setpoint Sub function: Down ERC 102 Reference manual – 7 PARAMETERS 25 mode 1 Click: Temperature setpoint Sub function: Up 7.2 Alarms / ALA ERC menu code Default Min Max Unit Conv Unit Scale Default Access Shop Ser OEM 1 Click: Temperature setpoint Sub function: Down Alarm ALA High Alarm delay Htd 30 0 240 no min 1 -- RW RW Low Alarm delay Ltd 0 0 240 no min 1 -- RW RW High Temp Alarm HAt 15.0/59.0 -50.0/-58.0 80.0/176.0 C/Fa °C/°F .1 -- RW RW Low Temp Alarm LAt -50.0/-58.0 -50.0/-58.0 80.0/176.0 C/F a °C/°F .1 -- RW RW Pulldown delay Pdd 240 0 960 no min 1 -- RW RW Door Open delay dod 2 0 60 no min 1 -- RW RW Alarm Buzzer Duration Abd 0 0 999 no min 1 -- RW RW Auto Clearance of Alarm/Error ACA yES no yES no 1 -- RW RW 26 ERC 102 Reference manual – 7 PARAMETERS e nallity: 2 e 2nallity: e nallity: 2 e nallity: e 2 nallity: e 2 nallity: e 1 Click: Temperature setpoint Sub function: Up 1 Click: Temperature setpoint High Temp AlarmUp/ HAt Sub function: Low Temp Alarm / Lat High temperature alarm and low temperature alarm allow for individual alarm setpoints. Both are absolute values. By setting HAt to the maximum value and LAt to the minimum value, alarms will be deactivated. 1 Click: Temperature setpoint Sub function: Up 1 Click: Temperature setpoint Sub function: Down 1 Click: Temperature setpoint Sub function: Up/ Htd High Alarm Delay 1 Click: Temperature setpoint Low Alarm Delay / Ltd Sub function: Down These parameters express the number of minutes to wait before sounding an alarm once the High/Low Temp Alarm temperature is reached. Immediately prior to the alarm sounding, another check of the temperature is made to see if the temperature still in the alarm zone; if it is not, the then the alarm is not sounded. 1 Click: is Temperature setpoint function: Upthe Low Alarm Delay will be set to 0 to warn about too low a In most Sub situations, 1 Click: Temperature setpoint temperature immediately. Sub function: Down Pulldown Delay / Pdd 1 Click: Temperature setpoint Normally, it is not necessary or desirable to sound an alarm during a pull down Sub function: Down (the initial phase of reaching the desired temperature). This parameter prevents the High Temp Alarm HAt sounding during pull down and after a defrost for the number1of minutes set for the parameter. Click: Temperature setpoint Sub function: Up NOTE: It does not apply to the Low Temp Alarm LAt. 1 Click: Temperature setpoint Sub function: Down Door Open Delay / dod It is possible to indicate to customers that a door has accidentally been left open. This parameter sets the delay in minutes before the alarm sounds. This is useful in environments where customers / users may hold the door open while making their selection. If the door is closed again before the set number of minutes is reached, the alarm does not sound. Click: Temperature setpoint NOTE: A1Sub door sensor is required if this parameter is to be activated. function: Down 1 Click: Temperature setpoint Sub function: Up Alarm Buzzer Duration / Abd The ERC 102 alarm sounds for 10 seconds, followed by silence for 50 seconds. One alarm sequence therefore lasts 60 seconds. These values cannot be changed. This parameter determines how long in minutes an audible alarm will continue while there is still a reason to have an alarm. If set to 999, the alarm will continue to sound until the reason for the alarm is cleared – for example the temperature has dropped enough or the door closed. In some cases, it may be necessary for a user 1 Click: Temperature setpoint or technician to take action in order to clear the alarm. If set to 0, the alarm will Sub function: Down never sound. ERC 102 Reference manual – 7 PARAMETERS 27 e 1 Click: Temperature setpoint Sub function: Up Auto Clear of Alarm / Error / ACA If this parameter is set to nO: The alarm status will not disappear automatically even if the condition which caused the alarm is no longer valid or present. If set to yES: 02 tionallity: As soon as the condition which caused the alarm is no longer valid or present, the 1 Click: Temperature setpoint alarm status will automatically change back to inactive. There will be no trace of Sub function: Down the alarm having occurred. In general, Glass Door Merchandise applications will be set to yES and Commercial Fridges and Freezers set to nO. For example, if the temperature goes too high for a period there may be food safety considerations in a freezer containing food but not in a fridge with cold drinks. mode 1 Click: Temperature setpoint Sub function: Up 7.3 Compressor / CoP ERC menu code Compressor Default Min Max Unit Conv Unit Scale Default Access Shop Ser OEM CoP Min run time Crt 0 0 30 no1 Click: min 1 -- RW RW Temperature setpoint Min Stop time CSt 0 0 30 no Sub function: min 1 Down Max Off time Cot 0 0 480 no min 1 -- -- RW Error run time Ert 0 0 60 no min 1 -- -- RW -- RW RW Error stop time ESt 1 0 60 no min 1 -- -- RW Minimum cut-in voltage uLi 0 0 270 no Vac 1 -- -- RW Minimum cut-out voltage uLo 0 0 270 no Vac 1 -- -- RW Maximum voltage uHi 270 0 270 no Vac 1 -- -- RW -- RW RW Power On Delay Pod 300 0 300 no Sec 1 Power Factor PFA 0 -90 90 no Degree 1 -- -- RW Initial cut in iCi no no yes no 1 -- R- RW Cdd 0 0 15 no 1 -- RO RW Compressor door open delay 28 ERC 102 Reference manual – 7 PARAMETERS min e 2 nallity: e 2 nallity: 2 e 2nallity: e nallity: e 1 Click: Temperature setpoint Sub function: Up Minimum Run Time / Crt This parameter is a number of minutes from 0 to 30. It determines the minimum number of minutes the compressor must run before a Temperature cut-out can take effect. For example, if the temperature sensor indicated that the cut-out temperature has been reached, but the number of minutes set in this parameter have not elapsed since the compressor last started, then the 1 Click:will Temperature setpoint compressor continue. It will only stop once the duration given by Crt has been Click: Temperature setpoint function: Up reached1Sub – provided the temperature is still low enough. Sub function: Down Crt thus overrides the cut-out. Minimum Stop Time / CSt This parameter is a number of minutes from 0 to 30. It determines the minimum number of minutes the compressor must remain idle before a Temperature cut-in can take effect. For example, if the temperature sensor indicates that the cut-in temperature has been reached, but the number of minutes set in this parameter have not elapsed since the compressor last stopped, then the compressor will stay off. It will only start once the duration given by CSt has been 11 Click: Temperature Temperature setpoint reachedSub –Click: provided thesetpoint temperature is still high enough. Subfunction: function:Up Down CSt thus overrides the cut-in. Maximum Off Time/ Cot This is the maximum time in minutes the compressor is allowed to idle – up to 480 1 Click: Temperature setpoint minutes.Sub Cot is setUpto zero by default (inactive). If ERC102 is to be used on a draft function: beer (ice bank) application, this parameter can be used to control the ice thickness. 1 Click: Temperature setpoint SubTime function:/ Up Error Run Ert 1 Click: Temperature Error Stop Time / ESt setpoint Sub function: Down These two parameters only become active in the unlikely event of a broken temperature sensor. They are then used to run the application in safety mode. At the same time the sensor error will be shown in the display. Ert and ESt values are based on OEM experience and are by default inactive. 1 Click: Temperature setpoint Ert and ESt define the duration the compressor will run (Ert) and be idle (ESt). Sub function: Down Example: Ert = 4 [min] and ESt = 16 [min] will provide an average cooling system activity of 20%. 1 Click: Temperature setpoint Sub function: Down ERC 102 Reference manual – 7 PARAMETERS 29 2nallity: e 1 Click: Temperature setpoint Sub function: Up e nallity: 1 Click: Temperature setpoint Sub cut-in function: Up Minimum voltage / uLi Minimum cut-out voltage / uLo Maximum voltage / uHi 1 Click: Temperature setpoint These three parameters provide voltage protection to the compressor. Start by Sub function: Up setting uHi, followed by uLo and uLi. e uLi: When the compressor is due to start, the voltage of the power supply will be 1 Click: Temperature setpoint checkedSub and the compressor will only be allowed to start if it is at least the value function: Down given in this parameter. uLo: When the compressor 1 Click: Temperature setpointis running, it will be switched off if the voltage goes Sub function: Down below that given in this parameter. uHi: When the compressor is running, it will be switched off if the voltage exceeds 1 Click: Temperature setpoint that given in this parameter. If the compressor is already stopped, it will remain Sub function: Down switched off. 2 nallity: 2 e 1 Click: Temperature setpoint Sub function: Up nallity: 02 e 1 Click: Temperature Power On Delay / Podsetpoint Sub function: Up This is the delay in seconds between power-on and the compressor being activated. Depends on the Power on Temperature setting as explained below. tionallity: 2 Power Factor / PFA This value is hidden by default. The parameter is used by the Zero Cross function to optimize1 Click: the Temperature switchingsetpoint position of the relay contact. mode 1 Click: Temperature setpoint function: Up SubSub function: Down onallity: Warning: Do not change without first consulting your local Danfoss representative. Initical 1Cut-in / iCi setpoint 1Click: Click:Temperature Temperature setpoint Sub Down Sub function: function: Up if the control temperature is between cut-in and cut-out at power up customers can determine if the compressor shall start immediatly (yes) or wait for cut-in temperature to start (no). de Power on Temperature / PoT This parameter is used to accelerate the first application test on the OEM assembly line; if the cabinet temperature 1 Click: Temperature setpoint is higher than this parameter the Power On Delay is Sub function: Down are activated without delay. overruled and the outputs Compressor Door Open Delay / Cdd This parameter sets the delay in minutes before the compressor stops when the 1 Click: Temperature door is opened. If set tosetpoint zero, the function is disabled. Sub function: Down 30 ERC 102 Reference manual – 7 PARAMETERS mode 1 Click: Temperature setpoint Sub function: Up 7.4 Defrost / dEF Note: ERC controllers feature Safe Defrost functionality (patents pending) by default. This function ensures proper defrost under poor power conditions. For more details please contact Danfoss. ERC menu code Default Min Max Unit Conv Unit Scale Default Access Shop Ser OEM 1 Click: Temperature setpoint Sub function: Down -- RW RW Defrost dEF Def type dFt no no Hgd no Def reset temp drt 5 0 80 C/F a °C 1 -- RW RW Def Min Interval dii 6 0 96 no hour 1 -- RW RW Def Max Interval dAi 7 0 96 no hour 1 -- RW RW Def Min Time dit 5 0 240 no min 1 -- RW RW Def Max time dAt 30 0 480 no min 1 -- RW RW Drip off time dot 0 0 60 no min 1 -- -- RW Fan delay after Defrost Fdd 0 0 60 no sec 1 -- -- RW C/F a °C/°F .1 -- -- RW 1 -- -- RW Fan start Temp Ftd Defrost Fan on dFA 25.0/77.0 -25.0/13.0 25.0/77.0 no no yES no Initial Defrost Interval idi 3 0 96 no 1 -- -- RW Initial Defrost Duration idd 100 0 999 no hour 1 -- RW RW Defrost on compressor time dCt no no yES no 1 -- -- RW ERC 102 Reference manual – 7 PARAMETERS 31 e 1 Click: Temperature setpoint Sub function: Up 2 nallity: Defrost Type / dFt When set to nO, the defrost function is disabled and no automatic defrosting will occur. 2 e 1 Click: Temperature setpoint When set EL orUp nAt, electrical, natural or off-cycle defrosting is used. An adSubto function: ditional setting of Hgd (hot gas defrosting) is available. nallity: 1 Click: Temperature setpoint 2 Sub function: Down Terminate Temperature / dtt This parameter defines at what temperature the defrost cycle will stop. 1 Click: Temperature setpoint The temperature is given by the evaporator sensor or by the cabinet Sub function: Up temperature sensor if no evaporator sensor is used. e nallity: Defrost reset temperature / drt 1 Click:counter Temperature The defrost issetpoint saved and restored at power-up, but if the temperature 1Sub Click: Temperature function: Down setpoint sensor, used for defrost, is higher than this value at power-up, it is assumed that Sub function: Up the evaporator is free of ice and the defrost counter will be cleared. 2 e nallity: 2 Minimum Interval / dii 1 Click: Temperature This parameter can besetpoint set to between 0 and 96 hours and defines the minimum Sub function: Down time period between the start of two defrost cycles. Once the minimum interval 1 Click: Temperature setpoint has expired, the defrost cycle will start at the following cut-out or once the maxiSub function: Up mum interval dAi has been reached. e nallity: 1 Click: Temperature setpoint Maximum Interval / dAi 1Sub Click: Temperature function: Down setpoint This parameter can be set to between 0 and 96 hours and defines the maximum Sub function: Up time period between the start of two defrost cycles. e 2 Minimum Time / dit This parameter can be set to between 0 and 240 minutes and defines the mini1 Click: Temperature setpoint mum duration of a defrost cycle. During this period, the ERC 102 will not check Sub function: Down the temperature. Once the minimum time has expired, the temperature will be checked and if the Terminate Temperature dtt has been reached, the defrost 1 Click: Temperature setpoint cycle willSubend. If dtt has not been reached, defrost will continue until either dtt is function: Up reached or the Maximum Time dAt reached, whichever occurs first. nallity: 2 e 1 Click: Temperature setpoint Sub function: Down nallity: Maximum Time / dAt This parameter can be set to between 0 and 240 minutes and defines the maximum duration of a defrost cycle. 1 Click: Temperature setpoint function: Up allow a maximum time to be entered which is less than the The ERCSub 102 will not minimum time, or a minimum time which is more than the maximum time. e Drip Off1 Time / dot setpoint Click: Temperature Sub function: Downan electrical heater. This parameter can be set to between This is only used with 0 and 60 minutes and defines how long the delay is between the heater being switched off and the compressor starting again. 32 ERC 102 Reference manual – 7 PARAMETERS 1 Click: Temperature setpoint Sub function: Down 2 e 1 Click: Temperature setpoint Sub function: Up nallity: e 2 nallity: e allity: allity: 2 nallity: e Fan Delay after Defrost / Fdd This parameter can be set to between 0 and 60 seconds and defines how 1 Click: Temperature setpoint long theSub delay is between the start of the compressor after defrost and the function: Up fan starting again. Fan Start Temperature / Ftd Temperature setpoint This only1 Click: applies if an evaporator temperature sensor is fitted. This parameter Sub function: Down determines at what evaporator temperature the fan will start after a defrost cycle is complete. If the time set in Fdd occurs before the temperature set in Ftd, the fan will start in line with Fdd. If the temperature set in Ftd occurs first, then the fan will start in 1 Click: Temperature setpoint line withSub Ftd. It is Up therefore a case of whichever parameter’s setting is reached first function: 1 Click: Temperature setpoint which determines when the fan starts. Sub function: Down Defrost Fan On / dFA 1 Click: Temperature setpoint Set to Sub yES,function: the fan Up will constantly run during defrost cycles. Set to nO, the fan will not run during defrost cycles. Initial Defrost Interval / idi The initial defrost interval determines the time for first defrost after power-up. The 1 Click: Temperature initial defrost is mainlysetpoint intended for factory testing of the defrost functionality and Sub function: Down can be set to expire after a number compressor cycles according to the setting 1 Click: Temperature setpoint of parameter idd Sub function: Up. During normal operation, the defrost counter will be saved in memory and restored after power loss, making the initial defrost unnecessary. 1 Click: Temperature setpoint Sub function: Down Initial Defrost Duration / idd The initial defrost duration is the number of compressor cycles before the initial defrost is deactivated. 0: idi No initial defrost 1 Click: Temperature setpoint 1-998: number of Up compressor cycles before deactivation Sub function: 999: Initial defrost always active. 1 Click: Temperature setpoint Sub function: Down Defrost On Compressor Time / dCt If this parameter is set to yES, then defrost cycles are based on the total time the compressor has been running. If this parameter is set to nO, then defrost cycles are related to elapsed time, regardless of how long and how often the compressor has been on. 1 Click: Temperature setpoint Sub function: Down ERC 102 Reference manual – 7 PARAMETERS 33 mode 1 Click: Temperature setpoint Sub function: Up 7.5 Fan / FAn The fan parameters are all related to energy saving, and to redistribution of air within the cabinet to reduce the amount of energy spent on cooling. 2 nallity: 2 e nallity: ERC menu code Default Min Max Unit Conv Fan FAn Fan always On FAo yES no yES no Fan stop time on door open Fdt 999 0 999 no 0 0 240 no 0 Temperature 0 setpoint240 1 Click: Sub function: Up 0 0 960 no Fan On Delay Fod Fan Stop delay FSd Fan On Cycle FoC Fan Stop Cycle FSC 2 0 0 960 Unit Scale Default Access Shop Ser OEM 1 -- -- RW 1 Click: Temperature setpoint Sec 1 -- -- RW Sub function: Down Sec 1 -- -- RW Sec 1 -- -- RW no Sec 1 -- -- RW no Sec 1 -- -- RW Fan Always On / FAo 1 Click: Temperature setpoint If this parameter Sub function:is Upset to yES, all other parameters in this section about the fan are deactivated. NOTE: If FAo is set to nO, then the following parameters will be applied. e 2nallity: Fan stop time on door open: Fdt The maximum time the fan will be stopped after the door has been opened. 1 Click: setpoint 0: fan will notTemperature stop under opening Sub Subfunction: function:Up Down 1-998: number of seconds fan will be stopped during door opening 999: fan will be stopped as long as the door is open e nallity: e 2 1 Click: Temperature setpoint function: Up Fan On Sub Delay / Fod 1 Click: Temperature setpoint Fan Stop Delay / FSd Sub function: Down If this parameter and FSd are both set to zero then the fan runs whenever the compressor runs. 2nallity: Fod defines the fan delay (in seconds) after a compressor Click: Temperature setpoint cut-in. 1Sub Subfunction: function:Up Down FSd defines the fan delay after a compressor cut-out. e nallity: e 1 Click: Temperature setpoint Up Subfunction: function: Down Fan On Sub Cycle / FoC Fan Stop Cycle / FSC When the compressor is off, and FoC or FSC are not zero, the fan runs in cycles according to FoC and FSC. Example: FoC = 120 [sec] and FSC = 120 [sec] means that the fan runs for half the time when the compressor is off. When the compressor is on, the fan is always on (according to FAo and Fod). 1 Click: Temperature setpoint Sub function: Down 34 ERC 102 Reference manual – 7 PARAMETERS 1 Click: Temperature setpoint mode 2 2nallity: 1 Click: Temperature setpoint Sub function: Up 7.6 Energy Management / Eng ERC menu code Energy management Default Min Max Unit Conv Unit Scale Default Access Shop Ser OEM Eng Shop Light Day SLd 50 0 100 no Shop Light Night SLn 50 0 100 no % Temperature 1 RW RW RW 1 Click: setpoint % 1 RW RW RW Sub function: Down Eco Activity delay EAd 0 0 360 no min 1 Eco Light delay ELd 5 0 10 no min 1 RW RW RW -- RW RW Light Blocking delay Lbd 0 0 360 no min 1 -- RW RW Eco Temperature Offset Eto 4.0/7.2 0,0 10.0/18.0 C/F r K/°R .1 -- RW RW NOTE: Some of these parameters require the installation of the Danfoss Ambient Light Sensor. e 1 Click: Temperature setpoint nallity: The Danfoss USB Gateway in combination with KoolProg software allows for real time measurement of the Sub function: Up e 2 nallity: 2 e nallity: e current light intensity. Danfoss recommends testing and adjusting SLd and SLn values according to customers’ specific needs. 1 Click: Temperature setpoint Sub function: Shop Light Day /Up SLd Shop Light Night / SLn These parameters are set as the percentage of the maximum light and determine when the device moves into or out of Eco mode for power-saving purposes. SLd is the amount of ambient light which will cause the device to move to normal / serving mode from Eco mode (normally occurs in the morning). 11 Click: Click: Temperature Temperature setpoint setpoint Subfunction: function:Up Down Sub SLn is the amount of ambient light which will cause the device to move to Eco mode from normal / serving mode (normally occurs in the evening). 1 Click: Temperature setpoint SubDelay function:/ Down Eco Door EAd The transition from Eco to normal mode and vice versa occurs on a change in light 1 Click: Temperature setpoint level or door activity. Sub function: Up NOTE: A door sensor is required. Eco Light Delay / ELd 1 Click: Temperature setpoint This parameter causes a delay to the switch from Normal to Eco mode when the Sub function: Down shop lights are switched on or off. The ambient light sensor detects the change in light level and causes a switch mode. With this parameter set to zero, the switch off mode occurs immediately. If not set to zero (max: 10 minutes), then the change will be delayed by the number of minutes set. 1 Click: Temperature setpoint Sub function: Down ERC 102 Reference manual – 7 PARAMETERS 35 2 Light Blocking delay / Lbd If the cooler is placed where the ambient light is unstable, the ambient light sensor can cause the cooler to toggle between ECO and normal mode. The light blocking delay disables the light-sensor for a given time after ambient light change from bright to dark, so that the cooler stays in ECO mode for at least this time.1 Click: When the cooler is in serving or pull-down mode, the light sensor is Temperature setpoint de-activated and Up a change to ECO mode will be determined by the door-sensor. Sub function: 0: No blocking of the ambient light sensor. nallity: 02 e tionallity: Eco Temperature Offset / Eto This parameter gives a relative temperature in degrees. It is the difference in temperature for Eco mode operation compared to Normal mode. NOTE: Setting a temperature offset may be illegal in some jurisdictions. 1 Click: Temperature setpoint mode Sub function: Up 1 Click: Temperature setpoint Sub function: Down 7.7 Pull Down / Pud Pull down (sometimes known as Super Cool) is a procedure for improving cooling performance, accelerating the time used to reach the desired temperature. Pull Down settings overrule all other settings. ERC menu code Pull Down Default Min Max Unit Unit Scale Default Access setpoint Conv 1 Click: Temperature Shop Ser OEM Sub function: Down Pud Pull-down Initiate Temperature Pit Pull-down Cycling PCy 50.0/122.0 -40.0/-40.0 50.0/122.0 30 0 360 C/F a °C/°F .1 -- -- RW no min 1 -- -- RW Pull-down defrost Interval Pdi 15 0 48 no hour 1 -- -- RW Pull-down duration Pdd 24 0 48 no hour 1 -- -- RW Pull-down limit temp PLt 0.0/32.0 -55.0/-67.0 55.0/131.0 C/F a °C/°F .1 -- -- RW Pull-down reduction temp △t Prt 0.1/0.2 C/F r K/°R .1 -- -- RW 36 ERC 102 Reference manual – 7 PARAMETERS 0,0 10.0/16.0 2 nallity: e 2 nallity: 2 e nallity: e 2 nallity: 2 e nallity: e 2 nallity: e 1 Click: Temperature setpoint Sub function: Up Pull Down Initiate Temperature / Pit This parameter indicates the temperature which causes a pull down to start. If the temperature measured inside the cabinet exceeds this value for longer than one hour, then pull down will start. The compressor will have already cut-in, so the only 1 Click: Temperature setpoint Up effect is Sub to function: stop defrost cycles until the desired temperature is reached. The period of one hour is fixed and cannot be altered. 1 Click: Temperature setpoint Pull Down Cycling / PCy Sub function: Down This is the duration in minutes of the compressor cycling at the reduced set point temperature. Once the desired Pull Down Limit Temperature PLt has been reached 1 Click: Temperature setpoint during Pulldown, the compressor will continue to cycle on / off for the duration of Sub function: Up PCy. At the end of the period defined by PCy, the Set Point temperature will return to normal and Pulldown will cease. 1 Click: Temperature setpoint Pull Down Defrost Interval / Pdi Sub function: Down Even though most applications do not need Defrost during Pull Down, an extended defrost during pull down can be applied. This is the time between defrost cycles during Pull Down. It is setpoint measured in hours and can be up to 48 hours. During Pull 1 Click: Temperature Sub function: Down, this settingUpoverrides the Defrost Interval and Defrost Time settings (see the Defrost section). 1 Click: Temperature setpoint Sub function: Down/ Pdd Pull Down Duration You can 1choose to limitsetpoint the maximum Pull Down time. Once this time value Click: Temperature function: (max. 48Sub hours) isUp reached, Pull Down will stop regardless of whether the desired pull-down temperature has been reached. Pull Down Limit Temperature / PLt This parameter sets thesetpoint minimum allowed temperature during pull-down, 1 Click: Temperature function: Down In order Sub to protect valuable contents you must always specify the absolute mini1 Click: Temperature setpointin your application. mum temperature allowed Sub function: Up For Glass Door Merchandisers 0°C/32°F protects bottles from freezing; for Commercial Fridges you may opt for a slightly higher temperature (e.g. 2°C) 1 Click: Temperature setpoint Pull Down Reduction Sub function: Down Temperature Δt / Prt ERC 102 calculates a lower set-point during Pull Down mode to increase the cooling capacity of your appliance. For each hour the cabinet temperature is above the Pull down initiate temperature, the set-point is reduced with the value of Prt. ERC 102 Reference manual – 7 PARAMETERS 1 Click: Temperature setpoint Sub function: Down 37 mode 2 1 Click: Temperature setpoint Sub function: Up 7.8 Automatic Heater Control / AHC Automatic Heater Control applies reverse cooling mode (heating) to your refrigeration appliance. This feature requires: A) that your appliance is exposed to ambient temperatures below the desired temperature in your cabinet (e.g. very cold climates and outdoor use) B) a special heater (for example a large defrost heater) built in to your appliance. ERC menu code Default Min Max no no yES setpoint Unit 1 Click: Unit Temperature Scale Default Access Conv Sub function: Down Shop Ser OEM Auto-Heater Control AHC Automatic heater mode enable AuH Energy mode delay End 60 0 360 no min 1 -- -- RW Heater displacement temperature Hdi 2.0/3.0 0.0/0.0 50.0/90.0 C/F r K/oR .1 -- -- RW no -- -- RW nallity: 2 e 1 Click: Temperature setpoint Sub function: Up nallity: Automatic Heater Mode Enable / AuH This setting is normally set to nO. 1 Click: Temperature setpoint End and Hdi apply. When set to yES, parameters 2 e Sub function: Up nallity: Energy 1Mode Delay /setpoint End Click: Temperature Subdelay function: This is the inDown minutes between the heater and the compressor operation. 1 Click: setpoint The heater is Temperature not allowed to start until this number of minutes has expired after Sub function: Up the compressor has cut out and vice versa. e Heater Displacement Temperature / Hdi 1 Click: Temperature setpoint This is the Subtemperature function: Down relative to (below) the desired temperature. 38 ERC 102 Reference manual – 7 PARAMETERS 1 Click: Temperature setpoint mode 2 1 Click: Temperature setpoint Sub function: Up 7.9 Condenser Protection / Con NOTE: A condensor temperature sensor is required to use these parameters. Condenser protection is generally used in dusty environments where the condenser may accumulate a layer of dust or dirt and therefore be at risk of overheating. ERC menu code Condenser Protection Con Condenser Alarm Limit CAL Default Min Max Unit Conv 80/176 0/32 85/185 C/F a Unit Scale Default Access Shop Ser OEM 1 Click: Temperature setpoint Sub°C/°F function:1 Down -- -- RW Condenser Block Limit CbL 85/185 0/32 85/185 C/F a °C/°F 1 -- -- RW Condenser OK limit CoL 60/140 0/32 85/185 C/F a °C/°F 1 -- -- RW Condenser Low Limit CLL 5 -20/-4 20/68 C/F a °C/°F 1 -- -- RW nallity: 2 e 1 Click: Temperature setpoint Sub function: Up nallity: 2 e nallity: 2 e nallity: e Condenser Alarm Limit / CAL 1 Click: Temperature This parameter sets thesetpoint temperature for the condenser at which an alarm will Sub function: Up be generated. Condenser Block Limit / CbL 1 Click: Temperature setpoint This parameter sets thesetpoint temperature which if reached will cause the compressor function: Up 1Sub Click: Temperature to switchSuboff. function: Down Condenser OK Limit / CoL 1 Click: Temperature setpoint This parameter sets the temperature at which the compressor is allowed to function: Up 1Sub Click: Temperature setpoint start again after the temperature set in CbL above has been exceeded and the Sub function: Down compressor stopped. Condenser Low Limit / CLL This parameter sets the lowest (condenser) temperature at which the 1 Click: Temperature setpoint compressor is allowed Sub function: Down to start. ERC 102 Reference manual – 7 PARAMETERS 1 Click: Temperature setpoint 39 mode 2 nallity: 2 e nallity: 1 Click: Temperature setpoint Sub function: Up 7.10 Display / diS ERC menu code Default Min Max Unit Conv Display diS Display Unit CFu -C -C -F no Display Resolution rES 0.1 0.1 1 no Display Range Limit Unit Default Access Shop Ser OEM 1 Click: Temperature RW setpoint RW RW Sub function: Down -- -- RW rlt no no yES no Display Delay ddL 0 0 10 no Sec Display Offset doF 0.0/0.0 C/F r K/oR Lock-time After defrost dLt 15 0 60 no min Show Economy state SEC no no yES no -10.0/-18.0 10.0/18.0 Scale -- -- RW 1 -- -- RW 1 -- -- RW -- -- RW -- -- RW Show Pull Down state SSC no no yES no -- -- RW Show Defrost SdF yES no yES no -- -- RW Display Intensity din 10 1 10 no 1 RW RW RW Click: Temperature This section deals with parameters1for the display.setpoint Sub function: Up NOTE: Some display parameters can be set in such as way that they may be illegal in some jurisdictions. Please check local legislation. e 1 Click: Temperature setpoint DisplaySub Unit / CFu function: Up This parameter sets the display to Fahrenheit or Celsius. Switching from one to the other will cause all temperature settings to be automatically updated accordingly. 2 Display Resolution / rES This parameter can be set to 0.1, 0.5 or 1 and affects the way the temperature is displayed. With the parameter set to 1, the display will only ever show tempera1 Click: Temperature setpoint tures rounded to the nearest whole degree. At 0.5, it will round the temperature to Sub function: Down the nearest half degree for display. 1 Click: Temperature setpoint For example, 3.3 degrees will be shown in the display as 3.5 degrees and 3.9 as 4.0. Sub function: Up With the parameter set to 0.1, no rounding occurs. 1 Click: Temperature setpoint This parameter does not affect the temperature itself, merely the display. Sub function: Down nallity: e Display Range Limit / rLT In some Point of Sales applications you may want to show the desired instead of the real temperature. This parameter sets whether the displayed temperature is the actual temperature or whether it is restricted to the cut-in / cut-out limits. Set to nO means that the actual temperature will de displayed. The parameter is set to nO by default. 40 1 Click: Temperature setpoint Sub function: Down ERC 102 Reference manual – 7 PARAMETERS e 1 Click: Temperature setpoint Sub function: Up Display Delay/ ddL In order to provide a realistic temperature appearance for an application, a display delay can be set. The parameter sets the time constant τ (tau) of the moving average filter for the display. Physically, one time constant represents the time it takes the system’s step-response to reach 66% of its final value and five time-constants the time 1 Click: Temperature setpoint it takes to reach 99% of its final value. Sub function: Down The parameter can be set from 0 to 10 minutes. 2 nallity: 2 e 1 Click: Temperature setpoint Sub function: Up nallity: 2 e nallity: 2 e Display Offset / doF This parameter is a relative value and allows the temperature displayed to be 1 Click: Temperature setpoint differentSub tofunction: the temperature measured. For instance, at a measured temperature Up of 7°C and doF set to -2K, the displayed temperature will be 5°C instead. Lock Time After Defrost / dLt Click:to Temperature In order1not show a setpoint rising temperature during defrosting, the displayed temSub function: Down perature is locked at the temperature shown at the start of the defrost cycle for the 1 Click: Temperature setpoint numberSub of function: minutes Up set in this parameter. 0 = no lock. nallity: 2 e 1 Click: Temperature Show Economy Statesetpoint / SEC Sub function: Down If set to yES, this parameter causes the display to show ECO when the system is in 1 Click: Temperature setpoint ECO mode. Sub function: Up If set to nO, the temperature continues to be displayed. nallity: e Show Pull down state / SSC 1 Click: Temperature setpoint If set to yES, this parameter causes the display to show SC when the system is in function: Down setpoint 1Sub Click: Temperature Pull Down Sub mode. function: Up If set to nO, the temperature continues to be displayed. Show Defrost / SdF Click: Temperature setpoint If set to1yES, this parameter causes the display to show DEF when the system is in Sub function: Down defrost mode. If set to nO, the temperature continues to be displayed. ERC 102 Reference manual – 7 PARAMETERS 1 Click: Temperature setpoint 41 e 1 Click: Temperature setpoint Sub function: Up Display Intensity / din ERC 102 can have its display intensity (brightness) set in one of two ways: A) with a Danfoss ambient light sensor attached, the brightness of the display is adjusted automatically according to the ambient light level (see the Assignments section) B) when no ambient light sensor is attached, the display intensity can be set to 1 Click: Temperature setpoint a fixed intensity. Sub function: Down Both options are on a scale of 1 to 10, where 10 is the brightest. 7.11 Assignments / ASi For more details on how to set parameters - see chapter 6. ERC menu code Default Min Max Unit Conv Unit Scale Default Access Shop Ser OEM Assignments ASi S1 Config S1C Stn Stn dig no -- -- RW S2 Config S2C Stn Stn dig no -- -- RW S3 Config S3C Stn Stn dig no -- -- RW S1 Application S1A SCo nC doo no -- -- RW S2 Application S2A nC nC doo no -- -- RW S3 Application S3A nC nC doo no -- -- RW DI Config diC dio doC dio no -- -- RW DO1 Config o1C CoP CoP HEt no -- -- RW DO2 Config o2C dEF 0 Lig no -- -- RW DO3 Config o3C FAn 0 Lig no -- -- RW DO4 Config o4C Lig 0 Lig no -- -- RW Button 1 Short Config b1C noP tP noP no -- -- RW Button 1 Long Config b1L PoF tP PoF no -- -- RW Button 2 Short Config b2C dEF tP noP no -- -- RW Button 3 Short Config b3C tP tP noP no -- -- RW Button 3 Long Config b3L ECo tP PoF no -- -- RW Button 4 Short Config b4C tn tP noP no -- -- RW Button 4 Long Config b4L Lig tP PoF no -- -- RW Pass-word level1 PS1 0 0 999 no RW RW RW Pass-word level2 PS2 0 0 999 no -- RW RW Pass-word level3 PS3 0 0 999 no -- -- RW Cabinet Light Control Source CLC Lig Lig LEC no -- -- RW Door close delay dCd 0 0 300 no Sec 1 -- -- RW Light off delay Lod 0 0 300 no Sec 1 -- -- RW 42 ERC 102 Reference manual – 7 PARAMETERS mode 1 Click: Temperature setpoint Sub function: Up 7.12 Service Information / Ser The parameters in the following section are READ ONLY and cannot be changed by the user. They provide information for technicians and OEM users. NOTE: the only parameters that can be configured are: oEL, oEn, oEH. These parameters allow OEMs to enter their own product code. ERC menu code Default Min Max Unit Unit Scale Default Access setpoint Conv 1 Click: Temperature Shop Ser OEM Sub function: Down Service SEr DI Sdi --- oFF on no Voltage value uAC --- 0 270 no DOs Status ouS --- IIII IIII no Relay 1 counter rL1 --- 0 999 no -- R- RVac 1 -- R- R- 1000 1000 -- R- R- -- R- R- Relay 2 counter rL2 --- 0 999 no 1000 1000 -- R- R- Relay 3 counter rL3 --- 0 999 no 1000 1000 -- R- R- Relay 4 counter rL4 --- 0 999 no 1000 1000 -- R- R- interval Counter int --- 0 999 no min 1 -- R- R- Defrost time counter dnt --- 0 999 no min 1 -- R- R- Door open counter ont --- 0 999 no 1 1 -- R- R- SW version Fir SWVER -32768 32767 no R- R- R- HW version HAr HWVER -32768 32767 no R- R- R- OrderNoLow OnL ORNOL -32768 32767 no -- -- -- OrderNoHigh OnH ORNOH -32768 32767 no -- -- -- OEM code Low oEL 0 0 999 no R- R- R- OEM code Middle oEn 0 0 999 no R- R- R- OEM code High oEH 0 0 999 no R- R- R- Parameter version PAr PARVER -32768 32767 no R- R- R- Last change CHA 0 0 999 no 1 -- -- -- Manufacturing date CHd 0 0 999 no 1 -- R- R- 1 Copy Key ID Cid 0 0 999 no Set as Default SFC no no yES no -- -- RRW RW RW ERC 102 Reference manual – 7 PARAMETERS 43 8. TECHNICAL SPECS Power Supply 100 V AC - 240 V AC, switch mode power supply Average 0 7 W Rated Power 4 Inputs: 3 Analogue & Digital, 1 Digital; user specific assignment Input • Air / Evaporator / Condenser • Door sensor: All types, user specific • Light sensor: Danfoss ECO light sensor • DP for remote communication DO1 (Compressor relay): DO4 Output UL60730 120 V ac: 16A resistive/ FLA16 / LRA72. 240 V ac: 10A resistive /FLA10 /LRA60. 8 A resistive, FLA2/ LRA12, TV-1 EN60730 16(16)A 8 A resistive, 2(2) A DO5 FLA2/ LRA12, TV-1 8 A resistive, 2(2) A DO6 FLA2/ LRA12, TV-1 8 A resistive, 2(2) A Max 10 A total DO4-6 Probes Danfoss NTC sensors and Danfoss ECO accessories (300 - 3,000 mm) Connectors Modular connector system for OEM customers, with optional output screw terminal adapter; Input connector type: Rast2 5 Edge connectors; Output connector type: RAST 5 Standard Programming Programming with Danfoss ERC docking station, integrated system Assembly 3 types for all controls: Front mounting (patents pending); brackets; fully integrated solution (requires OEM specific design of mounting hole) Display LED display, 3 digit, decimal point and multi functionality icons; °C/F scale Keypad 4 buttons (integrated IP65 design), 2 left, 2 right; user programmable Operating Conditions 0 °C to 55 °C, 93% rH Storage Conditions -40 °C to 85 °C, 93% rH Range of Measurement -40 °C to 85 °C Protection front: IP65/rear: water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to IP00 Environmental Pollution degree II, non-condensing Resistance to heat & fire Category D (UL94-V0) EMC category Category I Operating Cycles Approvals Compressor relay: more than 175,000 at full load (16A(96A)) R290/R600a : EN/IEC 60079-15:2005 Glow wire according to EN/IEC 60335-1 IEC/EN 60730 UL60730 NSF CQC GOST R 60730 Note: These approvals are only valid when using the accessories listed in this document IMPORTANT NOTE The inputs are not galvanic separated and are connected directly to the mains supply! Dimensions: 36,5 mm 71 mm 28,5 mm Front mounting 78,25 mm 71 mm 28 mm 30 mm 78,25 mm 82,25 mm 44 ERC 102 user manual – 8 TECHNICAL SPECS Rear mounting APPENDIX I: PARAMETER QUICK LIST ERC menu code Description Thermostat tHE Thermostat settings Set point adjustment ratio SPr Current setpoint adjustment value diF * SPr Differential diF Thermostat differential High Set Point HSE Upper limit of thermostat set point Low Set Point LSE Lower limit of thermostat set point Air Temp Adj. tAd Applies to non-Danfoss temperature sensors only ERC menu code Description Alarm ALA Alarm settings High Alarm delay Htd Alarm delay on high temperature Low Alarm delay Ltd Alarm delay on low temperature High Temp Alarm HAt Alarm is activated above this temperature (Celsius) Low Temp Alarm LAt Alarm is activated below this temperature (Celsius) Pulldown delay Pdd Alarm delay during pulldown (0-960 minutes) (high temperature only) Door Open delay dod Alarm delay for door open (0-60 minutes) Alarm Buzzer Duration Abd Alarm buzzer duration in minutes (0=no buzzer) Auto Clearance of Alarm/Error ACA yES: alarm auto-clears if system returns to normal; nO : alarm state maintained regardless ERC menu code Description Compressor CoP Compressor settings Min run time Crt Minimum time compressor must run 0-30 minutes Min Stop time CSt Min time compressor must idle 0-30 minutes Max Off time Cot Max time compressor must idle 0-480 minutes Compressor door open delay Cdd Minutes before compressor stops when door opened Error run time Ert Compressor run time if temperature sensor is not working (0-60 minutes) Error stop time ESt Compressor stop time if temperature sensor is not working (0-60 minutes) Minimum Cutin voltage uLi When compressor is off: Lowest compressor start voltage (0-270 V) Minimum cut-out voltage uLo When compressor is on: Lowest operation voltage (0-270 V) Maximum voltage uHi When compressor is on: Highest operation voltage (0-270 V) Power On Delay Pod Delay in seconds after power-on before outputs active (change with care) Power Factor PFA Phasic angle in degrees. Changing this may give decreased relay lifetime Power-on temperature Pot If the temperature of compressor at power-on exceeds this then Power On Delay does not apply ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST 45 ERC menu code Description Defrost dEF Defrost Settings Def. type dFt no: Defrost function is disabled EL: Electrical or time defrost Hgd: Hot gas defrost (contact Danfoss for details) nat:Off-cycle defrost (natural defrost) Def terminate temp dtt Temperature at which defrost cycle will stop Def Min Interval dii The minimum time in hours between the start of each defrost cycle Def Max Interval dAi The maximum time in hours between the start of each defrost cycle Def Min Time dit The minimum duration of a defrost cycle in minutes Def Max time dAt The maximum duration of a defrost cycle in minutes Drip off time dot The duration in minutes of the drip-off time at the end of a defrost cycle Fan delay after Defrost Fdd The duration in seconds before the fan starts after a defrost cycle Fan start Temp Ftd The temperature at which the fan will start after a defrost Defrost Fan on dFA Whether the fan will run during a defrost cycle Initial Defrost Interval idi The number of hours after power-up before the first defrost cycle starts Defrost on compressor time dCt Whether the defrost cycles are measured by elapsed time (nO) or compressor run time (yES) Fan ERC menu code Description FAn Fan settings Fan always On FAo nO: fan parameters below active. yES: Fan is always on Fan On Delay Fod Delay in seconds before fan starts after compressor starts Fan Stop delay FSd Delay in seconds before fan stops after compressor stops Fan On Cycle FoC The number of seconds the fan runs when the compressor is off Fan Stop Cycle FSC The number of seconds the fan does not run when the compressor is off ERC menu code Description Energy management Eng Energy Management Shop Light Day SLd When ambient light is above this level, Eco mode is cancelled. Requires light sensor Shop Light Night SLn When ambient light is below this level, Eco mode is enabled. Requires light sensor Eco Activity delay EAd Minutes delay after last door opening until ECO mode is enabled; 0: disable Eco Light delay ELd Delay [min] between detection of shop light on/off and ECO mode activation / suspension Eco Temperature Offset Eto Temperature increase for Eco mode relative to normal mode 46 ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST ERC menu code Pull Down Pud Description Pull down settings Pull-down Initiate Temperature Pit Pull-down Cycling PCy Minimum duration [min] of the pull-down mode, starting at PiT Pull-down defrost Interval Pdi Defrost interval during pull-down. Over-rules the defrost interval in normal mode. Pull-down duration Pdd Maximum duration [min] of the pull-down mode, starting at PiT Pull-down limit temp PLt A safety feature; the lowest temperature allowed during pull-down. Pull-down reduction temp Δt Prt A calculation value for pull-down performance improvement. Instructions: See manual ERC menu code If the cabinet temperature is above this temperature for >1h, pull-down mode is activated Description Auto-Heater Control AHC Auto-Heater settings (only if heater fitted for outdoor use in cold climates) Automatic heater mode enable AuH yES: Activate heater if ambient temperature is below desired cabinet temperature Energy mode delay End Delay in minutes between heater and compressor operation Heater displacement temperature Hdi Heater displacement or OFFSET temperature relative to desired temperature. ERC menu code Description Condenser Protection Con Condenser Alarm Limit CAL If condenser sensor exceeds this temperature, alarm is activated Condenser Block Limit CbL If this temperature is exceeded, compressor will be stopped. Condenser OK limit CoL Temperature at which compressor may start after a stop due to exceeding CbL Condenser Low Temp. Limit CLL Temperature below which the compressor is not allowed to start ERC menu code Condenser protection settings Description Display diS Display Unit CFu Display settings F: Fahrenheit; C: Celsius Display Resolution rES Display resolution for temp: 0.1, 0.5 or 1.0 C/F Display Range Limit rlt Limits displayed temperature to actual setpoint +/- differential; may be illegal in some countries Display Delay ddL Time period for moving average temperature display Display Offset doF Display a different temperature relative to measured temperature Lock-time After defrost dLt Display lock time after defrost [0-60 min] Show Economy state SEC yES: display will show “Eco” when in Eco mode. nO: temperature will be shown Show Pull Down state SSC yES: “SC “ will be displayed during Pull down; nO: “SC “ will not be displayed. Show Defrost SdF yES: display will show deF during defrost ; no: Display will show temp Display Intensity din Display intensity when no ambient sensor; min intensity with sensor ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST 47 ERC menu code Description Assignments ASi Assignment of inputs and outputs S1 Config S1C Sensor type input 1 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input S2 Config S2C Sensor type input 2 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input S3 Config S3C Sensor type input 3 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input S1 Application S1A Application to be controlled with Sensor D. nC: Not connected SCo: Temperature control EuA: Evaporator temperture Con: Condenser temperature (Condenser cleaning) LS1: Light sensor(Ldr), Luminens, delicated for Economy detection LS2: Light sensor(Ldr), Luminens, delicated for LED intensity scope LS3: Light sensor(Ldr), Luminens, delicated for both Economy detection and LED intensity scope doC: Door contact, Contact closed when door closed doo: Door contact, Contact open when door closed S2 Application S2A Application to be controlled with Sensor C. nC: Not connected SCo: Temperature control EuA: Evaporator temperture Con: Condenser temperature (Condenser cleaning) LS1: Light sensor(LDR), Luminens, delicated for Economy detection LS2: Light sensor(LDR), Luminens, delicated for LED intensity scope LS3: Light sensor(LDR), Luminens, delicated for both Economy detection and LED intensity scope doC: Door contact, Contact closed when door closed doo: Door contact, Contact open when door closed S3 Application S3A Application to be controled with Sensor B. nC: Not connected SCo: Temperature control EuA: Evaporator temperture Con: Condenser temperature (Condenser cleaning) LS1: Light sensor(LDR), Luminens, delicated for Economy detection LS2: Light DI Config diC Sensor A (digital) doC: Door contact, Contact closed when door closed doo: Door contact, Contact open when door closed dio: One wire digital communication buS: MODBUS communication DO1 Config o1C CoP: Compressor; PiL: Pilot Relay (No zero-cross); HEt: Inverse output, Heating application DO2 Config o2C no:Not used; dEF: Elec defr heater/hot gas valve;ALA:Alarm output;FAn:Fan control;Lig:Light control DO3 Config o3C nO: Not used; ALA: Alarm output; FAn: Fan control; Lig: Light control DO4 Config o4C nO: Not used; ALA: Alarm output; Lig: Light control Button 1 Config b1C Lower left button configuration. tP:Increase Setpoint tn: Decrease setpoint ECo: Toggle Eco mode Lig: Toggle light dEF: Toggle defrost SuP: Activate Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity noP: Not operating 48 ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST ERC menu code Description Assignments ASi Assignment of inputs and outputs Button 2 Config b2C Upper left button configuration. tP:Increase Setpoint tn: Decrease setpoint ECo: Toggle Eco mode Lig: Toggle light dEF: Toggle defrost SuP: Activate Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity noP: Not operating Button 3 Config b3C Upper right button configuration. tP:Increase Setpoint tn: Decrease setpoint ECo: Toggle Eco mode Lig: Toggle light dEF: Toggle defrost SuP: Activate Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity noP: Not operating Button 4 Config b4C Lower right button configuration. tP:Increase Setpoint tn: Decrease setpoint ECo: Toggle Eco mode Lig: Toggle light dEF: Toggle defrost SuP: Activate Super-Cool /Pull-down diP : Increase display intensity din : Decrease display intensity noP: Not operating Pass-word level1 PS1 Level 1 Password (End user, shop owner), 0= disabled Pass-word level2 PS2 Level 2 Password (Technical field service), 0= disabled Pass-word level3 PS3 Level 3 Password (OEM), 0= disabled; choose a secure number, e.g. 735 Cabinet Light Control Source CLC Cabinet light management Lig: button only” Ldo: door (and button if defined) only LEC: Economy (and button if defined) only Light off delay Lod Light off delay [sec] after door has been closed ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST 49 ERC menu code Description Service SEr Service DI Sdi DI: physcial DI pin state (ON; OFF) Voltage value uAC Current main power supply voltage DOs Status ouS Current relay open / closed status. IIII = All Relay on (Upper bar for on, Lower bar for off ) II = DO1 On, DO2 Off, DO3 & DO4 NA (No bar if relay not mounted) IIII = All Relay off (Upper bar for on, Lower bar for off ) Relay 1 counter rL1 Thousands of cycles of compressor relay since manufacture Relay 2 counter rL2 Thousands of cycles of no.2 relay since manufacture Relay 3 counter rL3 Thousands of cycles of no. 3 relay since manufacture Relay 4 counter rL4 Thousands of cycles of no. 4 relay since manufacture interval Counter int Compressor run time since last defrost Defrost time counter dnt Duration of last defrost cycle [min] Door open counter ont ont/100 = Number of door openings since last reset Serial numbe Snu Serial number given at manufacturing SW version Fir Danfoss software version number HW version HAr Danfoss hardware version number OrderNoLow OnL Danfoss order code number OrderNoHigh OnH Danfoss order code number Parameter version PAr OEM parameter version number [requires EKA copy key update] Last change CHA Not used Manufacturing date CHd Programme date WWY: week number and year number (2010-19) Copy Key ID Cid Copy key used for last program Set as Default SFC Resets all parameters to last good OEM settings 50 ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST APPENDIX II: CODE NUMBERS AND LENGHTS Code no. I-Pack Type Approvals 230V, CQC/UL/CE GDM-front Code no. I-Pack Type Approvals 230V, CQC/UL/CE Defrost sensors* ERC 102C RED LED without buzzer 080G3102 PVC Standard (C2), 470 mm, 2-pole 077F8780 ERC 102D RED LED without buzzer 080G3103 PVC Standard (C2), 1000 mm, 2-pole 077F8786 ERC 102C BLUE LED without buzzer 080G3106 PVC Standard (C2), 1500 mm, 2-pole 077F8790 ERC 102D BLUE LED without buzzer 080G3107 PVC Standard (C2), 2000 mm, 2-pole 077F8794 PVC Standard (C2), 3000 mm, 2-pole 077F8798 PVC Standard (C3), 470 mm, 3-pole 077F8750 CFF-front ERC 102C RED LED with buzzer 080G3113 PVC Standard (C3), 1000 mm, 3-pole 077F8756 ERC 102D RED LED with buzzer 080G3112 PVC Standard (C3), 1500 mm, 3-pole 077F8760 ERC 102C BLUE LED with buzzer 080G3116 PVC Standard (C3), 2000 mm, 3-pole 077F8764 ERC 102D BLUE LED with buzzer 080G3117 PVC Standard (C3), 2200 mm, 3-pole 077F8766 PVC Standard (C3), 3000 mm, 3-pole 077F8768 Light-sensors Light sensor, 1000 mm (C3), 3-pole 080G3311 Other sensors Light sensor, 2000 mm (C3), 3-pole 080G3313 TPFE low temp (C1), 1000 mm, 3-pole 077F8657 Light sensor, 3000 mm (C3), 3-pole 080G3315 TPFE low temp (C1), 2000 mm, 3-pole 077F8665 TPE precision (C1), 500 mm, 3-pole 077F8724 TPE precision (C1), 1000 mm, 3-pole 077F8725 Door-sensors Door-sensor, 1000 mm (C4), 3-pole 080G3332 TPE precision (C1), 1500 mm, 3-pole 077F8726 Door-sensor, 2000 mm (C4), 3-pole 080G3334 TPE precision (C1), 2000 mm, 3-pole 077F8727 Door-sensor, 3000 mm (C4), 3-pole 080G3336 TPE precision (C1), 2500 mm, 3-pole 077F8728 TPE precision (C1), 3000 mm, 3-pole 077F8729 Temperature sensors PVC Standard (C1), 470 mm, 3-pole 077F8751 Clamps PVC Standard (C1), 1000 mm, 3-pole 077F8757 Black (2 needed per controller) PVC Standard (C1), 1500 mm, 3-pole 077F8761 PVC Standard (C1), 2000 mm, 3-pole 077F8765 PVC Standard (C1), 2200 mm, 3-pole 077F8767 PVC Standard (C1), 3000 mm, 3-pole 077F8769 Note: For more information about temperature sensor types and connectors, please refer to Danfoss’ technical brochure “NTC type temperature sensors for ETC & ERC controllers” 080G3308 Programming OEM Docking station, production line 080G9701 Gateway incl USB Cable, R&D 080G9711 Copy Stick EKA-183A 080G9740 C: connector type * Defrost sensors can also be used as condenser sensors. . ERC 102 Reference manual – APPENDIX II: CODE NUMBERS AND LENGHTS 51 APPENDIX III: TROUBLESHOOTING Problem Probable cause Remedy Compressor does not start Waiting for compressor delay timer Check CoP->CSt Defrost in progress Check CoP ->Pot /Pod Line voltage to compressor too low or too high Check dEF ->dit, dot Check CoP->uLi, uLo, uHi Fan does not start Door is open or door contact is defective Fan stops when door is opened Check that door contact is ok Defrost does not start Controller in pull-down mode Defrost might be delayed during pull-down Check parameter Pud->Pdi Alarm does not sound Alarm delayed Check ALA->Htd, Abd Check Pud->Pdd Display brightness is weak Ambient light sensor broken Replace sensor Shift between Eco and Normal mode does not happen on ambient light change Ambient light sensor broken or light level not set properly Check Eng->SLd, SLn E01, E02 or E03 is shown on display E01: Sensor S1 defective Replace sensor E02: Sensor S2 defective E03: Sensor S3 defective Display alternates between Con and temperature Condenser too hot Clean condenser Check Con ->CAL, CbL Display alternates between Hi and temperature Temperature too high Check ALA->HAt Display alternates between Lo and temperature Temperature too low Check ALA -> LAt Display shows dEf Defrost in progress Check diS ->SdF 52 ERC 102 Reference manual – APPENDIX III: TROUBLE SHOOTING APPENDIX IV: TYPICAL APPLICATIONS – WIRING DIAGRAMS IV.1 ERC 102D Glass Door Merchandiser No-frost freezer / sub-zero cooler 100 – 240VAC SMPS L N 1 DO1 2 3 Lights Fan Compressor Defrost Heater ERC 102C 3 relays 4 DO2 5 6 DO3 AI/DI’s Red LED without buzzer 080G3101 Blue LED without buzzer 080G3106 ERC102D Controller DO’s DO4 D(S1) C(S2) B(S3) A(di) LL Temperature Sensor for Cabinet Temperature Control Temperature Sensor for Evaporator Temperature Control Ambient Light Door input PVC Standard Connector type (C1) 3-pole PVC Standard Connector type (C2) 2-pole Light sensor Connector type (C3) 3-pole Door-sensor cable Connector type (C4) 3-pole 470 mm 1000 mm 1500 mm 2000 mm 2200 mm 3000 mm 077F8751 077F8757 077F8761 077F8765 077F8767 077F8769 470 mm 1000 mm 1500 mm 2000 mm 3000 mm 077F8780 077F8786 077F8790 077F8794 077F8798 1000 mm 2000 mm 3000 mm 080G3311 080G3313 080G3315 1000 mm 2000 mm 3000 mm 080G3332 080G3334 080G3336 ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS 53 IV.2 ERC 102C Glass Door Merchandiser 100 – 240VAC SMPS N ERC 102C Controller Compressor Fan Lights L 1 DO1 2 3 4 DO2 AI/DI’s 5 Red LED without buzzer 080G3102 Blue LED without buzzer 080G3106 ERC102C Controller DO’s DO3 D(S1) C(S2) B(S3) A(di) LL Temperature Sensor for Cabinet Temperature Control Temperature Sensor for Evaporator Temperature Control Ambient Light Door input PVC Standard Connector type (C1) 3-pole PVC Standard Connector type (C2) 2-pole Light sensor Connector type (C3) 3-pole Door-sensor cable Connector type (C4) 3-pole 470 mm 1000 mm 1500 mm 2000 mm 2200 mm 3000 mm 54 077F8751 077F8757 077F8761 077F8765 077F8767 077F8769 470 mm 1000 mm 1500 mm 2000 mm 3000 mm 077F8780 077F8786 077F8790 077F8794 077F8798 1000 mm 2000 mm 3000 mm ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS 080G3311 080G3313 080G3315 1000 mm 2000 mm 3000 mm 080G3332 080G3334 080G3336 IV.3 ERC 102D Gastro No-frost freezer ERC 102D Controller 100 – 240VAC SMPS DO1 2 3 Fan Compressor 1 4 DO2 5 080G3103 Blue LED without buzzer 080G3107 6 DO3 AI/DI’s Red LED without buzzer Lights N Defrost Heater L DO’s ERC102D Controller DO4 D(S1) C(S2) B(S3) A(di) Temperature Sensor for Cabinet Temperature Control Temperature Sensor for Evaporator Temperature Control Temperature Sensor for Condenser Temperature Control Door input PVC Standard Connector type (C1) 3-pole PVC Standard Connector type (C2) 2-pole PVC Standard Connector type (C3) 3-pole Door-sensor cable Connector type (C4) 3-pole 470 mm 1000 mm 1500 mm 2000 mm 2200 mm 3000 mm 077F8751 077F8757 077F8761 077F8765 077F8767 077F8769 470 mm 1000 mm 1500 mm 2000 mm 3000 mm 077F8780 077F8786 077F8790 077F8794 077F8798 470 mm 1000 mm 1500 mm 2000 mm 2200 mm 3000 mm 077F8750 077F8756 077F8760 077F8764 077F8766 077F8768 1000 mm 2000 mm 3000 mm 080G3332 080G3334 080G3336 ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS 55 IV.4 ERC 102C Gastro Cooler 100 – 240VAC SMPS Fan Compressor 1 DO1 2 ERC 102C Controller N 3 Red LED without buzzer 080G3102 Blue LED without buzzer 080G3106 Lights L 4 DO2 AI/DI’s 5 ERC102C Controller DO’s DO3 D(S1) C(S2) B(S3) A(di) Temperature Sensor for Cabinet Temperature Control Temperature Sensor for Evaporator Temperature Control Temperature Sensor for Condenser Temperature Control Door input PVC Standard Connector type (C1) 3-pole PVC Standard Connector type (C2) 2-pole PVC Standard Connector type (C3) 3-pole Door-sensor cable Connector type (C4) 3-pole 470 mm 1000 mm 1500 mm 2000 mm 2200 mm 3000 mm 077F8751 077F8757 077F8761 077F8765 077F8767 077F8769 470 mm 1000 mm 1500 mm 2000 mm 3000 mm 077F8780 077F8786 077F8790 077F8794 077F8798 470 mm 1000 mm 1500 mm 2000 mm 2200 mm 3000 mm 077F8750 077F8756 077F8760 077F8764 077F8766 077F8768 1000 mm 2000 mm 3000 mm 080G3332 080G3334 080G3336 Note: This is a typical (default) wiring diagram since both inputs(AI/DI’s) and outputs (DO’s) can be assigned differently. Please see manual for further details, folder “ASi”, Assignment. 56 ERC 102 Reference manual – 8 TYPICAL APPLICATIONS – WIRING DIAGRAMS APPENDIX V: APPLICATION SPECIFICATON V.1 Control sensor The control sensor must always be connected and is used for controlling the cut-in and cut-out of the compressor according to the set-point. The sensor is also used for the displayed temperature. Placement of sensor: Vertical coolers with fan Most common placement is in the return air to the evaporator. The sensor can be placed close to the fan – even when the fan is pulsed during compressor off periods: The updating of the temperature is blocked when the fan is stopped and only updated when the fan has been running for a while, so that the heat from the fan does not affect the temperature reading. For applications sensitive to sub-zero temperatures, sensor placement in the evaporator outlet air can be considered. Vertical freezers with fan Placement in the return air or in the freezer compartment Coolers without fan the best results are normally obtained when the sensor is placed at the side-wall, 10 cm from the back and approximately at 1/3 from the bottom or where the evaporator ends. The control sensor must always be connected and is used for controlling the cut-in and cut-out of the compressor according to the set-point. The sensor is also used for the displayed temperature. ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION 57 V.2 Evaporator sensor The evaporator sensor is only used for de-icing of the evaporator and has no control purpose. Placement of sensor: Place the sensor where the ice melts last. Please be aware of that sharp finns can damage the cable. V.3 Condenser sensor The condenser sensor is used to protect the compressor against high pressure when the condenser is blocked or the condenser fan fails. Placement of sensor: Place the sensor at the liquid side of the condenser. Use a metal bracket or metal tape to ensure good thermal conductivity. Be sure that the cable does not pass hot spots at the compressor or condenser that exceeds 80°C. 58 ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION V.4 Ambient light sensor The ambient light sensor is used to detect opening hours of the shop. Placement of sensor: The sensor must be placed so that the interior light does not affect the sensor. Possible placement could be in the front of the cooler or at the top. V.5 Door sensor The door sensor is used to detect buying activity and to stop the fan when the door is opened. Danfoss does not supply the door-switch. Use the door-switch you have and connect it to the cable supplied by Danfoss. ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION 59 ERC102 Application Matrix Application ERC type Output DO1 DO2 DO3 Input DO4 S1 (C1) S2 (C2) S3 (C3) Di (C4) Control Defrost Condenser or Ambient Light Door Standard Beverage cooler ERC102C Comp Fan Lamp Sub-zero beverage cooler ERC102D Comp Heater Fan Lamp Control Defrost Condenser or Ambient Light Door Out-door beverage cooler ERC102D Comp Heater Fan Lamp Control Condenser Ambient Light Door Nofrost freezer w. glassdoor ERC102D Comp Heater Fan Lamp Control Evaporator Condenser or Ambient Light Door CFF Refrigerator ERC102C Comp Fan Lamp Control Defrost Condenser Door CFF Freezer ERC102D Comp Heater Fan Control Defrost Condenser Door Lamp C: connector type NOTE: • Select only one function per input, e.g. condenser sensor or ambient light sensor. • Make sure that the accessory you select has a matching connector to the input, e.g. a sensor for input S2 must have C2 connector. • Condenser sensor or light sensor are optional and can be omitted. • Defrost sensor is mandatory when electrical heater is used for defrost. For natural defrost it can be omitted. DKRCC.ES.RL0.A9.02 / 520H8849 Copyright Danfoss A/S www.danfoss.com – 08/2014
Danfoss серия ERC — холодильные контроллеры Danfoss | Управление Холодом
- Холодильное оборудование
- Контроллеры
4 491,26 P / шт
с НДС актуально на 14.07.23
цена не является публичной офертой.
Артикул | 080G3181 |
id товара | 15602 |
Страна | Китай |
Минимальный заказ | 1 шт |
В наличии на складах | 9 шт |
Выберите город доставки: Москва
Выберите способ доставки:
Деловые линии
Самовывоз
Склад | В наличии на складе | Цена за ед. без доставки | Цена доставки | Срок доставки, дней | Сколько нужно, шт | Стоимость с доставкой | ||
---|---|---|---|---|---|---|---|---|
Москва10 | 1 шт | 4491,26P |
Общее описание
Контроллер ERC 102 оснащен 3 аналоговыми и 1 цифровым входами и 3 выходами. Он особенно подходит для ОЕМ клиентов, так как время, простая и надежная установка и высокое качество важны наряду с гибкостью. Дисплей может быть красным или синим. Контроллер доступен с верхней левой кнопкой «ECO» или «Оттайка». Нижняя левая кнопка может быть «Свет», «Отключение» или «Ускоренное охлаждение». Большой диапазон совместимых типов датчиков и клеммы винтового соединения обеспечивают высокую гибкость при установке. Модульная система разъёмов для ОЕМ-клиентов с опциональным адаптером с винтовыми клеммами. Тип входного разъёма- Rast 2.5 Edge. Тип выходного разъёма- Rast 5 Standard.
Читать далее…
Видео
Технические
характеристикиЧертежи
и схемыДополнительная
информацияКомплектующие
Характеристика
Производитель | Danfoss |
Марка | Adap-Kool |
Назначение | Для торговой мебели и камер |
Количество релейных выходов | 3 |
Напряжение питания | 90 — 240 V |
Описание | Красный дисплей, 100..240 В, без звук. сигнализации |
Чертежи
Дополнительная информация
Описание, технические характеристики, руководство пользователя контроллеров Danfoss серии ERC 112 (4.28Mb)
Рекламный проспект по контроллерам Danfoss серии ERC 112 (0.30Mb)
Общий каталог Danfoss (16.06Mb)
Полезные ссылки
Сайт производителя Danfoss
Вам также может понадобиться
Датчик температуры AKS 12
- Артикул: 084N0036
- Страна: Дания
- В наличии: много
Датчик температуры воздуха со средним диапазоном рабочих температур и средним временем задержки.Датчик основан на платиновом чувствительном элементе с сопротивлением 1000 Ом при 0 °C.Температурный диапазон: -40 — +80 °C.Класс защиты: IP 67подключения: ПВХ кабель, 2 х 0,22 мм2.датчики настроены и соответствуют требованиям DIN IEC 751, класс B.
Датчик температуры EKS 111 (-55…80C) 1,5m
- Артикул: 084N1161
- Страна: Италия
- В наличии: 1 шт
Датчик основан на PTC-элементе с сопротивлением 1000 Ом при 25 °C Датчик может быть использован для измерения температуры в следующих областях: охлаждение, кондиционер, отопление. В первую очередь в сочетании с типами контроллеров ЕКС 101, ЕКС 201 и ЕКС 301. Датчик имеет относительно большой допуск на сопротивление. Это означает, что датчик не может быть используются для измерения значения, используемые для производства продуктов питания журнала безопасности или регулирование перегрева.
Датчик температуры EKS 211 (-40…80C) 1,5m
- Артикул: 084B4403
- Страна: Индонезия
- В наличии: много
Датчик может быть использован для измерения температуры в следующих областях: охлаждение, кондиционер, отопление.
Датчик температуры AKS 11 Pt1000
- Артикул: 084N0005
- Страна: Дания
- В наличии: нет
Датчики накладные и погружные.Датчиков настроены и соответствуют требованиям DIN IEC 751, класс В.Температурный диапазон: -50 — +100 °C.Степень защиты: IP 67.Подключения: ПВХ кабель, 2 х 0,2 мм2
Вам также может понадобиться
-
16.07.2014, 19:22
#1
Новичок
Danfoss ERC 102C
Кто сталкивался с DANFOSS ERC 102C,как он в работе и программирование не совсем понятно,как-то мудрено по сравнению с Eliwel или EVK
-
16.07.2014, 19:24
#2
сервисник
Если масла нету в репе, то и в тумбочке не будет… )
-
16.07.2014, 19:48
#3
Эксплуататор 2х ZR620
Сообщение от slawenti3
Кто сталкивался с DANFOSS ERC 102C,как он в работе и программирование не совсем понятно,как-то мудрено по сравнению с Eliwel или EVK
Норм все)
-
16.07.2014, 22:54
#4
Мастер
Чем мудренее, тем меньше рукосуев! Нормальный блок, не хуже не лучше.
-
16.07.2014, 23:06
#5
сервисник
Если масла нету в репе, то и в тумбочке не будет… )
-
18.07.2014, 11:09
#6
Мастер
Сообщение от slawenti3
как-то мудрено
К аббревиатурам привык?
-
20.07.2014, 20:30
#7
Новичок
-
11.08.2014, 17:46
#8
Новичок
Так все же какой код для входа в параметры компресора?
-
29.04.2015, 10:44
#9
Заблокирован
Последний раз редактировалось YetiOdessa; 29.04.2015 в 11:02.
-
29.04.2015, 11:12
#10
Мастер
Стр. 25 инструкции
Некоторые параметры могут быть скрыты для Вас.
Доступные параметры предварительно определены с помощью программы KoolProg. Ваш уровень доступа будет определять, какие параметры вы можете просматривать и редактировать.Скорее всего, конфигурация кнопок убрана на 3-й уровень (ОЕМ) и без пароля 3-го уровня или софта её не выставишь.
-
22.07.2015, 15:44
#11
Пользователь
[QUOTE=slawenti3;324836]Кто сталкивался с DANFOSS ERC 102C,как он в работе и программирование не совсем понятно,как-то мудрено по сравнению с Eliwel или EVK[/QUOT
ничего мудрёного в них нет ничем не отличается от EKC только корпусом а так всё тоже самое в инструкции всё описано как и что
-
23.05.2020, 07:03
#12
Мастер
У кого есть инструкция на ЕКС 102С, не могу найти в сетях. Если есть скиньте, нужно срочно. 80286392-e0df-4ed9-b942-6df69e86df38.jpg
-
23.05.2020, 08:25
#13
Мастер
Сообщение от Сергей Р
У кого есть инструкция на ЕКС 102С,
Есть ERC 102Х-универсальная, но почему то не закружается
Последний раз редактировалось mihail97; 23.05.2020 в 08:38.
-
23.05.2020, 08:40
#14
Мастер
-
23.05.2020, 09:06
#15
Мастер
-
23.05.2020, 09:09
#16
Мастер
Ещё…., но третью страницу не грузит
-
23.05.2020, 11:40
#17
Мастер
Похожие темы
-
Ответов: 2
Последнее сообщение: 17.03.2019, 15:55
-
Ответов: 3
Последнее сообщение: 13.01.2018, 21:54
-
Ответов: 11
Последнее сообщение: 19.04.2014, 18:20
-
Ответов: 32
Последнее сообщение: 10.11.2011, 23:42
Социальные закладки
Социальные закладки
-
Google
Ваши права
- Вы не можете создавать новые темы
- Вы не можете отвечать в темах
- Вы не можете прикреплять вложения
- Вы не можете редактировать свои сообщения
- BB коды Вкл.
- Смайлы Вкл.
- [IMG] код Вкл.
- [VIDEO] код Вкл.
- HTML код Выкл.
Правила форума