Контроллер erc 102c инструкция данфосс

Danfoss ERC 102C 102 User Guide | Manualzz

MAKING MODERN LIVING POSSIBLE
ERC 102 refrigeration controller
Reference manual
This reference manual is intended to be used primarily by OEMs for the purposes of programming ERC 102.
It may also be useful for technicians. It is not intended as a user guide for end users.
www.danfoss.com/erc
Table of Content
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. CONTENT OF THE BOX
2.1 Main product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3. OVERVIEW OF THE PRODUCT
3.1 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Connector inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Connector outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Top label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4. MOUNTING
4.1 Rear mounting – Option 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Front mounting – Option 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Fully-integrated design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
11
12
13
13
5. CONTROLLING/NAVIGATION
5.1 KoolProg and Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Docking station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Manual operation with buttons (Direct Access) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.1 ERC Front and Button Functionallity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.2 Direct functions for access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3 Operating the menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.4 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.5 Password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
14
14
14
15
16
18
18
6. CONFIGURATION OF INPUTS AND OUTPUTS
6.1 Changing input and output configuration settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Program the buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Set passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 Set lighting function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
22
23
23
2
ERC 102 Reference manual
7. PARAMETERS
7.1 Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4 Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.6 Energy management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.7 Pull down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.8 Automatic heater control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.9 Condenser protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.10 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.11 Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.12 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
26
28
31
35
35
37
38
39
40
42
43
8. TECHNICAL SPECS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
APPENDIX
I
Parameter quick list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II
Code numbers and lenghts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . III
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV
Typical applications – wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV.1 Typical Wiring Diagram, ERC 102D, Glass Door Merchandiser,
No-frost freezer / sub-zero cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IV.2 Typical Wiring Diagram, ERC 102C, Glass Door Merchandiser . . . . . . . . . . . . . . . . . . . . . IV.3 Typical Wiring Diagram, ERC 102D, Gastro No-frost freezer . . . . . . . . . . . . . . . . . . . . . . IV.4 Typical Wiring Diagram, ERC 102C, Gastro Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V
Application specificatons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V.1 Control sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V.2 Evaporator sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V.3 Condenser sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V.4 Ambient light sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V.5 Door sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ERC102 Application Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ERC 102 Reference manual
45
51
52
53
53
54
55
56
57
57
58
58
59
59
60
3
1. INTRODUCTION
The ERC 102 is an electronic refrigeration controller with an LED display especially developed for bottle
coolers and commercial fridges and freezers. It is particularly suited for OEM customers where time, easy and
reliable installation and high quality need to go hand in hand with flexibility.
The latest generation CPU, plenty of memory and high-end electronic components allow for a uniquely
versatile software. Three separate password-protected user levels can be used to control more than 200
different parameters to fit all individual requirements.
ERC 102’s IP rated body, advanced materials and internationally approved hardware design open it up for use
in almost any climate globally, indoors as well as outdoors.
Laboratory work with ERC 102 is rendered easy and flexible. Danfoss KoolProg software with a USB-powered
gateway accelerate programming; on the OEM assembly line, just one Danfoss unique Docking station can
easily program up to 3,000 controllers a day – at zero inventory cost.
It uses a globally-compatible, lightweight, switch mode power supply.
All components have been carefully selected to help reduce the CO2 footprint. The globally-compatible
internal power supply uses an average of just 0.7W – 4 times less than an average controller today.
Sensors include ambient light for display brightness, which also detect shop opening hours for
energy-saving routines. Door and temperature sensors provide input for controlling the compressor,
the light, the fan and automatic defrosting.
4
ERC 102 Reference manual
2. CONTENT OF THE BOX
If delivered in a sample box the following content
is shipped. The sample box is not available for other
than sample purposes.
See Appendix II for code numbers and lengths.
For box lots (pcs per box), please contact your local
Danfoss representative.
2. 1 Main product
ERC 102 control unit without front frame.
NOTE: The front frame is included in the sample box.
2.2 Accessories
Control temperature sensor: see Appendix II for
different lengths and connector types.
Defrost temperature sensor: should be mounted on
the evaporator. For detailed mounting instructions,
please contact your local Danfoss representative.
NOTE: Defrost sensors can also be used as condenser
sensors.
Condenser temperature sensor: should be
mounted on the condenser. For detailed
mounting instructions, please contact your
local Danfoss representative.
NOTE: This sensor is not included in the sample box .
Defrost sensors can also be used as condenser
sensors.
ERC 102 Reference manual – 2 CONTENT OF THE BOX
5
Door sensor connector cable: please see Appendix II
for lengths and code numbers.
NOTE: Door sensor: is optional and is a connector
and cable with spade terminals compatible with door
contacts used in refrigeration applications.
Light sensor: is optional and is used to measure the
level of ambient light around the cabinet so
that night and day (Economy / Normal) modes
of operation can automatically be set, as well
as the brightness of the display.
Power plug: for laboratory use, low quantity
OEM production or whenever spade connectors are
not available.
Clips: are used to secure the ERC 102 in place in
the case of rear mounting. They are not used with
front mounting. There are two identical clips, one
placed on either side of the ERC 102. See Chapter 4
– Mounting – for further details.
6
ERC 102 Reference manual – 2 CONTENT OF THE BOX
2.3 Connections
Programming an individual unit in a laboratory:
the USB gateway requires KoolProg Software
running on a PC. It enables parameters to be set in
real time and an array of status information to be
read (bidirectional connection). This method is used
to determine the correct parameters during R&D.
Once the desired settings have been determined,
a KoolProg ERC specific parameter file is saved to the
EKA183 USB copy key for later mass programming.
The USB Gateway is a laboratory tool, offering fast
and easy programming of any ERC102 controller.
KoolProg software installation is provided;
the gateway is standard inventory for OEM labs.
Mass programming on an assembly line:
the docking station is used for high volume
programming of ERC controllers, for example
on an assembly line. The docking station is a
write-only device.
See above (Programming an individual unit) for
preparing the EKA183 USB copy key, which is to
be inserted into the docking station. The settings
are then loaded into each successive controller
in a matter of seconds.
KoolProg software is not required for mass
programming.
Note: please refer to the koolprog manual for more
details about programming.
KoolProg: is the software from Danfoss for
programming the ERC 102 via a USB cable and
a PC rather than with the front panel buttons.
Please refer to the KoolProg manual for details.
ERC 102 Reference manual – 2 CONTENT OF THE BOX
7
3. OVERVIEW OF THE PRODUCT
The ERC 102 is a state-of-the art, IP65 (front)-rated
refrigeration controller for use in both Glass Door
Merchandising and Commercial Fridges and Freezer
applications.
With four inputs and four outputs, powerful
algorithms and input from multiple sensors, the ERC
102 delivers both energy-saving routines and
compressor, light, fan and defrost control.
Together with the Danfoss docking station,
programming of pre-prepared parameter sets can
be achieved in just five seconds. There are over 200
parameters (see Chapter 7) including innovative
features such as night mode detection,
store opening detection, door open alarm control
and display dimming for restaurants.
The ERC 102 can also be programmed via USB using
the Danfoss KoolProg software, allowing the most
suitable parameter findings to be found quickly
during the application development process.
It is also possible to operate and program the
controller using the control buttons (only when
actually installed in a refrigerator / freezer).
Overview of ERC 102 models:
Model:
Digital outputs:
ERC 102A
1 relay
ERC 102C
3 relays
ERC 102D
4 relays
3.1 Control buttons
The ERC 102 has four buttons (circled in image)
on the front which can be programmed to perform
different functions. See Chapter 6 – Configuration of
inputs and outputs for detailed information.
3.2 Connector inputs
Connect up to four Danfoss original sensors according
to your application needs.
There are three analogue inputs: S1, S2 and
S3 ( a ).
The ambient light sensor can be used for determining shop open / closed times for economy mode
switching, for determining the brightness of the LED
display or both.
Supported input options:
· Ambient light - analogue data [luminens]
· Cabinet (air) temperature - analogue data [°C]
· Evaporator temperature - analogue data [°C]
· Condenser temperature - analogue data [°C]
· Digital input - binary data [on/off ]
There is one digital input: diC ( b ) for PC
communication being used either with a door
sensor or with the USB Gateway.
NOTE: for detailed information refer to section 6.1.
8
ERC 102 Reference manual – 3 OVERVIEW OF THE PRODUCT
S1
S2
a
S3
b
3.3 Connector outputs
All four outputs ( c ) are digitally controlled
on/off relays.
Functions controlled are:
• Compressor
• Pilot Relay
• Heater
• Defrost heater / valve for hot gas
• Alarm
• Fan
• Light
C
3.4 Top label
The illustration shows an example of a top label
affixed to an ERC 102D. The examples show what
is connected:
• Output 1 is used to switch the compressor
on and off.
• Outputs 2 and 3 are power – Live and Neutral.
• Output 4 is used to switch the heater on and off.
• Output 5 is used to switch the fan on and off.
• Output 6 is used to switch the light on and off.
• Input D (S1) is connected to a Cabinet Sensor to
measure temperature inside the cabinet.
• Input C(di) is used for Communications – a docking
station or KoolProg software running on a PC.
• Input B(S2) is connected to an Evaporator
Temperature Sensor.
• Input A(S3) is connected to an Ambient Light Sensor.
NOTE: Parameters depend on the code number supplied. Please refer to the code number
specific technical drawing or use the KoolProg information menu. For other applications,
a condenser sensor and a door sensor may
be used.
ERC 102 Reference manual – 3 OVERVIEW OF THE PRODUCT
9
4. MOUNTING
There are three options for mounting the ERC 102
in a freezer or refrigerator.
SAFETY INFO
Risk of electrocution!
For mounting: Do not connect mains power until
the controller is correctly mounted.
For unmounting: Disconnect the power supply
before unmounting.
4.1 Rear mounting – Option 1
1. Insert the ERC 102 into the cabinet.
2. Attach the clips to each side of the ERC 102.
3.Place the front frame on to the ERC 102 and click
it into place.
4.Connect the sensors and outputs as required and
then the power cable (see Chapter 6 – parameters
for information about programming which inputs
and outputs are applicable to your configuration).
10
ERC 102 Reference manual – 4 MOUNTING
4.1.1 Unmounting
1. Disconnect the power cable and then the sensors.
2.Use a flat head screwdriver (ideally the one
supplied with the ERC 102 sample package)
and insert it carefully between the front frame
and the controller.
3.Gently twist the screwdriver to remove the
front frame. Do this in four places next to each
clip area.
5.Reach around the side to the clips.
ERC 102 Reference manual – 4 MOUNTING
11
6.Press the centre section of each clip to release
them in turn. Push the controller carefully out
of the cabinet.
4.2 Front mounting – Option 2
1.Connect all the cables as required (see Chapter 6
– parameters for information about programming
which inputs and outputs are applicable to your
configuration).
2.Insert the ERC 102 into place in the cabinet.
3.Press the front frame into place – this locks the
ERC 102 into position.
NOTE: there is no need to use the clips for
front mounting.
12
ERC 102 Reference manual – 4 MOUNTING
4.2.1 Unmounting
1.Use a flat head screwdriver (ideally the
one supplied with the ERC 102 sample package)
and insert it carefully between the front frame
and the controller.
2.Gently twist the screwdriver to remove the
front frame. Do this in four places next to each
clip area.
3.Cabinet. Do not use a different type of
screwdriver or a sharp item such as a knife
which risks causing damage.
4.3 Fully integrated design – Option 3
An option is available for OEMs wanting to use the ERC
102 in a fully-integrated design. Please contact your
local Danfoss representative for more information.
ERC 102 Reference manual – 4 MOUNTING
13
5. CONTROLLING / NAVIGATION AND ACCESS LEVELS
The ERC 102 can be controlled in three ways:
using KoolProg software, the Danfoss Docking
Station or manually by means of the buttons
on the front panel.
5.1 KoolProg/Gateway
KoolProg is licenced Danfoss software offering easy
parameter setup via a USB gateway. This software
is supplied separately; for technical literature and
further information, please contact your local
Danfoss representative.
5.2 Docking station
The ERC 102 controller docking station is supplied
separately. For further information, please contact
your local Danfoss representative.
5.3 Manual operation with buttons
(Direct Access)
Danfoss ERC 102
Explained as follows:
ERC Front and Button Functionallity:
5.3.1 ERC Front
and Button Functionallity
1 Press: Variable direct function, e.g.ECO/Night mode
function:
Up setpoint
1Sub
Click:
Temperature
Sub function: Up
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
Sub
function:
Down setpoint
1 Press:
Temperature
3 sec:
Menu direct function, e.g. light
1Hold
Press:
Variable
Sub function: OK
Sub function: OK
14
1 Press: Temperature setpoint
1Sub
Click:
VariableBack
direct function, e.g.ECO/Night mode
function:
Sub function: Back
Sub function: Down
ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
C 102
5.3.2 Direct functions for access
on Functionallity:
C 102Changing the Desired Temperature Setpoint (applies similarly when using Fahrenheit scale):
g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Up
on Functionallity:
1.)
C 102
The display shows the current
temperature.
1 Click: Temperature setpoint
g.ECO/Night mode
Sub function: Up
(Current temperature)
on Functionallity:
2.)
g. light
1 Click: Temperature setpoint
C 102
Sub
function:toDown
Press:
up/down
adjust setpoint
g.ECO/Night mode
on Functionallity:
1 Click: Temperature setpoint
Sub function: Up
(Flashing: temperature setpoint)
3.)
After 30 seconds, the display automatically
reverts to showing the current temperature
g. light
1 Click: Temperature setpoint
Sub function: Down
g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Up
(Flashing: temperature setpoint)
4.)
g. light
1 Click: Temperature setpoint
Sub function: Down
ss ERC 102
g. light
1 Click: Temperature setpoint
Sub function: Down
and Button Functionallity:
ss ERC
102
Turning
On/Off the ECO Function:
irect function, e.g.ECO/Night mode
k
1 Click: Temperature setpoint
Sub function: Up
and Button Functionallity:
1.)
Press briefly
to enter
rect function, e.g.ECO/Night mode
ECO mode
1 Click: Temperature setpoint
Sub function: Up
k
rect function, e.g. light
rect function, e.g. light
2.)
ECO
˚C
1 Click: Temperature setpoint
Sub function: Down
The green ECO symbol
is lit when in ECO mode
1 Click: Temperature setpoint
Sub function: Down
ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
15
oss ERC 102
t and Button Functionallity:
direct function, e.g.ECO/Night mode
ck
1 Click: Temperature setpoint
Sub function: Up
Turn ON/Off the Light
1.)
Press the
Light button
briefly
oss ERC 102
Danfoss ERC 102
To turn off the Light
Press the light button again
t and Button Functionallity:
ERC Front and Button Functionallity:
direct function, e.g. light
u
K
oss ERC
102 Alarms:
Acknowledging
direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g.ECO/Night mode
ck
Sub function: Back
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub function: Up
t and Button Functionallity:
1.)
direct function, e.g.ECO/Night mode
ck
1 Click: Temperature setpoint
Sub function: Up
Flashing
Press any button to acknowlege
2.)
direct function, e.g. light
u
K
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
Sub function: OK
direct function, e.g. light
u
K
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function: Down
5.3.3 Operating the menu
Button assignments in this manual refer
to the Glass Door Merchandiser default ERC 102.
For customised controls you may assign different
shortcuts (ASI menu --> button configuration).
Use this feature only when the ERC 102 is supplied
without button prints.
INFO: Some parameters may be hidden to you.
When scrolling through menus, the parameters
available will have been pre-determined using
KoolProg software. Your access level will determine
which parameters you can view and edit.
16
ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
Danfoss ERC 102
ERC Front and Button Functionallity:
Danfoss
ERC 102
Example of Changing a Parameter:
1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
1 Click: Temperature setpoint
Sub function: Up
ERC Front and Button Functionallity:
1.)
Danfoss ERC 102
1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
Press and hold for 5 seconds to enter the menu
1 Click: Temperature setpoint
Sub function: Up
ERC Front and Button Functionallity:
2.)
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
Sub function: OK
1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
Danfoss ERC 102
ERC Front and Button Functionallity:
3.)
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
function:
OKdirect function, e.g.ECO/Night mode
1Sub
Click:
Variable
Danfoss ERC 102
To select:
press
the lower left button (OK)
Sub
function:
Back
1 Click: Temperature setpoint
Sub
function:toDown
Press:
up/down
scroll
through the menu
1 Click: Temperature setpoint
Sub function: Up
(scroll through parameter groups)
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function: Up
ERC Front and Button Functionallity:
4.)
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
function:
OKdirect function, e.g.ECO/Night mode
1Sub
Click:
Variable
Sub function: Back
Danfoss ERC 102
ERC Front and Button Functionallity:
1 Click:
Temperature
Press:
up/down
to find setpoint
Sub function:
Down
the desired
parameter
1 Click: Temperature setpoint
Sub function: Up
(scroll through group “dEf” parameters)
5.)
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
Sub function: OK
1 Click: Variable direct function, e.g.ECO/Night mode
To
confirm: press the lower left button (OK)
Sub function: Back
Danfoss ERC 102
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function: Up
ERC Front and Button Functionallity:
6.)
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
1Sub
Click:
Variable
function:
OKdirect function, e.g.ECO/Night mode
Sub function: Back
Danfoss ERC 102
1 Click: Temperature setpoint
Press:
up/down
enter
Sub
function:toDown
the desired
value
1 Click: Temperature
setpoint
Sub function: Up
ERC Front and Button Functionallity:
7.)
Danfoss ERC 102
1 Click: Variable direct function, e.g. light
Hold 3 sec:Press:
MenuOK to accept
1Sub
Click:
Variable
direct function, e.g.ECO/Night mode
function:
andOK
return to parameter name
Sub function:
Back
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function: Up
ERC Front and Button Functionallity:
8.)
1 Click: Variable
e.g. light
Press:direct
upperfunction,
left button
(back)
3 sec:
toMenu
return
to function,
parameter
group
1Hold
Click:
Variable
direct
e.g.ECO/Night
mode
Sub
function:
OK
Sub function: Back
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function: Up
9.)
Press:direct
upperfunction,
left button
(back)
1 Click: Variable
e.g. light
return to the menu
Hold 3 sec:toMenu
Sub function: OK
1 Click: Temperature setpoint
Sub function: Down
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
Sub function: OK
1 Click: Temperature setpoint
Sub function: Down
ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
17
102 Danfoss ERC 102
Danfoss ERC 102
Functionallity: ERC Front and Button Functionallity:
O/Night mode
ERC Front and ERC
Button Functionallity:
Danfoss
102
1 Click: Temperature setpoint
Sub function: Up
ERC Front and ERC
Button Functionallity:
Danfoss
102
1 Click: Temperature setpoint
Sub function: Up
1 Click: Variable direct function, e.g.ECO/Night mode1 Click: Temperature setpoint
Sub function: Back
5.3.4
Menu structure
Sub function: Up
1 Click: Variable direct function, e.g.ECO/Night mode
Press and hold 5 1. ) Parameter groups
Sub function: Back
sec to access the
menu
ERC Front and ERC
Button Functionallity:
Danfoss
102Danfoss ERC 102
1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
1 Click: Temperature setpoint
Sub function: Up
Lower left button
ERC Front and ERC
Button Functionallity:
ERC Front and ERC
Button Functionallity:
Danfoss
102Danfoss
102Danfoss ERC 102
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Back
function:
Up
1 Click: Variable direct function, e.g. light
1Sub
Click:
Temperature
setpoint
1 Click: Temperature setpoint
Hold 3 sec: Menu
Sub function: Down
Sub function: Down
Sub function: OK
1 ERC
Click: Variable
function,
e.g.ECO/Night
mode1 Click: Variable direct function, e.g.ECO/Night mode ERC Front and Button Functionallity:
Frontdirect
and
Button
Functionallity:
ERC Front and Button Functionallity:1 Click: Temperature setpoint
1 Click: Temperature setpoint
Sub function: Back
Sub function: Back
Sub function: Up
Sub function: Up
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
Hold 3 sec: Menu
Sub function: Down
Sub function: OK
1 ERC
Click: Variable
function,
e.g.ECO/Night
mode1 Click: Variable direct function, e.g.ECO/Night mode 1 Click: Variable direct function, e.g.ECO/Night mode
Frontdirect
and
Button
Functionallity:
1 Click:
Temperature setpoint
ERC
Front
and
Button
Functionallity:
1 Click: Temperature setpoint
Sub
function:
Back
2.) Parameter
names
Sub function: Back
Sub function: Back
Sub function: Up
Sub function: Up
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
Hold 3 sec: Menu
Sub function: Down
Lower left button
Sub function: OK
1 ERC
Click: Variable
function,
e.g.ECO/Night
mode1 Click: Variable direct function, e.g.ECO/Night mode
Frontdirect
and
Button
Functionallity:
ERC Front and Button Functionallity:1 Click: Temperature setpoint
1 3.)
Click:
Temperature
setpoint
Parameter
value
Sub function: Back
Sub function: Back
Sub function: Up
Sub function: Up
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
Hold 3 sec: Menu
Sub function: Down
Sub function: OK
1 ERC
Click: Variable
function,
e.g.ECO/Night
mode1 Click: Variable direct function, e.g.ECO/Night mode
Frontdirect
and
Button
Functionallity:
1 Click: Temperature setpoint
ERC
Front
and
Button
Functionallity:
1 Click: Temperature setpoint
Sub function: Back
Sub function: Back
Sub function: Up
Sub function: Up
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
Hold 3 sec: Menu
Hold 3 sec: Menu
Sub function: Down
Sub function: Down
Sub function: OK
Sub function: OK
1 ERC
Click: Variable
function,
e.g.ECO/Night
mode1 Click: Variable direct function, e.g.ECO/Night mode
Frontdirect
and
Button
Functionallity:
1 Click: Temperature setpoint
1 Click: Temperature setpoint
Sub function: Back
Sub function: Back
Sub function:function,
Up
Sub function: Up
1 Click: Variable
e.g. light
1 Click: Variable direct function, e.g. light
1 Click: direct
Temperature setpoint
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
Hold 3 sec:
Menu
Hold 3 sec: Menu
Hold 3 sec: Menu
Sub
function: Down
Sub function: Down
Sub
function:
OK
Sub function: OK
Sub function: OK
1 ERC
Click: Variable
function,
e.g.ECO/Night
mode
Frontdirect
and
Button
Functionallity:
1 Click: Temperature setpoint
Sub function: Back
Sub function: Up
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
Hold 3 sec: Menu
Hold 3 sec: Menu
Sub function: Down
Sub function: Down
Sub function: OK
Sub function: OK
1 ERC
Click: Variable
direct
function,
e.g.ECO/Night
mode
Front and Button Functionallity:
1 Click: Temperature setpoint
Sub function: Back
Sub function: Up
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
(scroll through parameters)
Hold 3 sec: Menu
Hold 3 sec: Menu
Sub function: Down
Sub function: Down
Sub function: OK
Sub function: OK
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Back
Sub function: Up
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
1 Click: Variable direct function, e.g. light
1 Click: Temperature setpoint
Hold 3 sec: Menu
Hold 3 sec: Menu
Sub function: Down
Sub function: Down
Sub function: OK
Sub function: OK
ht
Danfoss ERC 102Danfoss ERC 102
Danfoss ERC 102Danfoss ERC 102
Danfoss ERC 102Danfoss ERC 102
Danfoss ERC 102
Danfoss ERC 102
Danfoss ERC 102
102
Danfoss ERC 102Danfoss ERC 102
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
Sub function: OK
1 Click: Temperature setpoint
Sub function: Down
Functionallity: 1 Click:
Variable
directand
function,
e.g. light Functionallity:
ERC
Front
Button
ERC Front and
Button
(scroll
throughFunctionallity:
menu group) 1 Click: Temperature setpoint
O/Night mode
Hold 3 sec: Menu
Sub function: OK
Sub function: Down
1 Click:
Variable
direct
function,
mode
Click: Variablesetpoint
direct function, e.g.ECO/Night mode
1 Click:
Variable
direct
function,
e.g.e.g.ECO/Night
light
1 Click:1 Temperature
Sub function:
Sub function:
Up Back
1 Click:
Temperature
setpoint
1 Click:
Temperature
setpoint
SubSub
function:
Down
function:
Up
Sub
function:
Hold
3 sec:
MenuBack
5.3.5
Password
protection
Sub function: OK
1 Click: Temperature setpoint
Sub function: Up
Press and hold 5
sec to access the
menu
1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
Sub function: OK
ht
18
Click: Variablesetpoint
direct function, e.g. light
1 Click:1 Temperature
Hold 3 sec:
Menu
Sub function:
Down
Sub function: OK
Password protection on three levels
Level 1: Shop (daily use by shop personnel)
Level 2: Ser (service technician)
1 Click: Temperature setpoint
1 Click: Temperature setpoint
Level 3: OEM (OEM programming)
Sub function: Down
ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS
Sub function: Down
02 6. CONFIGURATION OF INPUTS AND OUTPUTS
The ERC 102 inputs and outputs are configurable by
tionallity:
the customer. Before getting started it is a good idea
to check if all inputs are configured correctly and
match the sensors attached.
mode Input and output configuration settings are part of
the assignment menu (ASi).
For instance: Danfoss supplies only 2-pole defrost
sensors, so input S3 will most likely be used as a
defrost / evaporator temperature sensor input.
Please contact your local Danfoss representative for
information about default settings.
1 Click: Temperature setpoint
Sub function: Up
NOTE: Coded sensors will impact on the number of
possible configurations.
Assignments / ASi
6.1 Changing input and output configuration settings
There are two steps to inputting the configuration:
1. Define the type of sensor attached to the input:
- Temperature / light / digital
1 Click: Temperature setpoint
Subapplication
function: for
Down
2. Define the
the sensor:
- Temperature: control / condenser / evaporator
- Light: ECO / display / both
- Digital: door sensor
Example: Input S1 is attached to a temperature sensor. The sensor measures cabinet temperature.
Example: Input S2 is attached a digital on/off sensor which is a door open / closed switch.
C
S1
S2
S3
b
a
Connector inputs: analogue ( a ), digital ( b )
Connector outputs ( c )
ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
19
ERC menu
code
Default
Min
Max
Unit Conv
Unit
Scale
Default Access
Shop Ser OEM
Assignments
ASi
S1 Config
S1C
Stn
Stn
dig
no
-- -- RW
S2 Config
S2C
Stn
Stn
dig
no
-- -- RW
S3 Config
S3C
Stn
Stn
dig
no
-- -- RW
S1 Application
S1A
SCo
nC
doo
no
-- -- RW
S2 Application
S2A
nC
nC
doo
no
-- -- RW
S3 Application
S3A
nC
nC
doo
no
-- -- RW
DI Config
diC
dio
doC
dio
no
-- -- RW
DO1 Config
01C
CoP
CoP
HEt
no
-- -- RW
DO2 Config
o2C
dEF
0
Lig
no
-- -- RW
DO3 Config
o3C
FAn
0
Lig
no
-- -- RW
DO4 Config
o4C
dEF
0
Lig
no
-- -- RW
Button 1 Short Config
b1C
noP
tP
noP
no
-- -- RW
Button 1 Long Config
b1L
PoF
tP
PoF
no
-- -- RW
Button 2 Short Config
b2C
dEF
tP
noP
no
-- -- RW
Button 3 Short Config
b3C
tP
tP
noP
no
-- -- RW
Button 3 Long Config
b3L
ECo
tP
PoF
no
-- -- RW
Button 4 Short Config
b4C
tn
tP
noP
no
-- -- RW
Button 4 Long Config
b4L
Lig
tP
PoF
no
-- -- RW
Password level1
PS1
0
0
999
no
RW RW RW
Password level2
PS2
0
0
999
no
-- -- RW
Password level3
PS3
0
0
999
no
-- -- RW
Cabinet Light Control
Source
CLC
Lig
Lig
LEC
no
-- -- RW
Light off delay
Lod
0
0
300
no
20
ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
Sec
1
-- -- RW
2nallity:
e
e
nallity:
2
e
2nallity:
2nallity:
e
e
nallity:
e
2
nallity:
e
2
nallity:
e
1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub /function:
S1 Config
S1C Up
S2 Config / S2C
S3 Config / S3C
Temperature
Available1 Click:
options
are: setpoint
Sub function: Up
Stn for a temperature sensor (values given in Celsius)
Ldr for a light sensor (values given in Luminens)
Dig for a digital sensor with simple on/off indication
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function:
S1 Application
/ Up
S1A
1 Click: Temperature
S2 Application
/ S2A setpoint
Sub function: Down
S3 Application
/ S3A
1
Temperature
AvailableClick:
options
are: setpoint
Sub function: Up
nC:Not connected
SCo:Temperature control
EuA:Evaporator temperature
1 Click: Temperature setpoint
Con:Condenser
temperature (Condenser cleaning)
Sub function: Down
LS1:Light sensor (Ldr), Luminens, dedicated to Eco mode switching detection
LS2:Light sensor (Ldr), Luminens, dedicated to determining LED intensity
LS3:Light
sensor(Ldr),
Luminens, used for both Eco mode detection and
1 Click:
Temperature setpoint
Sub function: Down
determining
LED intensity
doC:Door contact, contact closed when door closed
1 Click: Temperature setpoint
doo:Door
contact, contact open when door closed
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
DI Config / diC
This is the digital input used for a digital sensor or bus communications.
doC:Door contact, contact closed when door closed
doo:Door contact, contact open when door closed
bus:Modbus communication (used only for KoolProg)
1 Click: Temperature setpoint
diO:One
Communication
SubWire
function:
Up
1 Click: Temperature setpoint
Sub function: Down
D01 Config / D1C
CoP:Direct compressor control
Pil:Pilot Relay (No Zero Cross) – if using pilot relay to control a compressor,
this option must be used instead of CoP
Het:Heating application, inverse output.
1 Click: Temperature setpoint
Sub function: Down
ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
21
e
2nallity:
1 Click: Temperature setpoint
Sub function: Up
e
nallity:
1 Click: Temperature setpoint
Sub function:
D02 Config
/ o2CUp
D03 Config / o3C
D04 Config / o4C
e
1 Click: Temperature setpoint
Sub function: Up
nO: not used
dEF: Electric Defrost Heater / Valve for hot gas
ALA: Alamr
Output
1 Click: Temperature setpoint
Fan: FanSub
control
function: Down
LIG: Light control
2
2nallity:
1 Click: Temperature setpoint
Sub function: Down
2nallity: 6.2 Program the buttons
Click: Temperature
Temperature setpoint
setpoint
11 Click:
Sub
Subfunction:
function:Up
Down
e
e
2nallity:
1 Click: Temperature setpoint
function: (short
Up
Button Sub
1 Config
press) / b1C
Lower left button
Button 1 config (long press) / b1L
1 Click:
Temperature setpoint
Lower left
button
Sub function: Up
Button 2 Config (short press) / b2C
Upper left button
Button 3 Config (short press) / b3C
1 Click: Temperature setpoint
Upper right
button
Sub
Subfunction:
function:Up
Down
Button 3 config (long press) / b3L
Upper right button
Button 141 Click:
Config
(short
press) / b4C
Click: Temperature
Temperature setpoint
setpoint
Subfunction:
function:
Down
Lower right
button
Sub
Up
Button 4 Config (long press) / b4L
Lower right button
e
2
nallity:
e
2nallity:
e
2
nallity:
1 Click: Temperature setpoint
1Sub
Click:
Temperature
function:
Down setpoint
e
nallity:
Sub function:
Up programmed as follows:
The buttons
can be
e
Short press function
Long Press function
1 Click:
Temperature setpoint
tP: Increase
Setpoint
1Sub
Click:
Temperature
function:
Down setpoint
tn: Decrease
setpoint
Sub function:
Up
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle
defrost
1 Click:
Temperature setpoint
SubSuper-Cool
function: Down
SuP: Toggle
/Pull-down
diP : Increase display intensity
din : Decrease display intensity
tP: Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Toggle Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
Not operating
ERC power ON/OFF
1 Click: Temperature setpoint
Sub function: Down
NOTE: Buttons 1, 3 and 4 can be assigned to operate with 2 functions (short press or long press).
1 Click: Temperature setpoint
NOTE: Your assignments may notSub
befunction:
shownDown
on the printed buttons. We advice to use this functionality
together with the fully integrated mounting model only.
22
ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
2nallity:
2nallity: 6.3 Set passwords
e
1 Click: Temperature setpoint
Sub function: Up
e
nallity:
e
2
nallity:
1 Click: Temperature setpoint
Sub level
function:1Up
Password
/ PS1
Password Level 2 / PS2
Password Level 3 / PS3
1 Click: Temperature
setpoint
These assign
passwords
to the three levels of access. The password is a three-digit
Sub function: Up
number. Access levels are Shop, Service and OEM. You may not therefore have access to change all the passwords. Passwords are entered by using the up and down
arrow buttons.
1 Click: Temperature setpoint
Danfoss Sub
advises
against using passwords which are easy to remember or enter, for
function: Down
example 111, 222, 123 etc.
NOTE: When
the controller with 3 wrong password in a sequence ERC will
1 Click: accessing
Temperature setpoint
Sub function:
Down
automatically
block
access for 15 minutes.
e
2
nallity:
6.4 Set lighting function
1 Click: Temperature setpoint
Sub
Subfunction:
function:Up
Down
Cabinet Light Source Control / CLC
This parameter can be set to one of these alternatives to control the light in the
cabinet:
Lig:button only – the light will only come on when the light button on the ERC
102 is pressed (toggle functionality).
Ldo:door (and button if defined) only
LEC:economy (and button if defined) only
1 Click: Temperature setpoint
Sub function: Down
Light off delay / Lod
Number of seconds the light will stay on after the
door has been closed.
ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS
23
02
7. PARAMETERS
This chapter details all user-accessible parameters
in ERC 102 software 5.05.
The access level can be set separately for each
parameter using KoolProg software. There are three
levels of access – 1, 2 and 3. Level 1 is for shop access,
level 2 for technicians and level 3 for OEMs. The access
levels cannot be set using the buttons. Passwords for
the different levels can however be altered for the
level of access you have – for example a level 2 user
can change the password for level 1 and level 2 but
not level 3.
NOTE: Incorrect parameter settings can lead to
inadequate cooling, excessive energy consumption,
unnecessary alarms and in the case of temperaturesensitive food storage, breaches in food hygiene
principles and regulations. Only a trained operator
should make changes to parameters.
tionallity:
INFO! Some parameters may be hidden to you. When
scrolling through menus, the parameters available will
mode have been pre-determined using KoolProg software.
Your access level will determine which parameters you
can view and edit.
1 Click: Temperature setpoint
Sub function: Up
7.1 Thermostat / tHE
ERC 102 can handle both Celsius and
Fahrenheit. Changing from C to F and vice-versa
is done in the Display menu. When the change
is made, all temperature values are automatically
re-calculated and updated in all other
parameters accordingly.
ERC menu
code
Default
Min
1 Click: Temperature setpoint
Sub function: Down
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
Thermostat
tHE
Set point adjustment ratio
SPr
0.5
0.0
1.0
no
.1
-- -- RW
Differential
diF
2.0
0.0
20.0
C/F r
K
.1
-- RW RW
High Set Point
HSE
50.0/122.0 -50.0/122.0 80.0/176.0
C/F a
°C/°F
.1
-- RW RW
Low Set Point
LSE
-35.0/-31.0 -35.0/-31.0 80.0/176.0
C/F a
°C/°F
.1
-- RW RW
Air Temp Adj.
tAd
C/F r
K/°R
.1
-- -- RW
24
0.0/0.0
ERC 102 Reference manual – 7 PARAMETERS
0.0/0.0
20.0/36.0
e
2
nallity:
2
e
nallity:
2
e
1 Click: Temperature setpoint
Sub function: Up
Set point / StP
StP is visible with KoolProg software only. This parameter defines the desired
temperature (set point). In standard operation the set point is changed by
simply pressing the “temperature up / down” buttons on ERC102; for laboratory
1 Click: Temperature
and assembly
line yousetpoint
may opt for software controlled set point adjustment
Sub function: Up
(speed improvement)
1 Click: Temperature setpoint
Sub function: Down
Set point adjustment ratio / SPr
The default value is set to 0.5 and the parameter is hidden by default.
Spr defines the position of the setpoint in relation to cut-in and cut-out.
setpointmid between cut-in and cut-out. Spr = 0 sets
Spr = 0,51 Click:
setsTemperature
the setpoint
Sub function: Up
the setpoint at the cutout. Spr =1 sets the setpoint at cut-in.
nallity:
2
e
1 Click: Temperature setpoint
Differential
/ diF Down
Sub function:
This defines the difference between the cut-out and the cut-in. The desired
1 Click: is
Temperature
setpointby SPr and diF.
temperature
determined
Sub function: Up
nallity:
e
2
High Set Point / HSE
11 Click:
Click: Temperature
Temperature setpoint
setpoint
Low SetSub
Point
/ LSE
Sub
function:
Down
function:
Up
These parameters define the temperature range limit of the controller. Once set,
the desired temperatue (setpoint) can not go above HSE or below LSE.
LSE Sets the minimum value for the set point
HSE Sets the maximum value for the set point
1 Click: Temperature setpoint
Sub function: Down
Cut-in and cut-out are automatically calculated from the desired setpoint (set
bybuttons on the control) and the differential. By default, cut-out and cut-in are
0,5*DiF above or below the desired temperature.
1 Click:
setpoint temperature in the cabinet is 5 degrees, and the
Example:
TheTemperature
desired average
Sub function: Down
differential is set to 2 degrees:
nallity:
e
1 Click: Temperature setpoint
Sub function: Up
Air Temperature Adjustment / tAd
This parameter is a relative value and allows adjustment of the
control sensor temperature.
For instance, at a measured temperature of 7*C and tAd set to -2K,
the input from the control sensor will be 5*C instead.
1 Click: Temperature setpoint
Sub function: Down
ERC 102 Reference manual – 7 PARAMETERS
25
mode
1 Click: Temperature setpoint
Sub function: Up
7.2 Alarms / ALA
ERC menu
code
Default
Min
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
1 Click: Temperature setpoint
Sub function: Down
Alarm
ALA
High Alarm delay
Htd
30
0
240
no
min
1
-- RW RW
Low Alarm delay
Ltd
0
0
240
no
min
1
-- RW RW
High Temp Alarm
HAt
15.0/59.0 -50.0/-58.0 80.0/176.0
C/Fa
°C/°F
.1
-- RW RW
Low Temp Alarm
LAt
-50.0/-58.0 -50.0/-58.0 80.0/176.0
C/F a
°C/°F
.1
-- RW RW
Pulldown delay
Pdd
240
0
960
no
min
1
-- RW RW
Door Open delay
dod
2
0
60
no
min
1
-- RW RW
Alarm Buzzer Duration
Abd
0
0
999
no
min
1
-- RW RW
Auto Clearance of
Alarm/Error
ACA
yES
no
yES
no
1
-- RW RW
26
ERC 102 Reference manual – 7 PARAMETERS
e
nallity:
2
e
2nallity:
e
nallity:
2
e
nallity:
e
2
nallity:
e
2
nallity:
e
1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
High Temp
AlarmUp/ HAt
Sub function:
Low Temp Alarm / Lat
High temperature alarm and low temperature alarm allow for individual alarm
setpoints. Both are absolute values. By setting HAt to the maximum value and LAt
to the minimum value, alarms will be deactivated.
1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
1 Click: Temperature setpoint
Sub function:
Up/ Htd
High Alarm
Delay
1 Click: Temperature setpoint
Low Alarm
Delay
/ Ltd
Sub function: Down
These parameters express the number of minutes to wait before sounding an
alarm once the High/Low Temp Alarm temperature is reached. Immediately prior
to the alarm sounding, another check of the temperature is made to see if the
temperature
still in the
alarm zone; if it is not, the then the alarm is not sounded.
1 Click: is
Temperature
setpoint
function: Upthe Low Alarm Delay will be set to 0 to warn about too low a
In most Sub
situations,
1 Click: Temperature setpoint
temperature
immediately.
Sub function: Down
Pulldown Delay / Pdd
1 Click: Temperature setpoint
Normally,
it is not necessary or desirable to sound an alarm during a pull down
Sub function: Down
(the initial phase of reaching the desired temperature). This parameter prevents
the High Temp Alarm HAt sounding during pull down and after a defrost for the
number1of
minutes set for the parameter.
Click: Temperature setpoint
Sub function: Up
NOTE: It does not apply to the Low Temp Alarm LAt.
1 Click: Temperature setpoint
Sub function: Down
Door Open Delay / dod
It is possible to indicate to customers that a door has accidentally been left open.
This parameter sets the delay in minutes before the alarm sounds. This is useful in
environments where customers / users may hold the door open while making their
selection. If the door is closed again before the set number of minutes is reached,
the alarm does not sound.
Click: Temperature setpoint
NOTE: A1Sub
door
sensor is required if this parameter is to be activated.
function: Down
1 Click: Temperature setpoint
Sub function: Up
Alarm Buzzer Duration / Abd
The ERC 102 alarm sounds for 10 seconds, followed by silence for 50 seconds. One
alarm sequence therefore lasts 60 seconds. These values cannot be changed. This
parameter determines how long in minutes an audible alarm will continue while
there is still a reason to have an alarm. If set to 999, the alarm will continue to
sound until the reason for the alarm is cleared – for example the temperature has
dropped enough or the door closed. In some cases, it may be necessary for a user
1 Click: Temperature setpoint
or technician
to take action in order to clear the alarm. If set to 0, the alarm will
Sub function: Down
never sound.
ERC 102 Reference manual – 7 PARAMETERS
27
e
1 Click: Temperature setpoint
Sub function: Up
Auto Clear of Alarm / Error / ACA
If this parameter is set to nO:
The alarm status will not disappear automatically even if the condition which
caused the alarm is no longer valid or present.
If set to yES:
02
tionallity:
As soon as the condition which caused the alarm is no longer valid or present, the
1 Click: Temperature setpoint
alarm status
will automatically change back to inactive. There will be no trace of
Sub function: Down
the alarm having occurred.
In general, Glass Door Merchandise applications will be set to yES and Commercial
Fridges and Freezers set to nO. For example, if the temperature goes too high for
a period there may be food safety considerations in a freezer containing food but
not in a fridge with cold drinks.
mode
1 Click: Temperature setpoint
Sub function: Up
7.3 Compressor / CoP
ERC menu
code
Compressor
Default
Min
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
CoP
Min run time
Crt
0
0
30
no1 Click:
min
1
-- RW RW
Temperature
setpoint
Min Stop time
CSt
0
0
30
no Sub function:
min
1
Down
Max Off time
Cot
0
0
480
no
min
1
-- -- RW
Error run time
Ert
0
0
60
no
min
1
-- -- RW
-- RW RW
Error stop time
ESt
1
0
60
no
min
1
-- -- RW
Minimum cut-in voltage
uLi
0
0
270
no
Vac
1
-- -- RW
Minimum cut-out voltage
uLo
0
0
270
no
Vac
1
-- -- RW
Maximum voltage
uHi
270
0
270
no
Vac
1
-- -- RW
-- RW RW
Power On Delay
Pod
300
0
300
no
Sec
1
Power Factor
PFA
0
-90
90
no
Degree
1
-- -- RW
Initial cut in
iCi
no
no
yes
no
1
-- R- RW
Cdd
0
0
15
no
1
-- RO RW
Compressor door open delay
28
ERC 102 Reference manual – 7 PARAMETERS
min
e
2
nallity:
e
2
nallity:
2
e
2nallity:
e
nallity:
e
1 Click: Temperature setpoint
Sub function: Up
Minimum Run Time / Crt
This parameter is a number of minutes from 0 to 30.
It determines the minimum number of minutes the compressor must run before a
Temperature cut-out can take effect. For example, if the temperature sensor indicated that the cut-out temperature has been reached, but the number of minutes
set in this parameter have not elapsed since the compressor last started, then the
1 Click:will
Temperature
setpoint
compressor
continue.
It will only stop once the duration given by Crt has been
Click:
Temperature
setpoint
function:
Up
reached1Sub
–
provided
the
temperature
is still low enough.
Sub function: Down
Crt thus overrides the cut-out.
Minimum Stop Time / CSt
This parameter is a number of minutes from 0 to 30.
It determines the minimum number of minutes the compressor must remain idle
before a Temperature cut-in can take effect. For example, if the temperature sensor
indicates that the cut-in temperature has been reached, but the number of minutes
set in this parameter have not elapsed since the compressor last stopped, then the
compressor will stay off. It will only start once the duration given by CSt has been
11 Click:
Temperature
Temperature setpoint
reachedSub
–Click:
provided
thesetpoint
temperature is still high enough.
Subfunction:
function:Up
Down
CSt thus overrides the cut-in.
Maximum Off Time/ Cot
This is the maximum time in minutes the compressor is allowed to idle – up to 480
1 Click: Temperature setpoint
minutes.Sub
Cot
is setUpto zero by default (inactive). If ERC102 is to be used on a draft
function:
beer (ice bank) application, this parameter can be used to control the ice thickness.
1 Click: Temperature setpoint
SubTime
function:/ Up
Error Run
Ert
1 Click:
Temperature
Error Stop
Time
/ ESt setpoint
Sub function: Down
These two parameters only become active in the unlikely event of a broken temperature sensor. They are then used to run the application in safety mode. At the
same time the sensor error will be shown in the display.
Ert and ESt values are based on OEM experience and are by default inactive.
1 Click: Temperature setpoint
Ert and ESt
define the duration the compressor will run (Ert) and be idle (ESt).
Sub function: Down
Example: Ert = 4 [min] and ESt = 16 [min] will provide an average cooling system
activity of 20%.
1 Click: Temperature setpoint
Sub function: Down
ERC 102 Reference manual – 7 PARAMETERS
29
2nallity:
e
1 Click: Temperature setpoint
Sub function: Up
e
nallity:
1 Click: Temperature setpoint
Sub cut-in
function: Up
Minimum
voltage / uLi
Minimum cut-out voltage / uLo
Maximum voltage / uHi
1 Click: Temperature setpoint
These three
parameters provide voltage protection to the compressor. Start by
Sub function: Up
setting uHi, followed by uLo and uLi.
e
uLi: When the compressor is due to start, the voltage of the power supply will be
1 Click: Temperature setpoint
checkedSub
and
the compressor will only be allowed to start if it is at least the value
function: Down
given in this parameter.
uLo: When
the
compressor
1 Click:
Temperature
setpointis running, it will be switched off if the voltage goes
Sub function:
Down
below that
given in
this parameter.
uHi: When the compressor is running, it will be switched off if the voltage exceeds
1 Click: Temperature setpoint
that given
in this parameter. If the compressor is already stopped, it will remain
Sub function: Down
switched off.
2
nallity:
2
e
1 Click: Temperature setpoint
Sub function: Up
nallity:
02
e
1 Click:
Temperature
Power On
Delay
/ Podsetpoint
Sub function: Up
This is the delay in seconds between power-on and the compressor being
activated. Depends on the Power on Temperature setting as explained below.
tionallity:
2
Power Factor / PFA
This value is hidden by default. The parameter is used by the Zero Cross function
to optimize1 Click:
the Temperature
switchingsetpoint
position of the relay contact.
mode
1 Click: Temperature setpoint
function:
Up
SubSub
function:
Down
onallity:
Warning: Do not change without first consulting your local
Danfoss representative.
Initical 1Cut-in
/ iCi setpoint
1Click:
Click:Temperature
Temperature
setpoint
Sub
Down
Sub function:
function:
Up
if the control
temperature
is between cut-in and cut-out at power up customers can
determine if the compressor shall start immediatly (yes) or wait for cut-in temperature to start (no).
de
Power on Temperature / PoT
This parameter is used to accelerate the first application test on the OEM assembly
line; if the cabinet
temperature
1 Click: Temperature
setpoint is higher than this parameter the Power On Delay is
Sub function:
Down are activated without delay.
overruled and
the outputs
Compressor Door Open Delay / Cdd
This parameter sets the delay in minutes before the compressor stops when the
1 Click: Temperature
door is opened.
If set tosetpoint
zero, the function is disabled.
Sub function: Down
30
ERC 102 Reference manual – 7 PARAMETERS
mode
1 Click: Temperature setpoint
Sub function: Up
7.4 Defrost / dEF
Note: ERC controllers feature Safe Defrost
functionality (patents pending) by default. This function ensures proper defrost
under poor power conditions.
For more details please contact Danfoss.
ERC menu
code
Default
Min
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
1 Click: Temperature setpoint
Sub function: Down -- RW RW
Defrost
dEF
Def type
dFt
no
no
Hgd
no
Def reset temp
drt
5
0
80
C/F a
°C
1
-- RW RW
Def Min Interval
dii
6
0
96
no
hour
1
-- RW RW
Def Max Interval
dAi
7
0
96
no
hour
1
-- RW RW
Def Min Time
dit
5
0
240
no
min
1
-- RW RW
Def Max time
dAt
30
0
480
no
min
1
-- RW RW
Drip off time
dot
0
0
60
no
min
1
-- -- RW
Fan delay after Defrost
Fdd
0
0
60
no
sec
1
-- -- RW
C/F a
°C/°F
.1
-- -- RW
1
-- -- RW
Fan start Temp
Ftd
Defrost Fan on
dFA
25.0/77.0 -25.0/13.0 25.0/77.0
no
no
yES
no
Initial Defrost Interval
idi
3
0
96
no
1
-- -- RW
Initial Defrost Duration
idd
100
0
999
no
hour
1
-- RW RW
Defrost on compressor
time
dCt
no
no
yES
no
1
-- -- RW
ERC 102 Reference manual – 7 PARAMETERS
31
e
1 Click: Temperature setpoint
Sub function: Up
2
nallity:
Defrost Type / dFt
When set to nO, the defrost function is disabled and no automatic defrosting
will occur.
2
e
1 Click: Temperature setpoint
When set
EL orUp
nAt, electrical, natural or off-cycle defrosting is used. An adSubto
function:
ditional setting of Hgd (hot gas defrosting) is available.
nallity:
1 Click: Temperature setpoint
2
Sub function: Down
Terminate
Temperature / dtt
This parameter defines at what temperature the defrost cycle will stop.
1 Click: Temperature setpoint
The temperature
is given by the evaporator sensor or by the cabinet
Sub function: Up
temperature sensor if no evaporator sensor is used.
e
nallity:
Defrost reset temperature / drt
1 Click:counter
Temperature
The defrost
issetpoint
saved and restored at power-up, but if the temperature
1Sub
Click:
Temperature
function:
Down setpoint
sensor, used
for defrost,
is higher than this value at power-up, it is assumed that
Sub function:
Up
the evaporator is free of ice and the defrost counter will be cleared.
2
e
nallity:
2
Minimum Interval / dii
1 Click: Temperature
This parameter
can besetpoint
set to between 0 and 96 hours and defines the minimum
Sub function: Down
time period
between the start of two defrost cycles. Once the minimum interval
1 Click: Temperature setpoint
has expired,
the defrost
cycle will start at the following cut-out or once the maxiSub function:
Up
mum interval dAi has been reached.
e
nallity:
1 Click:
Temperature
setpoint
Maximum
Interval
/ dAi
1Sub
Click:
Temperature
function:
Down setpoint
This parameter
can
be
set to between 0 and 96 hours and defines the maximum
Sub function: Up
time period between the start of two defrost cycles.
e
2
Minimum Time / dit
This parameter can be set to between 0 and 240 minutes and defines the mini1 Click: Temperature
setpoint
mum duration
of a defrost
cycle. During this period, the ERC 102 will not check
Sub function: Down
the temperature. Once the minimum time has expired, the temperature will be
checked and if the Terminate Temperature dtt has been reached, the defrost
1 Click: Temperature setpoint
cycle willSubend.
If dtt has not been reached, defrost will continue until either dtt is
function: Up
reached or the Maximum Time dAt reached, whichever occurs first.
nallity:
2
e
1 Click: Temperature setpoint
Sub function: Down
nallity:
Maximum Time / dAt
This parameter can be set to between 0 and 240 minutes and defines the maximum duration
of a defrost
cycle.
1 Click: Temperature
setpoint
function:
Up allow a maximum time to be entered which is less than the
The ERCSub
102
will not
minimum time, or a minimum time which is more than the maximum time.
e
Drip Off1 Time
/ dot setpoint
Click: Temperature
Sub function:
Downan electrical heater. This parameter can be set to between
This is only
used with
0 and 60 minutes and defines how long the delay is between the heater being
switched off and the compressor starting again.
32
ERC 102 Reference manual – 7 PARAMETERS
1 Click: Temperature setpoint
Sub function: Down
2
e
1 Click: Temperature setpoint
Sub function: Up
nallity:
e
2
nallity:
e
allity:
allity:
2
nallity:
e
Fan Delay after Defrost / Fdd
This parameter can be set to between 0 and 60 seconds and defines how
1 Click: Temperature setpoint
long theSub
delay
is between
the start of the compressor after defrost and the
function:
Up
fan starting again.
Fan Start Temperature / Ftd
Temperature
setpoint
This only1 Click:
applies
if an evaporator
temperature sensor is fitted. This parameter
Sub function: Down
determines at what evaporator temperature the fan will start after a defrost cycle
is complete.
If the time set in Fdd occurs before the temperature set in Ftd, the fan will start
in line with Fdd. If the temperature set in Ftd occurs first, then the fan will start in
1 Click: Temperature setpoint
line withSub
Ftd.
It is Up
therefore a case of whichever parameter’s setting is reached first
function:
1 Click: Temperature setpoint
which determines
when the fan starts.
Sub function: Down
Defrost Fan On / dFA
1 Click: Temperature setpoint
Set to Sub
yES,function:
the fan
Up will constantly run during defrost cycles.
Set to nO, the fan will not run during defrost cycles.
Initial Defrost Interval / idi
The initial defrost interval determines the time for first defrost after power-up. The
1 Click: Temperature
initial defrost
is mainlysetpoint
intended for factory testing of the defrost functionality and
Sub function: Down
can be set to expire after a number compressor cycles according to the setting
1 Click: Temperature setpoint
of parameter
idd
Sub function:
Up. During normal operation, the defrost counter will be saved in
memory and restored after power loss, making the initial defrost unnecessary.
1 Click: Temperature setpoint
Sub function: Down
Initial Defrost Duration / idd
The initial defrost duration is the number of compressor cycles before the initial
defrost is deactivated.
0: idi No initial defrost
1 Click: Temperature setpoint
1-998: number
of Up
compressor cycles before deactivation
Sub function:
999: Initial defrost always active.
1 Click: Temperature setpoint
Sub function: Down
Defrost On Compressor Time / dCt
If this parameter is set to yES, then defrost cycles are based on the total time
the compressor has been running.
If this parameter is set to nO, then defrost cycles are related to elapsed time,
regardless of how long and how often the compressor has been on.
1 Click: Temperature setpoint
Sub function: Down
ERC 102 Reference manual – 7 PARAMETERS
33
mode
1 Click: Temperature setpoint
Sub function: Up
7.5 Fan / FAn
The fan parameters are all related to energy saving,
and to redistribution of air within the cabinet to
reduce the amount of energy spent on cooling.
2
nallity:
2
e
nallity:
ERC menu
code
Default
Min
Max
Unit
Conv
Fan
FAn
Fan always On
FAo
yES
no
yES
no
Fan stop time on door open
Fdt
999
0
999
no
0
0
240
no
0 Temperature
0 setpoint240
1 Click:
Sub function:
Up 0
0
960
no
Fan On Delay
Fod
Fan Stop delay
FSd
Fan On Cycle
FoC
Fan Stop Cycle
FSC
2
0
0
960
Unit
Scale
Default Access
Shop Ser OEM
1
-- -- RW
1 Click: Temperature
setpoint
Sec
1
-- -- RW
Sub function: Down
Sec
1
-- -- RW
Sec
1
-- -- RW
no
Sec
1
-- -- RW
no
Sec
1
-- -- RW
Fan Always On / FAo
1 Click: Temperature setpoint
If this parameter
Sub function:is
Upset to yES, all other parameters in this section
about the fan are deactivated.
NOTE: If FAo is set to nO, then the following parameters will be applied.
e
2nallity:
Fan stop time on door open: Fdt
The maximum time the fan will be stopped after the door has been opened.
1 Click:
setpoint
0: fan will
notTemperature
stop under
opening
Sub
Subfunction:
function:Up
Down
1-998: number of seconds fan will be stopped during door opening
999: fan will be stopped as long as the door is open
e
nallity:
e
2
1 Click: Temperature setpoint
function:
Up
Fan On Sub
Delay
/ Fod
1 Click: Temperature setpoint
Fan Stop
Delay / FSd
Sub function: Down
If this parameter and FSd are both set to zero then the fan runs whenever the
compressor runs.
2nallity:
Fod defines the fan delay
(in seconds) after a compressor
Click: Temperature setpoint
cut-in. 1Sub
Subfunction:
function:Up
Down
FSd defines the fan delay after a
compressor cut-out.
e
nallity:
e
1 Click: Temperature setpoint
Up
Subfunction:
function:
Down
Fan On Sub
Cycle
/ FoC
Fan Stop Cycle / FSC
When the compressor is off, and FoC or FSC are not zero, the fan runs in cycles
according to FoC and FSC.
Example: FoC = 120 [sec] and FSC = 120 [sec] means that the fan runs for half the
time when the compressor is off. When the compressor is on, the fan is always on
(according to FAo and Fod).
1 Click: Temperature setpoint
Sub function: Down
34
ERC 102 Reference manual – 7 PARAMETERS
1 Click: Temperature setpoint
mode
2
2nallity:
1 Click: Temperature setpoint
Sub function: Up
7.6 Energy Management / Eng
ERC menu
code
Energy management
Default
Min
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
Eng
Shop Light Day
SLd
50
0
100
no
Shop Light Night
SLn
50
0
100
no
% Temperature
1
RW
RW RW
1 Click:
setpoint
%
1
RW RW RW
Sub function: Down
Eco Activity delay
EAd
0
0
360
no
min
1
Eco Light delay
ELd
5
0
10
no
min
1
RW RW RW
-- RW RW
Light Blocking delay
Lbd
0
0
360
no
min
1
-- RW RW
Eco Temperature Offset
Eto
4.0/7.2
0,0
10.0/18.0
C/F r
K/°R
.1
-- RW RW
NOTE: Some of these parameters require the installation of the Danfoss Ambient Light Sensor.
e
1 Click: Temperature setpoint
nallity: The Danfoss USB Gateway in combination
with KoolProg software allows for real time measurement of the
Sub function: Up
e
2
nallity:
2
e
nallity:
e
current light intensity. Danfoss recommends testing and adjusting SLd and SLn values according to customers’ specific needs.
1 Click: Temperature setpoint
Sub function:
Shop Light
Day /Up
SLd
Shop Light Night / SLn
These parameters are set as the percentage of the maximum light and determine
when the device moves into or out of Eco mode for power-saving purposes.
SLd is the amount of ambient light which will cause the device to move to normal /
serving mode from Eco mode (normally occurs in the morning).
11 Click:
Click: Temperature
Temperature setpoint
setpoint
Subfunction:
function:Up
Down
Sub
SLn is the amount of ambient light which will cause the device to move to Eco
mode from normal / serving mode (normally occurs in the evening).
1 Click: Temperature setpoint
SubDelay
function:/ Down
Eco Door
EAd
The transition from Eco to normal mode and vice versa occurs on a change in light
1 Click: Temperature setpoint
level or door
activity.
Sub function: Up
NOTE: A door sensor is required.
Eco Light Delay / ELd
1 Click: Temperature setpoint
This parameter
causes a delay to the switch from Normal to Eco mode when the
Sub function: Down
shop lights are switched on or off. The ambient light sensor detects the change in
light level and causes a switch mode. With this parameter set to zero, the switch
off mode occurs immediately. If not set to zero (max: 10 minutes), then the change
will be delayed by the number of minutes set.
1 Click: Temperature setpoint
Sub function: Down
ERC 102 Reference manual – 7 PARAMETERS
35
2
Light Blocking delay / Lbd
If the cooler is placed where the ambient light is unstable, the ambient light sensor
can cause the cooler to toggle between ECO and normal mode.
The light blocking delay disables the light-sensor for a given time after ambient
light change from bright to dark, so that the cooler stays in ECO mode for at least
this time.1 Click:
When
the cooler is in serving or pull-down mode, the light sensor is
Temperature setpoint
de-activated
and Up
a change to ECO mode will be determined by the door-sensor.
Sub function:
0: No blocking of the ambient light sensor.
nallity:
02
e
tionallity:
Eco Temperature Offset / Eto
This parameter gives a relative temperature in degrees. It is the difference in
temperature for Eco mode operation compared to Normal mode.
NOTE: Setting a temperature offset may be illegal in
some jurisdictions.
1 Click: Temperature setpoint
mode
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
7.7 Pull Down / Pud
Pull down (sometimes known as Super Cool) is
a procedure for improving cooling performance,
accelerating the time used to reach the desired
temperature. Pull Down settings overrule all
other settings.
ERC menu
code
Pull Down
Default
Min
Max
Unit
Unit
Scale
Default Access
setpoint
Conv 1 Click: Temperature
Shop
Ser OEM
Sub function: Down
Pud
Pull-down Initiate
­Temperature
Pit
Pull-down Cycling
PCy
50.0/122.0 -40.0/-40.0 50.0/122.0
30
0
360
C/F a
°C/°F
.1
-- -- RW
no
min
1
-- -- RW
Pull-down defrost Interval
Pdi
15
0
48
no
hour
1
-- -- RW
Pull-down duration
Pdd
24
0
48
no
hour
1
-- -- RW
Pull-down limit temp
PLt
0.0/32.0 -55.0/-67.0 55.0/131.0
C/F a
°C/°F
.1
-- -- RW
Pull-down reduction
temp △t
Prt
0.1/0.2
C/F r
K/°R
.1
-- -- RW
36
ERC 102 Reference manual – 7 PARAMETERS
0,0
10.0/16.0
2
nallity:
e
2
nallity:
2
e
nallity:
e
2
nallity:
2
e
nallity:
e
2
nallity:
e
1 Click: Temperature setpoint
Sub function: Up
Pull Down Initiate Temperature / Pit
This parameter indicates the temperature which causes a pull down to start. If the
temperature measured inside the cabinet exceeds this value for longer than one
hour, then
pull
down will
start. The compressor will have already cut-in, so the only
1 Click:
Temperature
setpoint
Up
effect is Sub
to function:
stop defrost
cycles until the desired temperature is reached. The period
of one hour is fixed and cannot be altered.
1 Click: Temperature setpoint
Pull Down
Cycling
/ PCy
Sub function:
Down
This is the duration in minutes of the compressor cycling at the reduced set point
temperature. Once the desired Pull Down Limit Temperature PLt has been reached
1 Click: Temperature
setpoint
during Pulldown,
the compressor
will continue to cycle on / off for the duration of
Sub function: Up
PCy. At the
end of the period defined by PCy, the Set Point temperature will return
to normal and Pulldown will cease.
1 Click: Temperature setpoint
Pull Down
Defrost
Interval / Pdi
Sub function:
Down
Even though most applications do not need Defrost during Pull Down, an extended
defrost during pull down can be applied. This is the time between defrost cycles
during Pull
Down.
It is setpoint
measured in hours and can be up to 48 hours. During Pull
1 Click:
Temperature
Sub function:
Down, this
settingUpoverrides the Defrost Interval and Defrost Time settings (see the
Defrost section).
1 Click: Temperature setpoint
Sub function:
Down/ Pdd
Pull Down
Duration
You can 1choose
to limitsetpoint
the maximum Pull Down time. Once this time value
Click: Temperature
function:
(max. 48Sub
hours)
isUp
reached, Pull Down will stop regardless of whether the desired
pull-down temperature has been reached.
Pull Down Limit Temperature / PLt
This parameter
sets thesetpoint
minimum allowed temperature during pull-down,
1 Click: Temperature
function: Down
In order Sub
to protect
valuable contents you must always specify the absolute mini1 Click: Temperature
setpointin your application.
mum temperature
allowed
Sub function: Up
For Glass Door Merchandisers 0°C/32°F protects bottles from freezing;
for Commercial Fridges you may opt for a slightly higher temperature (e.g. 2°C)
1 Click: Temperature setpoint
Pull Down
Reduction
Sub function:
Down Temperature Δt / Prt
ERC 102 calculates a lower set-point during Pull Down mode to increase the cooling capacity of your appliance. For each hour the cabinet temperature is above the
Pull down initiate temperature, the set-point is reduced with the value of Prt.
ERC 102 Reference manual – 7 PARAMETERS
1 Click: Temperature setpoint
Sub function: Down
37
mode
2
1 Click: Temperature setpoint
Sub function: Up
7.8 Automatic Heater Control / AHC
Automatic Heater Control applies reverse cooling
mode (heating) to your refrigeration appliance.
This feature requires:
A) that your appliance is exposed to ambient temperatures below the desired temperature in your
cabinet (e.g. very cold climates and outdoor use)
B) a special heater (for example a large defrost
heater) built in to your appliance.
ERC menu
code
Default
Min
Max
no
no
yES
setpoint
Unit 1 Click:
Unit Temperature
Scale
Default
Access
Conv Sub function: Down
Shop Ser OEM
Auto-Heater Control
AHC
Automatic heater mode
enable
AuH
Energy mode delay
End
60
0
360
no
min
1
-- -- RW
Heater displacement
temperature
Hdi
2.0/3.0
0.0/0.0
50.0/90.0
C/F r
K/oR
.1
-- -- RW
no
-- -- RW
nallity:
2
e
1 Click: Temperature setpoint
Sub function: Up
nallity:
Automatic Heater Mode Enable / AuH
This setting is normally set to nO.
1 Click:
Temperature
setpoint End and Hdi apply.
When set
to yES,
parameters
2
e
Sub function: Up
nallity:
Energy 1Mode
Delay /setpoint
End
Click: Temperature
Subdelay
function:
This is the
inDown
minutes between the heater and the compressor operation.
1 Click:
setpoint
The heater
is Temperature
not allowed
to start until this number of minutes has expired after
Sub function: Up
the compressor has cut out and vice versa.
e
Heater Displacement
Temperature / Hdi
1 Click: Temperature setpoint
This is the
Subtemperature
function: Down relative to (below) the desired temperature.
38
ERC 102 Reference manual – 7 PARAMETERS
1 Click: Temperature setpoint
mode
2
1 Click: Temperature setpoint
Sub function: Up
7.9 Condenser Protection / Con
NOTE: A condensor temperature sensor is
required to use these parameters.
Condenser protection is generally used in dusty
environments where the condenser may accumulate a layer of dust or dirt and therefore be at risk of
overheating.
ERC menu
code
Condenser Protection
Con
Condenser Alarm Limit
CAL
Default
Min
Max
Unit
Conv
80/176
0/32
85/185
C/F a
Unit
Scale
Default Access
Shop Ser OEM
1 Click: Temperature setpoint
Sub°C/°F
function:1 Down -- -- RW
Condenser Block Limit
CbL
85/185
0/32
85/185
C/F a
°C/°F
1
-- -- RW
Condenser OK limit
CoL
60/140
0/32
85/185
C/F a
°C/°F
1
-- -- RW
Condenser Low Limit
CLL
5
-20/-4
20/68
C/F a
°C/°F
1
-- -- RW
nallity:
2
e
1 Click: Temperature setpoint
Sub function: Up
nallity:
2
e
nallity:
2
e
nallity:
e
Condenser Alarm Limit / CAL
1 Click: Temperature
This parameter
sets thesetpoint
temperature for the condenser at which an alarm will
Sub function: Up
be generated.
Condenser Block Limit / CbL
1 Click: Temperature setpoint
This parameter
sets
thesetpoint
temperature which if reached will cause the compressor
function:
Up
1Sub
Click:
Temperature
to switchSuboff.
function: Down
Condenser OK Limit / CoL
1 Click: Temperature
setpoint
This parameter
sets the
temperature at which the compressor is allowed to
function:
Up
1Sub
Click:
Temperature
setpoint
start again
after
the
temperature
set in CbL above has been exceeded and the
Sub function: Down
compressor stopped.
Condenser Low Limit / CLL
This parameter
sets the
lowest (condenser) temperature at which the
1 Click: Temperature
setpoint
compressor
is allowed
Sub function:
Down to start.
ERC 102 Reference manual – 7 PARAMETERS
1 Click: Temperature setpoint
39
mode
2
nallity:
2
e
nallity:
1 Click: Temperature setpoint
Sub function: Up
7.10 Display / diS
ERC menu
code
Default
Min
Max
Unit
Conv
Display
diS
Display Unit
CFu
-C
-C
-F
no
Display Resolution
rES
0.1
0.1
1
no
Display Range Limit
Unit
Default Access
Shop Ser OEM
1 Click: Temperature RW
setpoint
RW RW
Sub function: Down -- -- RW
rlt
no
no
yES
no
Display Delay
ddL
0
0
10
no
Sec
Display Offset
doF
0.0/0.0
C/F r
K/oR
Lock-time After defrost
dLt
15
0
60
no
min
Show Economy state
SEC
no
no
yES
no
-10.0/-18.0 10.0/18.0
Scale
-- -- RW
1
-- -- RW
1
-- -- RW
-- -- RW
-- -- RW
Show Pull Down state
SSC
no
no
yES
no
-- -- RW
Show Defrost
SdF
yES
no
yES
no
-- -- RW
Display Intensity
din
10
1
10
no
1
RW RW RW
Click:
Temperature
This section deals with parameters1for
the
display.setpoint
Sub function: Up
NOTE: Some display parameters can be set in such as way that they may be illegal in some jurisdictions. Please
check local legislation.
e
1 Click: Temperature setpoint
DisplaySub
Unit
/ CFu
function:
Up
This parameter sets the display to Fahrenheit or Celsius. Switching from one to the
other will cause all temperature settings to be automatically updated accordingly.
2
Display Resolution / rES
This parameter can be set to 0.1, 0.5 or 1 and affects the way the temperature is
displayed. With the parameter set to 1, the display will only ever show tempera1 Click: Temperature setpoint
tures rounded
to the nearest whole degree. At 0.5, it will round the temperature to
Sub function: Down
the nearest half degree for display.
1 Click: Temperature setpoint
For example,
3.3 degrees will be shown in the display as 3.5 degrees and 3.9 as 4.0.
Sub function: Up
With the parameter set to 0.1, no rounding occurs.
1 Click: Temperature setpoint
This parameter
does
not affect the temperature itself, merely the display.
Sub function:
Down
nallity:
e
Display Range Limit / rLT
In some Point of Sales applications you may want to show the desired instead of
the real temperature. This parameter sets whether the displayed temperature is
the actual temperature or whether it is restricted to the cut-in / cut-out limits. Set
to nO means that the actual temperature will de displayed.
The parameter is set to nO by default.
40
1 Click: Temperature setpoint
Sub function: Down
ERC 102 Reference manual – 7 PARAMETERS
e
1 Click: Temperature setpoint
Sub function: Up
Display Delay/ ddL
In order to provide a realistic temperature appearance for an application,
a display delay can be set.
The parameter sets the time constant τ (tau) of the moving average filter
for the display.
Physically, one time constant represents the time it takes the system’s
step-response to reach 66% of its final value and five time-constants the time
1 Click: Temperature setpoint
it takes to
reach 99% of its final value.
Sub function: Down
The parameter can be set from 0 to 10 minutes.
2
nallity:
2
e
1 Click: Temperature setpoint
Sub function: Up
nallity:
2
e
nallity:
2
e
Display Offset / doF
This parameter is a relative value and allows the temperature displayed to be
1 Click: Temperature setpoint
differentSub
tofunction:
the temperature
measured. For instance, at a measured temperature
Up
of 7°C and doF set to -2K, the displayed temperature will be 5°C instead.
Lock Time After Defrost / dLt
Click:to
Temperature
In order1not
show a setpoint
rising temperature during defrosting, the displayed temSub function: Down
perature is locked at the temperature shown at the start of the defrost cycle for the
1 Click: Temperature setpoint
numberSub
of function:
minutes
Up set in this parameter.
0 = no lock.
nallity:
2
e
1 Click: Temperature
Show Economy
Statesetpoint
/ SEC
Sub function: Down
If set to yES, this parameter causes the display to show ECO when the system is in
1 Click: Temperature setpoint
ECO mode.
Sub function: Up
If set to nO, the temperature continues to be displayed.
nallity:
e
Show Pull down state / SSC
1 Click: Temperature setpoint
If set to yES,
this parameter
causes the display to show SC when the system is in
function:
Down setpoint
1Sub
Click:
Temperature
Pull Down
Sub mode.
function: Up
If set to nO, the temperature continues to be displayed.
Show Defrost / SdF
Click: Temperature setpoint
If set to1yES,
this parameter causes the display to show DEF when the system is in
Sub function: Down
defrost mode. If set to nO, the temperature continues to be displayed.
ERC 102 Reference manual – 7 PARAMETERS
1 Click: Temperature setpoint
41
e
1 Click: Temperature setpoint
Sub function: Up
Display Intensity / din
ERC 102 can have its display intensity (brightness) set in one of two ways:
A) with a Danfoss ambient light sensor attached, the brightness of the display is
adjusted automatically according to the ambient light level (see the Assignments
section)
B) when no ambient light sensor is attached, the display intensity can be set to
1 Click: Temperature setpoint
a fixed intensity.
Sub function: Down
Both options are on a scale of 1 to 10, where 10 is the brightest.
7.11 Assignments / ASi
For more details on how to set parameters
- see chapter 6.
ERC menu
code
Default
Min
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
Assignments
ASi
S1 Config
S1C
Stn
Stn
dig
no
-- -- RW
S2 Config
S2C
Stn
Stn
dig
no
-- -- RW
S3 Config
S3C
Stn
Stn
dig
no
-- -- RW
S1 Application
S1A
SCo
nC
doo
no
-- -- RW
S2 Application
S2A
nC
nC
doo
no
-- -- RW
S3 Application
S3A
nC
nC
doo
no
-- -- RW
DI Config
diC
dio
doC
dio
no
-- -- RW
DO1 Config
o1C
CoP
CoP
HEt
no
-- -- RW
DO2 Config
o2C
dEF
0
Lig
no
-- -- RW
DO3 Config
o3C
FAn
0
Lig
no
-- -- RW
DO4 Config
o4C
Lig
0
Lig
no
-- -- RW
Button 1 Short Config
b1C
noP
tP
noP
no
-- -- RW
Button 1 Long Config
b1L
PoF
tP
PoF
no
-- -- RW
Button 2 Short Config
b2C
dEF
tP
noP
no
-- -- RW
Button 3 Short Config
b3C
tP
tP
noP
no
-- -- RW
Button 3 Long Config
b3L
ECo
tP
PoF
no
-- -- RW
Button 4 Short Config
b4C
tn
tP
noP
no
-- -- RW
Button 4 Long Config
b4L
Lig
tP
PoF
no
-- -- RW
Pass-word level1
PS1
0
0
999
no
RW RW RW
Pass-word level2
PS2
0
0
999
no
-- RW RW
Pass-word level3
PS3
0
0
999
no
-- -- RW
Cabinet Light Control
Source
CLC
Lig
Lig
LEC
no
-- -- RW
Door close delay
dCd
0
0
300
no
Sec
1
-- -- RW
Light off delay
Lod
0
0
300
no
Sec
1
-- -- RW
42
ERC 102 Reference manual – 7 PARAMETERS
mode
1 Click: Temperature setpoint
Sub function: Up
7.12 Service Information / Ser
The parameters in the following section are READ
ONLY and cannot be changed by the user. They provide information for technicians and OEM users.
NOTE: the only parameters that can be configured are:
oEL, oEn, oEH.
These parameters allow OEMs to enter their own
product code.
ERC menu
code
Default
Min
Max
Unit
Unit
Scale
Default Access
setpoint
Conv 1 Click: Temperature
Shop
Ser OEM
Sub function: Down
Service
SEr
DI
Sdi
---
oFF
on
no
Voltage value
uAC
---
0
270
no
DOs Status
ouS
---
IIII
IIII
no
Relay 1 counter
rL1
---
0
999
no
-- R- RVac
1
-- R- R-
1000
1000
-- R- R-
-- R- R-
Relay 2 counter
rL2
---
0
999
no
1000
1000
-- R- R-
Relay 3 counter
rL3
---
0
999
no
1000
1000
-- R- R-
Relay 4 counter
rL4
---
0
999
no
1000
1000
-- R- R-
interval Counter
int
---
0
999
no
min
1
-- R- R-
Defrost time counter
dnt
---
0
999
no
min
1
-- R- R-
Door open counter
ont
---
0
999
no
1
1
-- R- R-
SW version
Fir
SWVER
-32768
32767
no
R- R- R-
HW version
HAr
HWVER
-32768
32767
no
R- R- R-
OrderNoLow
OnL
ORNOL
-32768
32767
no
-- -- --
OrderNoHigh
OnH
ORNOH
-32768
32767
no
-- -- --
OEM code Low
oEL
0
0
999
no
R- R- R-
OEM code Middle
oEn
0
0
999
no
R- R- R-
OEM code High
oEH
0
0
999
no
R- R- R-
Parameter version
PAr
PARVER
-32768
32767
no
R- R- R-
Last change
CHA
0
0
999
no
1
-- -- --
Manufacturing date
CHd
0
0
999
no
1
-- R- R-
1
Copy Key ID
Cid
0
0
999
no
Set as Default
SFC
no
no
yES
no
-- -- RRW RW RW
ERC 102 Reference manual – 7 PARAMETERS
43
8. TECHNICAL SPECS
Power Supply
100 V AC - 240 V AC, switch mode power supply
Average 0 7 W
Rated Power
4 Inputs: 3 Analogue & Digital, 1 Digital; user specific assignment
Input
• Air / Evaporator / Condenser
• Door sensor: All types, user specific
• Light sensor: Danfoss ECO light sensor
• DP for remote communication
DO1
(Compressor relay):
DO4
Output
UL60730
120 V ac: 16A resistive/ FLA16 / LRA72.
240 V ac: 10A resistive /FLA10 /LRA60.
8 A resistive, FLA2/ LRA12, TV-1
EN60730
16(16)A
8 A resistive, 2(2) A
DO5
FLA2/ LRA12, TV-1
8 A resistive, 2(2) A
DO6
FLA2/ LRA12, TV-1
8 A resistive, 2(2) A
Max 10 A total DO4-6
Probes
Danfoss NTC sensors and Danfoss ECO accessories (300 - 3,000 mm)
Connectors
Modular connector system for OEM customers, with optional output screw terminal adapter; Input connector
type: Rast2 5 Edge connectors; Output connector type: RAST 5 Standard
Programming
Programming with Danfoss ERC docking station, integrated system
Assembly
3 types for all controls: Front mounting (patents pending); brackets; fully integrated solution (requires OEM
specific design of mounting hole)
Display
LED display, 3 digit, decimal point and multi functionality icons; °C/F scale
Keypad
4 buttons (integrated IP65 design), 2 left, 2 right; user programmable
Operating Conditions
0 °C to 55 °C, 93% rH
Storage Conditions
-40 °C to 85 °C, 93% rH
Range of Measurement -40 °C to 85 °C
Protection
front: IP65/rear: water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to IP00
Environmental
Pollution degree II, non-condensing
Resistance to heat & fire Category D (UL94-V0)
EMC category
Category I
Operating Cycles
Approvals
Compressor relay: more than 175,000 at full load (16A(96A))
R290/R600a : EN/IEC 60079-15:2005
Glow wire according to EN/IEC 60335-1
IEC/EN 60730
UL60730
NSF
CQC
GOST R 60730
Note: These approvals
are only valid when
using the accessories
listed in this document
IMPORTANT NOTE
The inputs are not galvanic separated and are connected directly to the mains supply!
Dimensions:
36,5 mm
71 mm
28,5 mm
Front mounting
78,25 mm
71 mm
28 mm
30 mm
78,25 mm
82,25 mm
44
ERC 102 user manual – 8 TECHNICAL SPECS
Rear mounting
APPENDIX I: PARAMETER QUICK LIST
ERC menu
code
Description
Thermostat
tHE
Thermostat settings
Set point adjustment ratio
SPr
Current setpoint adjustment value diF * SPr
Differential
diF
Thermostat differential
High Set Point
HSE
Upper limit of thermostat set point
Low Set Point
LSE
Lower limit of thermostat set point
Air Temp Adj.
tAd
Applies to non-Danfoss temperature sensors only
ERC menu
code
Description
Alarm
ALA
Alarm settings
High Alarm delay
Htd
Alarm delay on high temperature
Low Alarm delay
Ltd
Alarm delay on low temperature
High Temp Alarm
HAt
Alarm is activated above this temperature (Celsius)
Low Temp Alarm
LAt
Alarm is activated below this temperature (Celsius)
Pulldown delay
Pdd
Alarm delay during pulldown (0-960 minutes) (high temperature only)
Door Open delay
dod
Alarm delay for door open (0-60 minutes)
Alarm Buzzer Duration
Abd
Alarm buzzer duration in minutes (0=no buzzer)
Auto Clearance of
Alarm/Error
ACA
yES: alarm auto-clears if system returns to normal; nO : alarm state maintained regardless
ERC menu
code
Description
Compressor
CoP
Compressor settings
Min run time
Crt
Minimum time compressor must run 0-30 minutes
Min Stop time
CSt
Min time compressor must idle 0-30 minutes
Max Off time
Cot
Max time compressor must idle 0-480 minutes
Compressor door open
delay
Cdd
Minutes before compressor stops when door opened
Error run time
Ert
Compressor run time if temperature sensor is not working (0-60 minutes)
Error stop time
ESt
Compressor stop time if temperature sensor is not working (0-60 minutes)
Minimum Cutin voltage
uLi
When compressor is off: Lowest compressor start voltage (0-270 V)
Minimum cut-out voltage
uLo
When compressor is on: Lowest operation voltage (0-270 V)
Maximum voltage
uHi
When compressor is on: Highest operation voltage (0-270 V)
Power On Delay
Pod
Delay in seconds after power-on before outputs active (change with care)
Power Factor
PFA
Phasic angle in degrees. Changing this may give decreased relay lifetime
Power-on temperature
Pot
If the temperature of compressor at power-on exceeds this then Power On Delay does not apply
ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST
45
ERC menu
code
Description
Defrost
dEF
Defrost Settings
Def. type
dFt
no: Defrost function is disabled
EL: Electrical or time defrost
Hgd: Hot gas defrost (contact Danfoss for details)
nat:Off-cycle defrost (natural defrost)
Def terminate temp
dtt
Temperature at which defrost cycle will stop
Def Min Interval
dii
The minimum time in hours between the start of each defrost cycle
Def Max Interval
dAi
The maximum time in hours between the start of each defrost cycle
Def Min Time
dit
The minimum duration of a defrost cycle in minutes
Def Max time
dAt
The maximum duration of a defrost cycle in minutes
Drip off time
dot
The duration in minutes of the drip-off time at the end of a defrost cycle
Fan delay after Defrost
Fdd
The duration in seconds before the fan starts after a defrost cycle
Fan start Temp
Ftd
The temperature at which the fan will start after a defrost
Defrost Fan on
dFA
Whether the fan will run during a defrost cycle
Initial Defrost Interval
idi
The number of hours after power-up before the first defrost cycle starts
Defrost on compressor
time
dCt
Whether the defrost cycles are measured by elapsed time (nO) or compressor run time (yES)
Fan
ERC menu
code
Description
FAn
Fan settings
Fan always On
FAo
nO: fan parameters below active. yES: Fan is always on
Fan On Delay
Fod
Delay in seconds before fan starts after compressor starts
Fan Stop delay
FSd
Delay in seconds before fan stops after compressor stops
Fan On Cycle
FoC
The number of seconds the fan runs when the compressor is off
Fan Stop Cycle
FSC
The number of seconds the fan does not run when the compressor is off
ERC menu
code
Description
Energy management
Eng
Energy Management
Shop Light Day
SLd
When ambient light is above this level, Eco mode is cancelled. Requires light sensor
Shop Light Night
SLn
When ambient light is below this level, Eco mode is enabled. Requires light sensor
Eco Activity delay
EAd
Minutes delay after last door opening until ECO mode is enabled; 0: disable
Eco Light delay
ELd
Delay [min] between detection of shop light on/off and ECO mode activation / suspension
Eco Temperature Offset
Eto
Temperature increase for Eco mode relative to normal mode
46
ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST
ERC menu
code
Pull Down
Pud
Description
Pull down settings
Pull-down Initiate
­Temperature
Pit
Pull-down Cycling
PCy
Minimum duration [min] of the pull-down mode, starting at PiT
Pull-down defrost Interval
Pdi
Defrost interval during pull-down. Over-rules the defrost interval in normal mode.
Pull-down duration
Pdd
Maximum duration [min] of the pull-down mode, starting at PiT
Pull-down limit temp
PLt
A safety feature; the lowest temperature allowed during pull-down.
Pull-down reduction
temp Δt
Prt
A calculation value for pull-down performance improvement. Instructions: See manual
ERC menu
code
If the cabinet temperature is above this temperature for >1h, pull-down mode is activated
Description
Auto-Heater Control
AHC
Auto-Heater settings (only if heater fitted for outdoor use in cold climates)
Automatic heater mode
enable
AuH
yES: Activate heater if ambient temperature is below desired cabinet temperature
Energy mode delay
End
Delay in minutes between heater and compressor operation
Heater displacement
temperature
Hdi
Heater displacement or OFFSET temperature relative to desired temperature.
ERC menu
code
Description
Condenser Protection
Con
Condenser Alarm Limit
CAL
If condenser sensor exceeds this temperature, alarm is activated
Condenser Block Limit
CbL
If this temperature is exceeded, compressor will be stopped.
Condenser OK limit
CoL
Temperature at which compressor may start after a stop due to exceeding CbL
Condenser Low Temp.
Limit
CLL
Temperature below which the compressor is not allowed to start
ERC menu
code
Condenser protection settings
Description
Display
diS
Display Unit
CFu
Display settings
F: Fahrenheit; C: Celsius
Display Resolution
rES
Display resolution for temp: 0.1, 0.5 or 1.0 C/F
Display Range Limit
rlt
Limits displayed temperature to actual setpoint +/- differential; may be illegal in some countries
Display Delay
ddL
Time period for moving average temperature display
Display Offset
doF
Display a different temperature relative to measured temperature
Lock-time After defrost
dLt
Display lock time after defrost [0-60 min]
Show Economy state
SEC
yES: display will show “Eco” when in Eco mode. nO: temperature will be shown
Show Pull Down state
SSC
yES: “SC “ will be displayed during Pull down; nO: “SC “ will not be displayed.
Show Defrost
SdF
yES: display will show deF during defrost ; no: Display will show temp
Display Intensity
din
Display intensity when no ambient sensor; min intensity with sensor
ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST
47
ERC menu
code
Description
Assignments
ASi
Assignment of inputs and outputs
S1 Config
S1C
Sensor type input 1 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input
S2 Config
S2C
Sensor type input 2 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input
S3 Config
S3C
Sensor type input 3 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input
S1 Application
S1A
Application to be controlled with Sensor D.
nC: Not connected
SCo: Temperature control
EuA: Evaporator temperture
Con: Condenser temperature (Condenser cleaning)
LS1: Light sensor(Ldr), Luminens, delicated for Economy detection
LS2: Light sensor(Ldr), Luminens, delicated for LED intensity scope
LS3: Light sensor(Ldr), Luminens, delicated for both Economy detection and LED intensity scope
doC: Door contact, Contact closed when door closed
doo: Door contact, Contact open when door closed
S2 Application
S2A
Application to be controlled with Sensor C.
nC: Not connected
SCo: Temperature control
EuA: Evaporator temperture
Con: Condenser temperature (Condenser cleaning)
LS1: Light sensor(LDR), Luminens, delicated for Economy detection
LS2: Light sensor(LDR), Luminens, delicated for LED intensity scope
LS3: Light sensor(LDR), Luminens, delicated for both Economy detection and LED intensity scope
doC: Door contact, Contact closed when door closed
doo: Door contact, Contact open when door closed
S3 Application
S3A
Application to be controled with Sensor B.
nC: Not connected
SCo: Temperature control
EuA: Evaporator temperture
Con: Condenser temperature (Condenser cleaning)
LS1: Light sensor(LDR), Luminens, delicated for Economy detection
LS2: Light
DI Config
diC
Sensor A (digital)
doC: Door contact, Contact closed when door closed
doo: Door contact, Contact open when door closed
dio: One wire digital communication
buS: MODBUS communication
DO1 Config
o1C
CoP: Compressor; PiL: Pilot Relay (No zero-cross); HEt: Inverse output, Heating application
DO2 Config
o2C
no:Not used; dEF: Elec defr heater/hot gas valve;ALA:Alarm output;FAn:Fan control;Lig:Light control
DO3 Config
o3C
nO: Not used; ALA: Alarm output; FAn: Fan control; Lig: Light control
DO4 Config
o4C
nO: Not used; ALA: Alarm output; Lig: Light control
Button 1 Config
b1C
Lower left button configuration.
tP:Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Activate Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
noP: Not operating
48
ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST
ERC menu
code
Description
Assignments
ASi
Assignment of inputs and outputs
Button 2 Config
b2C
Upper left button configuration.
tP:Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Activate Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
noP: Not operating
Button 3 Config
b3C
Upper right button configuration.
tP:Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Activate Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
noP: Not operating
Button 4 Config
b4C
Lower right button configuration.
tP:Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Activate Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
noP: Not operating
Pass-word level1
PS1
Level 1 Password (End user, shop owner), 0= disabled
Pass-word level2
PS2
Level 2 Password (Technical field service), 0= disabled
Pass-word level3
PS3
Level 3 Password (OEM), 0= disabled; choose a secure number, e.g. 735
Cabinet Light Control
Source
CLC
Cabinet light management
Lig: button only”
Ldo: door (and button if defined) only
LEC: Economy (and button if defined) only
Light off delay
Lod
Light off delay [sec] after door has been closed
ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST
49
ERC menu
code
Description
Service
SEr
Service
DI
Sdi
DI: physcial DI pin state (ON; OFF)
Voltage value
uAC
Current main power supply voltage
DOs Status
ouS
Current relay open / closed status.
IIII = All Relay on (Upper bar for on, Lower bar for off )
II = DO1 On, DO2 Off, DO3 & DO4 NA (No bar if relay not mounted)
IIII = All Relay off (Upper bar for on, Lower bar for off )
Relay 1 counter
rL1
Thousands of cycles of compressor relay since manufacture
Relay 2 counter
rL2
Thousands of cycles of no.2 relay since manufacture
Relay 3 counter
rL3
Thousands of cycles of no. 3 relay since manufacture
Relay 4 counter
rL4
Thousands of cycles of no. 4 relay since manufacture
interval Counter
int
Compressor run time since last defrost
Defrost time counter
dnt
Duration of last defrost cycle [min]
Door open counter
ont
ont/100 = Number of door openings since last reset
Serial numbe
Snu
Serial number given at manufacturing
SW version
Fir
Danfoss software version number
HW version
HAr
Danfoss hardware version number
OrderNoLow
OnL
Danfoss order code number
OrderNoHigh
OnH
Danfoss order code number
Parameter version
PAr
OEM parameter version number [requires EKA copy key update]
Last change
CHA
Not used
Manufacturing date
CHd
Programme date WWY: week number and year number (2010-19)
Copy Key ID
Cid
Copy key used for last program
Set as Default
SFC
Resets all parameters to last good OEM settings
50
ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST
APPENDIX II: CODE NUMBERS AND LENGHTS
Code no. I-Pack
Type
Approvals
230V, CQC/UL/CE
GDM-front
Code no. I-Pack
Type
Approvals
230V, CQC/UL/CE
Defrost sensors*
ERC 102C RED LED without buzzer
080G3102
PVC Standard (C2), 470 mm, 2-pole
077F8780
ERC 102D RED LED without buzzer
080G3103
PVC Standard (C2), 1000 mm, 2-pole
077F8786
ERC 102C BLUE LED without buzzer
080G3106
PVC Standard (C2), 1500 mm, 2-pole
077F8790
ERC 102D BLUE LED without buzzer
080G3107
PVC Standard (C2), 2000 mm, 2-pole
077F8794
PVC Standard (C2), 3000 mm, 2-pole
077F8798
PVC Standard (C3), 470 mm, 3-pole
077F8750
CFF-front
ERC 102C RED LED with buzzer
080G3113
PVC Standard (C3), 1000 mm, 3-pole
077F8756
ERC 102D RED LED with buzzer
080G3112
PVC Standard (C3), 1500 mm, 3-pole
077F8760
ERC 102C BLUE LED with buzzer
080G3116
PVC Standard (C3), 2000 mm, 3-pole
077F8764
ERC 102D BLUE LED with buzzer
080G3117
PVC Standard (C3), 2200 mm, 3-pole
077F8766
PVC Standard (C3), 3000 mm, 3-pole
077F8768
Light-sensors
Light sensor, 1000 mm (C3), 3-pole
080G3311
Other sensors
Light sensor, 2000 mm (C3), 3-pole
080G3313
TPFE low temp (C1), 1000 mm, 3-pole
077F8657
Light sensor, 3000 mm (C3), 3-pole
080G3315
TPFE low temp (C1), 2000 mm, 3-pole
077F8665
TPE precision (C1), 500 mm, 3-pole
077F8724
TPE precision (C1), 1000 mm, 3-pole
077F8725
Door-sensors
Door-sensor, 1000 mm (C4), 3-pole
080G3332
TPE precision (C1), 1500 mm, 3-pole
077F8726
Door-sensor, 2000 mm (C4), 3-pole
080G3334
TPE precision (C1), 2000 mm, 3-pole
077F8727
Door-sensor, 3000 mm (C4), 3-pole
080G3336
TPE precision (C1), 2500 mm, 3-pole
077F8728
TPE precision (C1), 3000 mm, 3-pole
077F8729
Temperature sensors
PVC Standard (C1), 470 mm, 3-pole
077F8751
Clamps
PVC Standard (C1), 1000 mm, 3-pole
077F8757
Black (2 needed per controller)
PVC Standard (C1), 1500 mm, 3-pole
077F8761
PVC Standard (C1), 2000 mm, 3-pole
077F8765
PVC Standard (C1), 2200 mm, 3-pole
077F8767
PVC Standard (C1), 3000 mm, 3-pole
077F8769
Note: For more information about temperature sensor types and connectors, please refer to Danfoss’
technical brochure “NTC type temperature sensors
for ETC & ERC controllers”
080G3308
Programming
OEM Docking station, production line
080G9701
Gateway incl USB Cable, R&D
080G9711
Copy Stick EKA-183A
080G9740
C: connector type
* Defrost sensors can also be used as condenser
sensors. .
ERC 102 Reference manual – APPENDIX II: CODE NUMBERS AND LENGHTS
51
APPENDIX III: TROUBLESHOOTING
Problem
Probable cause
Remedy
Compressor does not start
Waiting for compressor delay timer
Check CoP->CSt
Defrost in progress
Check CoP ->Pot /Pod
Line voltage to compressor too low
or too high
Check dEF ->dit, dot
Check CoP->uLi, uLo, uHi
Fan does not start
Door is open or door contact is defective
Fan stops when door is opened
Check that door contact is ok
Defrost does not start
Controller in pull-down mode
Defrost might be delayed during pull-down
Check parameter Pud->Pdi
Alarm does not sound
Alarm delayed
Check ALA->Htd, Abd
Check Pud->Pdd
Display brightness is weak
Ambient light sensor broken
Replace sensor
Shift between Eco and Normal mode does
not happen on ambient light change
Ambient light sensor broken
or light level not set properly
Check Eng->SLd, SLn
E01, E02 or E03 is shown on display
E01: Sensor S1 defective
Replace sensor
E02: Sensor S2 defective
E03: Sensor S3 defective
Display alternates between Con and
temperature
Condenser too hot
Clean condenser
Check Con ->CAL, CbL
Display alternates between Hi and
temperature
Temperature too high
Check ALA->HAt
Display alternates between Lo and
temperature
Temperature too low
Check ALA -> LAt
Display shows dEf
Defrost in progress
Check diS ->SdF
52
ERC 102 Reference manual – APPENDIX III: TROUBLE SHOOTING
APPENDIX IV: TYPICAL APPLICATIONS – WIRING DIAGRAMS
IV.1 ERC 102D
Glass Door Merchandiser
No-frost freezer / sub-zero cooler
100 – 240VAC SMPS
L
N
1
DO1
2
3
Lights
Fan
Compressor
Defrost Heater
ERC 102C
3 relays
4
DO2
5
6
DO3
AI/DI’s
Red LED without buzzer
080G3101
Blue LED without buzzer
080G3106
ERC102D
Controller
DO’s
DO4
D(S1)
C(S2)
B(S3)
A(di)
LL
Temperature Sensor for Cabinet Temperature Control
Temperature Sensor for
Evaporator Temperature
Control
Ambient Light
Door input
PVC Standard
Connector type (C1) 3-pole
PVC Standard
Connector type (C2) 2-pole
Light sensor
Connector type (C3) 3-pole
Door-sensor cable
Connector type (C4) 3-pole
470 mm
1000 mm
1500 mm
2000 mm
2200 mm
3000 mm
077F8751
077F8757
077F8761
077F8765
077F8767
077F8769
470 mm
1000 mm
1500 mm
2000 mm
3000 mm
077F8780
077F8786
077F8790
077F8794
077F8798
1000 mm
2000 mm
3000 mm
080G3311
080G3313
080G3315
1000 mm
2000 mm
3000 mm
080G3332
080G3334
080G3336
ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS
53
IV.2 ERC 102C
Glass Door Merchandiser
100 – 240VAC SMPS
N
ERC 102C Controller
Compressor
Fan
Lights
L
1
DO1
2
3
4
DO2
AI/DI’s
5
Red LED without buzzer
080G3102
Blue LED without buzzer
080G3106
ERC102C
Controller
DO’s
DO3
D(S1)
C(S2)
B(S3)
A(di)
LL
Temperature Sensor for Cabinet Temperature Control
Temperature Sensor for
Evaporator Temperature
Control
Ambient Light
Door input
PVC Standard
Connector type (C1) 3-pole
PVC Standard
Connector type (C2) 2-pole
Light sensor
Connector type (C3) 3-pole
Door-sensor cable
Connector type (C4) 3-pole
470 mm
1000 mm
1500 mm
2000 mm
2200 mm
3000 mm
54
077F8751
077F8757
077F8761
077F8765
077F8767
077F8769
470 mm
1000 mm
1500 mm
2000 mm
3000 mm
077F8780
077F8786
077F8790
077F8794
077F8798
1000 mm
2000 mm
3000 mm
ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS
080G3311
080G3313
080G3315
1000 mm
2000 mm
3000 mm
080G3332
080G3334
080G3336
IV.3 ERC 102D
Gastro No-frost freezer
ERC 102D Controller
100 – 240VAC SMPS
DO1
2
3
Fan
Compressor
1
4
DO2
5
080G3103
Blue LED without buzzer
080G3107
6
DO3
AI/DI’s
Red LED without buzzer
Lights
N
Defrost Heater
L
DO’s
ERC102D
Controller
DO4
D(S1)
C(S2)
B(S3)
A(di)
Temperature Sensor for Cabinet Temperature Control
Temperature Sensor for
Evaporator Temperature
Control
Temperature Sensor for Condenser Temperature Control
Door input
PVC Standard
Connector type (C1) 3-pole
PVC Standard
Connector type (C2) 2-pole
PVC Standard
Connector type (C3) 3-pole
Door-sensor cable
Connector type (C4) 3-pole
470 mm
1000 mm
1500 mm
2000 mm
2200 mm
3000 mm
077F8751
077F8757
077F8761
077F8765
077F8767
077F8769
470 mm
1000 mm
1500 mm
2000 mm
3000 mm
077F8780
077F8786
077F8790
077F8794
077F8798
470 mm
1000 mm
1500 mm
2000 mm
2200 mm
3000 mm
077F8750
077F8756
077F8760
077F8764
077F8766
077F8768
1000 mm
2000 mm
3000 mm
080G3332
080G3334
080G3336
ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS
55
IV.4 ERC 102C
Gastro Cooler
100 – 240VAC SMPS
Fan
Compressor
1
DO1
2
ERC 102C Controller
N
3
Red LED without buzzer
080G3102
Blue LED without buzzer
080G3106
Lights
L
4
DO2
AI/DI’s
5
ERC102C
Controller
DO’s
DO3
D(S1)
C(S2)
B(S3)
A(di)
Temperature Sensor for Cabinet Temperature Control
Temperature Sensor for
Evaporator Temperature
Control
Temperature Sensor for Condenser Temperature Control
Door input
PVC Standard
Connector type (C1) 3-pole
PVC Standard
Connector type (C2) 2-pole
PVC Standard
Connector type (C3) 3-pole
Door-sensor cable
Connector type (C4) 3-pole
470 mm
1000 mm
1500 mm
2000 mm
2200 mm
3000 mm
077F8751
077F8757
077F8761
077F8765
077F8767
077F8769
470 mm
1000 mm
1500 mm
2000 mm
3000 mm
077F8780
077F8786
077F8790
077F8794
077F8798
470 mm
1000 mm
1500 mm
2000 mm
2200 mm
3000 mm
077F8750
077F8756
077F8760
077F8764
077F8766
077F8768
1000 mm
2000 mm
3000 mm
080G3332
080G3334
080G3336
Note: This is a typical (default) wiring diagram since both inputs(AI/DI’s) and outputs (DO’s) can be assigned
differently. Please see manual for further details, folder “ASi”, Assignment.
56
ERC 102 Reference manual – 8 TYPICAL APPLICATIONS – WIRING DIAGRAMS
APPENDIX V: APPLICATION SPECIFICATON
V.1 Control sensor
The control sensor must always be connected and
is used for controlling the cut-in and cut-out of the
compressor according to the set-point. The sensor is
also used for the displayed temperature.
Placement of sensor:
Vertical coolers with fan
Most common placement is in the return air to the
evaporator. The sensor can be placed close to the
fan – even when the fan is pulsed during compressor off periods: The updating of the temperature is
blocked when the fan is stopped and only updated
when the fan has been running for a while, so that
the heat from the fan does not affect the temperature reading.
For applications sensitive to sub-zero temperatures,
sensor placement in the evaporator outlet air can be
considered.
Vertical freezers with fan
Placement in the return air or in the freezer
compartment
Coolers without fan
the best results are normally obtained when the
sensor is placed at the side-wall, 10 cm from the
back and approximately at 1/3 from the bottom or
where the evaporator ends.
The control sensor must always be connected and
is used for controlling the cut-in and cut-out of the
compressor according to the set-point. The sensor is
also used for the displayed temperature.
ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION
57
V.2 Evaporator sensor
The evaporator sensor is only used for de-icing of
the evaporator and has no control purpose.
Placement of sensor:
Place the sensor where the ice melts last.
Please be aware of that sharp finns can damage the
cable.
V.3 Condenser sensor
The condenser sensor is used to protect the compressor against high pressure when the condenser is
blocked or the condenser fan fails.
Placement of sensor:
Place the sensor at the liquid side of the condenser.
Use a metal bracket or metal tape to ensure good
thermal conductivity. Be sure that the cable does not
pass hot spots at the compressor or condenser that
exceeds 80°C.
58
ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION
V.4 Ambient light sensor
The ambient light sensor is used to detect opening
hours of the shop.
Placement of sensor:
The sensor must be placed so that the interior light
does not affect the sensor.
Possible placement could be in the front of the
cooler or at the top.
V.5 Door sensor
The door sensor is used to detect buying activity and
to stop the fan when the door is opened.
Danfoss does not supply the door-switch. Use the
door-switch you have and connect it to the cable
supplied by Danfoss.
ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION
59
ERC102 Application Matrix
Application
ERC type
Output
DO1
DO2
DO3
Input
DO4
S1 (C1)
S2 (C2)
S3 (C3)
Di (C4)
Control
Defrost
Condenser or
Ambient Light
Door
Standard Beverage
cooler
ERC102C
Comp
Fan
Lamp
Sub-zero beverage
cooler
ERC102D
Comp
Heater
Fan
Lamp
Control
Defrost
Condenser or
Ambient Light
Door
Out-door beverage
cooler
ERC102D
Comp
Heater
Fan
Lamp
Control
Condenser
Ambient Light
Door
Nofrost freezer w.
glassdoor
ERC102D
Comp
Heater
Fan
Lamp
Control
Evaporator
Condenser or
Ambient Light
Door
CFF Refrigerator
ERC102C
Comp
Fan
Lamp
Control
Defrost
Condenser
Door
CFF Freezer
ERC102D
Comp
Heater
Fan
Control
Defrost
Condenser
Door
Lamp
C: connector type
NOTE:
• Select only one function per input, e.g. condenser sensor or ambient light sensor.
• Make sure that the accessory you select has a matching connector to the input, e.g. a sensor for input S2 must
have C2 connector.
• Condenser sensor or light sensor are optional and can be omitted.
• Defrost sensor is mandatory when electrical heater is used for defrost. For natural defrost it can be omitted.
DKRCC.ES.RL0.A9.02 / 520H8849
Copyright Danfoss A/S
www.danfoss.com – 08/2014

Danfoss серия ERC — холодильные контроллеры Danfoss | Управление Холодом

  • Холодильное оборудование
  • Контроллеры

Danfoss

Контроллер температуры ERC 102
Контроллер температуры ERC 102

4 491,26 P / шт
с НДС актуально на 14.07.23
цена не является публичной офертой.

гарантия производителя 1 год

Артикул 080G3181
id товара 15602
Страна Китай Китай
Минимальный заказ 1 шт
В наличии на складах 9 шт

Выберите город доставки: Москва
Выберите способ доставки:
Деловые линии
Самовывоз

Склад В наличии на складе Цена за ед. без доставки Цена доставки Срок доставки, дней Сколько нужно, шт Стоимость с доставкой
Москва10 1 шт 4491,26P загрузка загрузка загрузка

Общее описание

Контроллер ERC 102 оснащен 3 аналоговыми и 1 цифровым входами и 3 выходами. Он особенно подходит для ОЕМ клиентов, так как время, простая и надежная установка и высокое качество важны наряду с гибкостью. Дисплей может быть красным или синим. Контроллер доступен с верхней левой кнопкой «ECO» или «Оттайка». Нижняя левая кнопка может быть «Свет», «Отключение» или «Ускоренное охлаждение». Большой диапазон совместимых типов датчиков и клеммы винтового соединения обеспечивают высокую гибкость при установке. Модульная система разъёмов для ОЕМ-клиентов с опциональным адаптером с винтовыми клеммами. Тип входного разъёма- Rast 2.5 Edge. Тип выходного разъёма- Rast 5 Standard.

Читать далее…

Видео

Технические
характеристикиЧертежи
и схемыДополнительная
информацияКомплектующие
 

Характеристика

Производитель Danfoss
Марка Adap-Kool
Назначение Для торговой мебели и камер
Количество релейных выходов 3
Напряжение питания 90 — 240 V
Описание Красный дисплей, 100..240 В, без звук. сигнализации

Чертежи

Габаритный чертеж контроллеров Danfoss серии ERC 112
Габаритный чертеж контроллеров Danfoss серии ERC 112
Подключения контроллеров Danfoss серии ERC 112D
Подключения контроллеров Danfoss серии ERC 112D

Дополнительная информация

Описание, технические характеристики, руководство пользователя контроллеров Danfoss серии ERC 112 (4.28Mb)

Рекламный проспект по контроллерам Danfoss серии ERC 112 (0.30Mb)

Общий каталог Danfoss (16.06Mb)

Полезные ссылки

Сайт производителя Danfoss

Вам также может понадобиться

Датчик температуры AKS 12

Danfoss

Датчик температуры AKS 12

  • Артикул: 084N0036
  • Страна: Дания Дания
  • В наличии: много

Датчик температуры воздуха со средним диапазоном рабочих температур и средним временем задержки.Датчик основан на платиновом чувствительном элементе с сопротивлением 1000 Ом при 0 °C.Температурный диапазон: -40 — +80 °C.Класс защиты: IP 67подключения: ПВХ кабель, 2 х 0,22 мм2.датчики настроены и соответствуют требованиям DIN IEC 751, класс B.

Датчик температуры EKS 111 (-55...80C) 1,5m

Danfoss

Датчик температуры EKS 111 (-55…80C) 1,5m

  • Артикул: 084N1161
  • Страна: Италия Италия
  • В наличии: 1 шт

Датчик основан на PTC-элементе с сопротивлением 1000 Ом при 25 °C Датчик может быть использован для измерения температуры в следующих областях: охлаждение, кондиционер, отопление. В первую очередь в сочетании с типами контроллеров ЕКС 101, ЕКС 201 и ЕКС 301. Датчик имеет относительно большой допуск на сопротивление. Это означает, что датчик не может быть используются для измерения значения, используемые для производства продуктов питания журнала безопасности или регулирование перегрева.

Датчик температуры EKS 211 (-40...80C) 1,5m

Danfoss

Датчик температуры EKS 211 (-40…80C) 1,5m

  • Артикул: 084B4403
  • Страна: Индонезия Индонезия
  • В наличии: много

Датчик может быть использован для измерения температуры в следующих областях: охлаждение, кондиционер, отопление.

Датчик температуры AKS 11 Pt1000

Danfoss

Датчик температуры AKS 11 Pt1000

  • Артикул: 084N0005
  • Страна: Дания Дания
  • В наличии: нет

Датчики накладные и погружные.Датчиков настроены и соответствуют требованиям DIN IEC 751, класс В.Температурный диапазон: -50 — +100 °C.Степень защиты: IP 67.Подключения: ПВХ кабель, 2 х 0,2 мм2

Вам также может понадобиться

  1. 16.07.2014, 19:22


    #1

    slawenti3 вне форума


    Новичок


    По умолчанию Danfoss ERC 102C

    Кто сталкивался с DANFOSS ERC 102C,как он в работе и программирование не совсем понятно,как-то мудрено по сравнению с Eliwel или EVK


  2. 16.07.2014, 19:24


    #2

    muravei77 вне форума


    сервисник

    Аватар для muravei77


    По умолчанию

    Если масла нету в репе, то и в тумбочке не будет… )


  3. 16.07.2014, 19:48


    #3

    egoiste вне форума


    Эксплуататор 2х ZR620

    Аватар для egoiste


    По умолчанию

    Цитата Сообщение от slawenti3
    Посмотреть сообщение

    Кто сталкивался с DANFOSS ERC 102C,как он в работе и программирование не совсем понятно,как-то мудрено по сравнению с Eliwel или EVK

    Норм все)


  4. 16.07.2014, 22:54


    #4

    Bub вне форума


    Мастер

    Аватар для Bub


    По умолчанию

    Чем мудренее, тем меньше рукосуев! Нормальный блок, не хуже не лучше.


  5. 16.07.2014, 23:06


    #5

    muravei77 вне форума


    сервисник

    Аватар для muravei77


    По умолчанию

    Если масла нету в репе, то и в тумбочке не будет… )


  6. 18.07.2014, 11:09


    #6

    Valter вне форума


    Мастер

    Аватар для Valter


    По умолчанию

    Цитата Сообщение от slawenti3
    Посмотреть сообщение

    как-то мудрено

    К аббревиатурам привык?


  7. 20.07.2014, 20:30


    #7

    slawenti3 вне форума


    Новичок



  8. 11.08.2014, 17:46


    #8

    алекс7711 вне форума


    Новичок


    По умолчанию

    Так все же какой код для входа в параметры компресора?


  9. 29.04.2015, 10:44


    #9

    YetiOdessa вне форума


    Заблокирован


    Последний раз редактировалось YetiOdessa; 29.04.2015 в 11:02.


  10. 29.04.2015, 11:12


    #10

    Smag вне форума


    Мастер


    По умолчанию

    Стр. 25 инструкции

    Некоторые параметры могут быть скрыты для Вас.
    Доступные параметры предварительно определены с помощью программы KoolProg. Ваш уровень доступа будет определять, какие параметры вы можете просматривать и редактировать.

    Скорее всего, конфигурация кнопок убрана на 3-й уровень (ОЕМ) и без пароля 3-го уровня или софта её не выставишь.


  11. 22.07.2015, 15:44


    #11

    Евгений10 вне форума


    Пользователь


    По умолчанию

    [QUOTE=slawenti3;324836]Кто сталкивался с DANFOSS ERC 102C,как он в работе и программирование не совсем понятно,как-то мудрено по сравнению с Eliwel или EVK[/QUOT
    ничего мудрёного в них нет ничем не отличается от EKC только корпусом а так всё тоже самое в инструкции всё описано как и что


  12. 23.05.2020, 07:03


    #12

    Сергей Р вне форума


    Мастер


    По умолчанию

    У кого есть инструкция на ЕКС 102С, не могу найти в сетях. Если есть скиньте, нужно срочно. 80286392-e0df-4ed9-b942-6df69e86df38.jpg


  13. 23.05.2020, 08:25


    #13

    mihail97 на форуме


    Мастер


    По умолчанию

    Цитата Сообщение от Сергей Р
    Посмотреть сообщение

    У кого есть инструкция на ЕКС 102С,

    Есть ERC 102Х-универсальная, но почему то не закружается

    Последний раз редактировалось mihail97; 23.05.2020 в 08:38.


  14. 23.05.2020, 08:40


    #14

    mihail97 на форуме


    Мастер


    По умолчанию


  15. 23.05.2020, 09:06


    #15

    mihail97 на форуме


    Мастер


    По умолчанию


  16. 23.05.2020, 09:09


    #16

    mihail97 на форуме


    Мастер


    По умолчанию

    Ещё…., но третью страницу не грузит


  17. 23.05.2020, 11:40


    #17

    Сергей Р вне форума


    Мастер


    По умолчанию


Похожие темы

  1. Ответов: 2

    Последнее сообщение: 17.03.2019, 15:55

  2. Ответов: 3

    Последнее сообщение: 13.01.2018, 21:54

  3. Ответов: 11

    Последнее сообщение: 19.04.2014, 18:20

  4. Ответов: 32

    Последнее сообщение: 10.11.2011, 23:42

Социальные закладки

Социальные закладки
  • Отправить на Google

    Google


Ваши права

  • Вы не можете создавать новые темы
  • Вы не можете отвечать в темах
  • Вы не можете прикреплять вложения
  • Вы не можете редактировать свои сообщения
  •  
  • BB коды Вкл.
  • Смайлы Вкл.
  • [IMG] код Вкл.
  • [VIDEO] код Вкл.
  • HTML код Выкл.

Правила форума

Понравилась статья? Поделить с друзьями:
  • Контроллер elstat ems25 инструкция на русском
  • Контроллер eliwell extu pro rx tx инструкция
  • Контроллер eliwell 974 id plus инструкция по применению
  • Контроллер elitech etc 974 инструкция на русском языке
  • Контроллер elitech etc 961 инструкция на русском языке