-
Contents
-
Table of Contents
-
Troubleshooting
-
Bookmarks
Quick Links
Installation and Service
Instructions
AUTOMATIC
11.15am 71°F
180
Boiler Controls
Logamatic 2107
For the installing contractor
Please read carefully prior
to commissioning or
servicing.
Related Manuals for Buderus Logamatic 2107
Summary of Contents for Buderus Logamatic 2107
-
Page 1
Installation and Service Instructions AUTOMATIC 11.15am 71°F Boiler Controls For the installing contractor Logamatic 2107 Please read carefully prior to commissioning or servicing. -
Page 2
Change to SETBACK if no room sensor is being used or RMSETBACK if a room sensor is present Refer to page 10 for additional details. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 3: Table Of Contents
….. . . 46 Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 4
……….. . 68 Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 5: Safety Instructions And User Notes
USER NOTE User notes help you use and handle this technology in the optimum, most economical, safe and environmentally- friendly manner. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 6: Please Observe These Safety Instructions
RISK TO LIFE z In an emergency, switch OFF the emergency shutoff switch outside the WARNING! boiler room. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 7: Setting Parameters And Display Data For The Logamatic 2107
MAX TEMP Maximum heating circuit temperature REMOTE 2 Remote control ON/OFF DIFF T Room temperature hook-up OA SETBACK Type of setback OFFSET Room temperature offset Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 8
6 Only if FM 241 module is installed and if heating circuit 2 is selected as an «UND-FLOOR» or «RADIATOR» heating system. 7 Only if FM 244 module is installed. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 9: Installation
G234: The tridicator assembly should be moved to the supply piping and replaced with the chrome plated Logamatic well. The sensor bundle must be inserted into this well. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 10
Tilt the display to the desired position. z Replace the top housing of the controls and fasten the two screws. The control is ready to be placed into operation. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 11: Installation Of The Logabracket
GA124, GA244 These boilers do not require the bracket as strain relief connections are provided on the rear of the boiler. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 12: Logamatic 2107 Controls
Item 5: ON/OFF switch Item 6: Keys for basic functions Item 7: Dial Item 8: Keys for extended functions Item 9: Display Item 10: Flap Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 13
Item 1: Automatic mode following a program Item 2: Normal heating mode (day mode) Item 3: Flue gas test (for measuring flue gases) Item 4: Setback heating mode (night mode) Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 14
Item 11: «Display» key – Select the standard display This keypad is used, for example, to enter the day, set the time, select temperature values, etc. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 15: Checking The Manual Reset High Limit (Stb)
Release the «Display» key. °F z Remove the dial on the boiler water thermostat (Fig. 4). Fig. 4 Remove the dial on the boiler aquastat. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 16
(Fig. 6). 1…7 Zeit Temp PROG Urlaub Auswahl So/Wi Anzeige Install Zurück Fig. 6 Remove the STB cover. Item 1: STB cover. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 17: Using The Service Level
The service level is now activated. USER NOTE The unit automatically returns to the standard display if no settings are made within 5 minutes. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 18: Calling Up The Menu
REMOTE Press the «ENTER» key to return to the higher-level menu. CIRCUIT 1 PERIM HTG Press the «AUT» key to exit the service level. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 19: Modifying Settings
Return to the standard display Press «ENTER». The unit automatically returns to the standard display if no key is pressed within 5 minutes. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 20: General Data
5 second pause, then the mixing valves are set to «OPEN» for 3 minutes. All pumps then return to normal operation. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 21: System Frost Protection
The setting applies to all heating circuits. Input range Factory setting System frost protection -4°F – 50°F (-20°C – 10°C) 41°F (5°C) Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 22: Type Of Building
Note: In areas where rapid changes in outdoor temperature occur, choose Building Response 1. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 23
Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting 1 (low) Building response 2 (medium) 3 (high) Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 24: Setting The Burner Type
Press «ENTER» to return to the next higher level. Input range Factory setting Burner system without burner module FM 242 – 1-stage Burner system with burner module FM 242 1-stage/2-stage/modulating 2-stage Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 25: Minimum Modulating Output Of The Modulating Burner
Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting 10 %–60 % 30 % minimum modulation output Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 26: Operating Time Of The Modulating Burner Actuator
Press «ENTER» to return to the next higher level. Input range Factory setting Operating time of the actuator 5 – 60 seconds 12 seconds Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 27: Pump Logic
Press «ENTER» to return to the next higher level. Input range Factory setting Pump logic for 104°F (40°C) 1-stage 60°F – 140°F 113°F (45°C) 2-stage (15°C – 60°C) 122°F (50°C) Modulating burners Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 28: Maximum Boiler Temperature
Input range Factory setting 158°F – 210°F Maximum OFF temperature 176°F (80°C) (70°C – 99°C) Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 29: Language Selection
«AMERICAN». Now hold down the «Display» key and turn the dial to set the language. Release the «Display» key to store the set language. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 30: Heating Circuit Data
If the right heating system is selected, the other heating circuit parameters are preset. They must still be verified, however. Further information on this can be found on the next page. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 31
If there is only one heating circuit with mixing valve present (HK2), circuit 1 must be set to «NO SYSTEM». If the «NO SYSTEM» setting is used, all of the following settings are hidden for this circuit. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 32
FLOOR HTG Input range Factory setting NO SYSTEM PERIM HTG Heating circuit 1 PERIM HTG NO SYSTEM Heating circuit 2 FLOOR HTG FLOOR HTG Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 33: Reference Design Temperature
(+20) (+15) (+10) (+5) (±0) (-5) (-10) (-15) The factory setting is: Outdoor temperature [°F(°C)] With PERIM HTG: 167°F (75°C) Fig. 9 Determining the heating With FLOOR HTG: 113°F (45°C) curve Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 34
Reference design temperature for PERIM HTG 86 – 194°F (30 – 90°C) 167°F (75°C) Reference design temperature for FLOOR HTG 86 – 140°F (30 – 60°C) 113°F (45°C) Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 35: Dhw Priority
(in this case «OFF»). DHW PRIOR Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting DHW priority Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 36: Maximum Heating Circuit Temperature
68 – 140°F (20°C – 60°C) 122°F (50°C) FLOOR HTG *) *) This function does not replace the safety thermostat for switching of the pump for radiant heating circuit. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 37: Remote Control On/Off
Release «Display» to store your input. Press «ENTER» to return to the next higher level. Further information on this can be found on the next page. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 38
All settings can then only be made via the remote control. Input range Factory setting Remote control Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 39: Maximum Room Temperature Compensation
This setting is generally recommended for FLOOR HTG systems. The factory setting is: With FLOOR HTG system: 6°F (3°C) Further information on this can be found on the next page. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 40
Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting Differential temperature 6°F (3°C) 2 – 18°F (1°C – 10°C) Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 41: Setback Mode Selection
Heating circuit with constant circulation zone: RMSETBACK (Requires room sensor) Heating circuit with ONlOFF thermostats: SETBACK (No room sensor present) Commercial (day use only) buildings: OASETBACK Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 42
Press «ENTER» to return to the next higher level. Input range Factory setting Outdoor setback Room setback Type of setback Outdoor setback Setback Boiler off Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 43: Room Temperature Offset
Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting OFFSET -9 – +9°F (-5°C – +5°C) 0°F (0°C) Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 44: Solar Data
(in this case «SLRFN OFF»). SLRFN OFF Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting SOLAR Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 45: Maximum Storage Tank Temperature In Solar Mode
«MAX-SL SR» setting in order to prevent the tank scaling up. Input range Factory setting Max sol T 140 – 194°F (60°C – 90°C) 167°F (75°C) Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 46: Minimum Storage Tank Temperature In Solar Mode
Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting 86 – 130°F (30°C – 54°C) MIN SL SR Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 47: Dhw Production On/Off
(in this case «OFF»). DHW PROD Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting DHW production Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 48: Dhw Recirculation Pump
The intermittent mode may be set to 1 to 6 pump starts per hour in order to minimize the operating costs of the recirculation pump. This setting saves energy while ensuring comfort. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 49
(in this case «4»). RECIRCPUMP Release «Display» to store your input. Press «ENTER» to return to the next higher level. Input range Factory setting DHW recirculation pump Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 50: Heating Curve
50°F (+10°C), the second at 32°F (±0°C) and the third at 14°F (-10°C). HTG CURVE °F HTG CURVE °F HTG CURVE °F Release the «Display» key to return to the next higher level. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 51: Running The Relay Test
Boiler system pump HK1 z Heating circuit pump HK 2 z Mix valve open/closed/OFF z Tank DHW pump z DHW recirculation pump z Solar pump Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 52
Press «ENTER» to return to the next higher level. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 53: Performing An Lcd Test
Hold down «Display» and turn the dial. All the numbers and symbols must appear on the display. °F°C Release the «Display» key. 1234567 Press «ENTER» to return to the next higher level. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 54: Time, Correcting The Accuracy
Release «ENTER» to store your input. Press the «Display» key to return to the next higher level. Input range Factory setting -30 seconds/day – +30 seconds/day Time Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 55: Reset
No «RESET» is carried out if you release the «Display» key before all the numbers have disappeared. Press «ENTER» to return to the next higher level. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 56: Version Number
«AMERICAN» appears as the first main menu. Turn the dial until «VERSION» and the version number (in this case «3.24») are displayed. VERSION 3.24 Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 57: Sensor Curves
41 (5) 50 (10) 60 (15) 5 (-15) 14 (-10) 23 (-5) 32 (0) 41 (5) 50 (10) 60 (15) Outdoor temperature [°F (°C)] Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 58
Water temperature [°F (°C)] Collector sensor (FSK) -58 (-50) 32 (0) 122 (50) 212 (100) 302 (150) 392 (200) 482 (250) Collector temperature [°F (°C)] Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 59: Operating Values At The Service Level/Setup Report
Outdoor setback Room setback Setback type for heating circuit 2 Outdoor setback Setback Switch-off Further information on this can be found on the next page. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 60
167°F (75°C) MIN-SL SR 86 – 130°F (30°C – 54°C)/OFF DHW PROD ON/OFF DHW recirculation pump OFF/1/2/3/4/5/6/ON Time -30 seconds/day – +30 seconds/day 0 seconds/day Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 61: Troubleshooting
Check the wiring Remote control is defective available, so the ambient REMOTE2 ERROR Replace the remote control influence does not apply Connecting cable interrupted Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 62
Module no longer present Module is no longer being (solar card) Plug the module in again Module defective addressed Replace the module FM 244 ERROR Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 63: Troubleshooting «No Heat» Call
The differential is split above & below the current target temperature. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 64
11 to Hot on the burner (terminal 4 is the the burner is now low voltage between terminals 10 & 11 neutral). on the R2107 and TT (or RW) on the boiler aquastat. Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 65
Troubleshooting Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 66: Troubleshooting „Insufficent Heat» Call
With this type of a call, you will want to increase the OFFSET setting. USE THE QUICK REFERNECE GUIDE FOR INITIAL PROGRAMMING Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 67: Troubleshooting Domestic Hot Water
Check the following: 1 — bad circulator 2 — stuck flow check 3 — piping is air bound 4 — closed valve Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 68: Index
Type of setback ….41 Version number ….56 Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications.
-
Page 69
Notes Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 70
Notes Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 71
Notes Logamatic 2107 controls — We reserve the right to make any changes due to technical modifications. -
Page 72
United States and Canada Bosch Thermotechnology Corporation 50 Wentworth Avenue Londonderry, NH 03053 U.S.A. Tel. 603-552-1100 Fax 603-584-1681 www.buderus.net Products manufactured by Bosch Thermotechnik GmbH D-35573 Wetzlar www.buderus.de Bosch Thermotechnology Corporation reserves the right to make changes without notice due to continuing…
Installation and Service Instructions AUTOMATIC 11.15am 71°F T 180 160 AU 140 120 6 720 618 142 - 07/2014 US/CA Boiler Controls Logamatic 2107 For the installing contractor Please read carefully prior to commissioning or servicing. Production This product has been tested and is certified for both the US and Canadian markets and meets all applicable US and Canadian standards. No t ic e: T o m a t c h t h e t y p i c a l b u i l d i n g , t he f o ll o wi ng f ac t o r y settings may need adjustment: BLDG RESP: Change to 1 if typical 2x4 or 2x6 construction MAX TEMP: Change to 185-190°F if high temperature baseboard is used OASETBACK: Change to SETBACK if no room sensor is being used or RMSETBACK if a room sensor is present Refer to page 10 for additional details. 2 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Contents 1 Safety instructions and user notes . 1.1 1.2 1.3 1.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Key to symbols . . . . . . . . . . . . . . . . Intended use . . . . . . . . . . . . . . . . . . Safety instructions.. . . . . . . . . . . . . . Please observe these safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 2 Setting parameters and display data for the Logamatic 2107 . 3 Installation . . . . . . . . . .7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 3.1 Mounting of the Logamatic . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .9 4 Logamatic 2107 controls . 5 Checking the manual reset high limit (STB) 6 Using the service level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 . . . . . . . . . . . . . . . . . . . . . . . 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 6.1 Calling up the service level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 6.2 Calling up the menu . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . .. . . . . . 17 6.3 Modifying settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 7 General data 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 8 System frost protection . . . . . . . . . . . . . . . . . . . Type of building . . . . . . . . . . . . . . . . . . . . . . . . Setting the burner type . . . . . . . . . . . . . . . . . . . Minimum modulating output of the modulating burner Operating time of the modulating burner actuator . . . Pump logic . . . . . . . . . . . . . . . . . . . . . . . . . . . Maximum boiler temperature . . . . . . . . . . . . . . . . Language selection . . . . . . . . . . . . . . . . . . . . . Heating circuit data . 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 . . . . . . . . . . . . . . . . . . . . 21 . . . . . . . . . . . . . . . . . . . . 23 . . . . . . . . . . . . . . . . . . . . 24 . . . . . . . . . . . . . . . . . . . . 25 . . . . . . . . . . . . . . . . . . . . 26 . . . . . . . . . . . . . . . . . . . . 27 . . . . . . . . . . . . . . . . . . . . 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Heating system . . . . . . . . . . . . . . . . . . Reference design temperature . . . . . . . . DHW priority . . . . . . . . . . . . . . . . . . . . Maximum heating circuit temperature . . . . Remote control ON/OFF . . . . . . . . . . . . Maximum room temperature compensation Setback mode selection . . . . . . . . . . . . . Room temperature offset . . . . . . . . . . . . Solar data . . . . . . . . . . . . . . . . . . . . 20 . . . . . . . . . . . . . . . . . . . . . . . . . . 29 . . . . . . . . . . . . . . . . . . . . . . . . . . 32 . . . . . . . . . . . . . . . . . . . . . . . . . . 34 . . . .. . . . . . . . . . . . . . . . . . .. . . . 35 . . . . . . . . . . . . . . . . . . . . . . . . . . 36 . . . . . . . . . . . . . . . . . . . . . . . . . . 38 . . . . . . . . . . . . . . . . . . . . . . . . . . 40 . . . . . . . . . . . . . . . . . . . . . . . . . . 42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . .43 9.1 Solar function ON/OFF (with FM 244 only) . . .. . . . . . . . . . . . . . . . . . .. . . . . . 43 9.2 Maximum storage tank temperature in solar mode . . . . . . . . . . . . . . . . . . . . . . 44 9.3 Minimum storage tank temperature in solar mode . . . . . . . . . . . . . . . . . . . . . . . 45 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 3 Contents 10 DHW production ON/OFF . 11 DHW recirculation pump 12 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 13 Running the relay test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 14 Performing an LCD test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 15 Time, correcting the accuracy . 16 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 17 Version number . 18 Sensor curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 19 Operating values at the service level/setup report 20 Troubleshooting . . . . . . . . . . . . . . . . . 58 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 20.1 Troubleshooting "NO HEAT" call . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 20.2 Troubleshooting „INSUFFICENT HEAT“ call . . . . . . . . . . . . . . . . . . . . . . . . . 65 20.3 Troubleshooting Domestic Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 21 Wiring diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 67 69 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Safety instructions and user notes 1 Safety instructions and user notes 1.1 Key to symbols Warnings Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken. The following keywords are defined and can be used in this document: • DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. • WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. • CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury. • NOTICE is used to address practices not related to personal injury. Important information This symbol indicates important information where there is no risk to people or property. This chapter contains general safety instructions, which you should observe when installing and servicing the Logamatic 2107 controls. The other safety instructions that appear in other sections of these service instructions must also be followed exactly. The safety instructions always precede the individual tasks. Read the safety instructions carefully before carrying out the tasks described below. The result of ignoring safety instructions can be severe injury or even death, as well as damage to property and the environment. 1.1 Intended use Logamatic 2107 controls are used to control and monitor heating systems in detached and terraced houses. The Logamatic 2107 controls can be used to check and set the room and DHW temperatures and to select and set heating programs. 1.3 1 Safety instructions Read all instructions before installing. Perform the steps in the indicated sequence. Have the water heater inspected by a trained service technician at least once every year. Failure to comply with these instructions can result in severe, possibly fatal, personal injury as well as damage to property and equipment. Installation and servicing ▶ Risk of fire when soldering and brazing! Take appropriate protective measures when soldering and brazing around combustible and flammable material. ▶ Ensure that only a licensed contractor installs or services the water heater. ▶ On hot components use only material with adequate temperature stability. Installation and commissioning ▶ In the Commonwealth of Massachusetts, the water heater must be installed by a licensed plumber. ▶ Do not install this device in rooms with a high moisture level (e.g. bathrooms, saunas). Function ▶ To ensure that the water heater functions properly, follow these installation and maintenance instructions. ▶ Never close the blow-off line of the T&P safety valve. For safety reasons, water may escape during heating. DANGER: Electric shock! Shock hazard: line voltage is present. ▶ Before servicing the water heater, unplug power supply cord from outlet. Failure to do so could result in severe personal injury or death. WARNING: Damage to the appliance from over pressure. ▶ The heater must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures equal to or more than 0.5 psi. NOTICE: ▶ The appliance should be located in an area where leakage of the heater or connections will not result in damage to the area adjacent to the appliance or to lower floors of the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow. CAUTION: Personal injury and property damage. ▶ Appliance must be installed vertically. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 5 1 1.4 Safety instructions and user notes Please observe these safety instructions The Logamatic 2107 controls has been designed and built in accordance with currently recognized standards and safety requirements. However, property damage resulting from inappropriate handling of this device cannot be completely excluded. – Only operate the Logamatic 2107 controls for the intended purpose and when it is in perfect working order. – Carefully read these service instructions before starting any work on the controls. SYSTEM DAMAGE CAUTION! through inappropriate work on the system. z Only enter or change the operating values in accordance with the details shown in these instructions. Other inputs alter the control program of the heating system and can lead to incorrect system functions. Note the following safety instructions while using the Logamatic 2107 controls. RISK OF LIFE from electric shock. DANGER! z Prior to opening the controls, isolate the system from the mains supply via the boiler emergency shutoff switch or the heating system circuit breaker. z All tasks listed in these service instructions, which require the opening of the control panel, must only be carried out by trained personnel. SYSTEM DAMAGE through frost. NOTICE z Frost protection is only active if the controls is switched ON. Switch OFF the controls and drain the water from the boiler, the DHW tank and the pipes of the heating system. The system is only protected from frost, if it is completely dry. RISK TO LIFE WARNING! 6 z In an emergency, switch OFF the emergency shutoff switch outside the boiler room. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Setting parameters and display data for the Logamatic 2107 2 2 Setting parameters and display data for the Logamatic 2107 Press the "Display" key and "Install" key at the same time to call up the service level (see Chapter "Keys for extended functions", page 14). Display AMERICAN Language selection BOILER Boiler parameters FROST AO Freeze protection limit BUILDING Building response 1 2-STAGE Burner type1 MIN MOD2 Minimum modulation output2 TIME RUN2 Minimum burner run time2 PUMPLOGIC Pump logic threshold MAX TEMP Maximum boiler switch-off temperature CIRCUIT 01 Heating circuit 1 installation parameters (unmixed heating circuit) PERIM HTG Heating system REF TEMP Design temperature REMOTE 1 Remote control ON/OFF DIFF T3 Room temperature hook-up3 OA SETBACK Type of setback OFFSET Room temperature offset CIRCUIT 025 Heating circuit 2 installation parameters (mixed heating circuit)4 UND-FLOOR Heating system REF TEMP Design temperature DHW PR5 DHW priority5 MAX TEMP Maximum heating circuit temperature REMOTE 2 Remote control ON/OFF DIFF T3 Room temperature hook-up3 OA SETBACK Type of setback OFFSET Room temperature offset Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 7 2 Setting parameters and display data for the Logamatic 2107 Display SOLAR7 SLR FN ON Solar function ON/OFF MAX SL SR Maximum storage tank temperature in solar mode MIN SL SR Minimum storage tank temperature in solar mode DHW PROD Domestic hot water ON/OFF RECIRC PUMP5 DHW circulation pump5 HTG CURVE 1 Heating characteristic curve HK1 HTG CURVE 2 4 Heating characteristic curve HK24 RELAYS 1 2 3 4 5 6 7 8 Relay test BURNER (St.1) Burner relay stage 1 BURNER21, Burner relay1 stage 2, modulation output2 MOD22 HTG1 PUMP Heating circuit pump (HZ1 unmixed) HTG2 PUMP4 Heating circuit pump (HZ2 mixed)4 MIX VALVE4 Mixer4 DHW PUMP Tank DHW pump RECIR PUMP DHW circulation pump SLR PUMP7 Solar pump7 LCD TEST LCD test TIME Time, accuracy RESET Reset VERSION Version number Only if the FM 242 module is installed and 2-stage burner is selected. Only if the FM 242 module is installed and modulating burner is selected. Only if BFU remote control is installed. Only if the FM 241 module is installed. Only if DHW is installed. Only if FM 241 module is installed and if heating circuit 2 is selected as an "UND-FLOOR" or "RADIATOR" heating system. Only if FM 244 module is installed. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Installation 3 Installation 3.1 Mounting of the Logamatic 3 z On the GC144, GC124, G124X, GA124, G234X, G244, and G334X boilers remove the front panel of the boiler. z Remove rear top panel of the boiler by first unscrewing 2 screws at the rear edge, then sliding rear panel backward to disengage the hooks. z Remove the two screws at the top of the Logamatic, and lift up top cover. z Insert the two front feet of the control into the holes provided on the top of the boiler. Then, firmly push down on the rear of the control until it snaps into place. z Fasten the control to the boiler jacket using the two screws as shown. z The sensor bundle consists of one thermistor (FK), two capillaries and a spacer. Mount the sensors per the following boiler specific instructions. Use the chrome well supplied with the Logamatic. z G115, G125, GB125, G215, G315: Replace brass well with chrome Logamatic well. The sensor bundle must be fully inserted into the Logamatic well. z GC124, G124X, GA124, GA244, GA334X: Unwrap the sensor bundle. Remove spacers from the chrome well on the boiler. Remove outer sleeve from one capillary. Insert both capillaries and thermistor into the chrome well together with Honeywell capillary. z G234: The tridicator assembly should be moved to the supply piping and replaced with the chrome plated Logamatic well. The sensor bundle must be inserted into this well. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 9 3 Installation z Electrical connections must be made according to the wiring diagrams. z All the wires should be routed through the cable raceway at the rear of the boiler. The rear panel jacket may be modified per local code. Route the wires on top of the insulation from the back of the boiler to the back of the controls. z Use the white strain relief brackets provided to lock all cables into place on the back of the control. z Tilt the display to the desired position. z Replace the top housing of the controls and fasten the two screws. The control is ready to be placed into operation. 10 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Logamatic 2107 controls 4 4 Logamatic 2107 controls Introduction to the user interface of the Logamatic 2107 controls. 9 8 10 7 AUTOMATIC 11.15am 71 6 T 180 160 AU 0 120 14 T 180 160 AU 140 120 1 3 5 2 4 Fig. 1 Controls on the Logamatic 2107 controls Item 1: Manual reset high limit (STB) Item 2: Boiler water thermostat Item 3: Fuse (10 Amp) Item 4: Switch for Automatic mode, Emergency mode Item 5: ON/OFF switch Item 6: Keys for basic functions Item 7: Dial Item 8: Keys for extended functions Item 9: Display Item 10: Flap Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 11 4 Logamatic 2107 controls 4 Keys for basic functions You can control the basic functions using this keypad. 1 Fig. 2 2 3 4 Keypad for basic functions Item 1: Automatic mode following a program Item 2: Normal heating mode (day mode) Item 3: Flue gas test (for measuring flue gases) Item 4: Setback heating mode (night mode) 12 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Logamatic 2107 controls 4 Keys for extended functions This keypad is located behind the flap. 1 2 3 4 5 6 7 8 11 Fig. 3 10 9 Keypad for extended functions Item 1: "Weekday" key – Enter the day of the week Item 2: "Vacation" key - Set vacation function Item 3: "Time" key – Set the time Item 4: "PROG" key – Select program Item 5: "WWSD" key Item 6: "Temp" key – Select temperature values Item 7: "DHW" key – Enter the domestic hot water temperature Item 8: "Heating circuit" key – Call up the heating circuits Item 9: "Enter" key – Back to standard display Item 10: "Install" key – Call up the service level Item 11: "Display" key – Select the standard display This keypad is used, for example, to enter the day, set the time, select temperature values, etc. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 13 5 5 Checking the manual reset high limit (STB) 4 5 Checking the manual reset high limit (STB) USER NOTE Check the STB after the initial installation, and after every service. z Switch on the system. + z Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until "RELAY" is shown. RELAY Hold down the "Display" key and turn the dial, until "BURNER ON" appears in the display. The burner starts running. BURNER °F Release the "Display" key. ON 14 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Checking the manual reset high limit (STB) 5 z Remove the dial on the boiler water thermostat (Fig. 4). 180 T AU 16 0 140 120 Fig. 4 Remove the dial on the boiler aquastat. z Push the lever or key (depending on the type of STB) back with a screwdriver or similar device and hold until the high limit safety cut-out has triggered (Fig. 5). 1 2 Fig. 5 Triggering the manual reset high limit Item 1: Key Item 2: Lever Terminating or exiting the test Press "AUT". Reattach the dial and turn it to the "AUT" position. z To reset the manual reset high limit, remove the cover on the STB and press the reset button located beneath it (Fig. 6). 1...7 Tag Urlaub Anzeige 90 Zeit Temp PROG Auswahl So/Wi Install Zurück AUT 70 60 50 I 0 1 Fig. 6 Remove the STB cover. Item 1: STB cover. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 15 5 6 Using the service level 4 6 Using the service level Access to the service level is password protected. The service level must only be used by trained heating contractors. Unauthorized access invalidates your warranty. SYSTEM DAMAGE through inappropriate work on the system. NOTICE 6.1 z Only enter or change the operating values in accordance with the details shown in these instructions. Different values will change the heating system control programs and can cause the system to malfunction. Calling up the service level The controls marked in grey are used for this function. + AMERICAN You will need a pointed object, such as a ball-point pen, to press the "Install" button. Press the "Display" key and "Install" key at the same time to call up the service level. Release both keys. The selected language, e.g. "AMERICAN", is displayed in the first main menu. The service level is now activated. USER NOTE The unit automatically returns to the standard display if no settings are made within 5 minutes. 16 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Using the service level 6.2 6 Calling up the menu + Press the "Display" key and "Install" key at the same time to call up the service level. Release both keys. Once you have called up the service level, you can access all the setting options it contains. The service level is broken down into main menus and submenus. You can scroll through the main menu level by turning the dial. AMERICAN BOILER CIRCUIT 01 Press the "Display" key to access the submenu. CIRCUIT 1 PERIM HTG REF TEMP REMOTE Press the "ENTER" key to return to the higher-level menu. CIRCUIT 1 PERIM HTG Press the "AUT" key to exit the service level. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 17 5 6 Using the service level 4 6.3 4 Modifying settings + When you press the "Display" key in a submenu, the setting parameter to be changed flashes. Hold down the "Display" key and turn the dial at the same time to change the parameter. The new value will be stored after you release the "Display" key. Some parameters are only displayed if the relevant modules are installed (module FM 241– mixer, FM 242– 2-stage burner, FM 244 – solar module). The controls detects the modules and enables the parameters. Return to the standard display Press "ENTER". The unit automatically returns to the standard display if no key is pressed within 5 minutes. 18 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. General data 7 7 General data USER NOTE "PUMP KICK" In all operating modes, all the pumps are switched on and then off again for 10 seconds every Wednesday at 12 noon to prevent pump damage. This is followed by a brief 5 second pause, then the mixing valves are set to "OPEN" for 3 minutes. All pumps then return to normal operation. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 19 5 7 General data 4 7.1 System frost protection The controls is equipped with a system frost protection function. If the outdoor temperature drops beneath the frost protection limit, the heating system pump (contacts 61/63) will be started. The factory default for the frost protection limit is an outdoor temperature of 41°F (5°C). The setting applies to all heating circuits. Changing the system frost protection Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "BLR TEMP" is shown. Press "Display" to call up a submenu. "FREEZE TEMP" appears. FREEZE TEMP °F 41 Hold down the "Display" key and turn the dial until the desired value appears (in this case "41°F"). + FREEZE TEMP °F Release "Display" to store your input. 43 Press "ENTER" to return to the next higher level. USER NOTE The value of the "OASETBACK" setback type is also limited to the freeze protection limit. The setting applies to all heating circuits. System frost protection 20 Input range Factory setting -4°F – 50°F (-20°C – 10°C) 41°F (5°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. General data Type of building Outdoor temperature in °F (°C) 7.2 7 79 (26) 75 (24) 72 (22) 68 (20) 64 (18) 61 (16) 57 (14) 1 54 (12) 2 50 (10) 46 (8) 43 (6) 12am 3am 6am 9am 12pm 3pm 6pm 9 pm Time in hours Fig. 7 Thermal delay Item 1: Current outdoor temperature Item 2: Adjusted outdoor temperature The building type is used to take into account the heat storage capacity of the building's mass and the thermal inertia of the building compared to fluctuations in the outdoor temperature. The lighter the building and the thinner its insulation, the faster the controls will respond to changes in outdoor temperature (known as "adjusted outdoor temperature calculation"). It is the adjusted outdoor temperature value that is used for the warm weather shutdown (WWSD) and to calculate the supply temperature using the characteristic heating curve (Fig. 7). For building type three levels are available: – Building response 1 (low) Buildings with small heat storage capacity and low to medium levels of insulation, e.g. 2x4 wood frame or prefabricated construction with typical insulation. – Building response 2 (medium) Buildings with medium heat storage capacity and high levels of insulation, e.g. 2x6 wood frame or cinder block construction with above average insulation. – Building response 3 (high) Massive buildings with high heat storage capacity and high levels of insulation, e.g. poured concrete, heavy brick or heavy cinder block construction with excellent insulation. Note: In areas where rapid changes in outdoor temperature occur, choose Building Response 1. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 21 5 7 General data 4 Changing the type of building Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "BLR TEMP" is shown. Press "Display" to call up a submenu. "FREEZE TEMP" appears. Turn the dial until "BLDG RESP" is shown. BLDG RESP 2 Hold down the "Display" key and turn the dial until the required value appears (in this case "1"). + BLDG RESP Release "Display" to store your input. 1 Press "ENTER" to return to the next higher level. Building response 22 Input range Factory setting 1 (low) 2 (medium) 3 (high) 2 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. General data 7.3 7 Setting the burner type The basic 2107 controls single stage burners. To use it with 2-stage or modulating burners install a FM 242 burner module. When the FM 242 burner module is installed, the factory default changes from "1-STAGE" to "2-STAGE". With 2-stage burners, the operating hours are displayed separately for stage 1 and stage 2. Changing the burner type + Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until "BLR TEMP" is shown. Press "Display" to call up a submenu. "FREEZE TEMP" appears. Turn the dial until "2-STAGE" is displayed. 2-STAGE + MODULATE Hold down the "Display" key and turn the dial until the required value appears (in this case "MODULATE") is displayed. Release "Display" to store your input. Press "ENTER" to return to the next higher level. Burner system without burner module FM 242 Burner system with burner module FM 242 Input range Factory setting – 1-stage 1-stage/2-stage/modulating 2-stage Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 23 5 7 General data 4 7.4 Minimum modulating output of the modulating burner The modulating output requires the burner module FM 242 and "MODULATE" burner setting. The factory default is "30 %", i.e. the burner modulates its set output within an output range of 30-100 %. USER NOTE The data can be found in the technical documentation for the installed burner. Changing the minimum modulation Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "BLR TEMP" is shown. Press "Display" to call up a submenu. "FREEZE TEMP" appears. Turn the dial until "MIN MOD" is shown. MIN MOD 30 Hold down the "Display" key and turn the dial until the required value appears (in this case "40"). + MIN MOD Release "Display" to store your input. 40 Press "ENTER" to return to the next higher level. minimum modulation output 24 Input range Factory setting 10 %–60 % 30 % Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. General data 7.5 7 Operating time of the modulating burner actuator This feature requires the burner module FM 242 and "MODULATE" burner setting. The factory default is "12 seconds". USER NOTE The data can be found in the technical documentation for the installed burner. Changing the operating time of the actuator Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "BLR TEMP" is shown. Press "Display" to call up a submenu. "FREEZE TEMP" appears. Turn the dial until "MOD TIME" is shown. MOD TIME 12 Hold down the "Display" key and turn the dial until the required value appears (in this case "15"). + MOD TIME Release "Display" to store your input. 15 Press "ENTER" to return to the next higher level. Operating time of the actuator Input range Factory setting 5 – 60 seconds 12 seconds Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 25 5 7 General data 4 7.6 Pump logic To protect the boiler against corrosion from condensation inside the combustion chamber, the boiler pump (while the burner is running) will not start until the boiler water has reached a certain temperature. The temperature can be set using the "PUMPLOGIC" parameter. The factory default is 104°F (40°C), which is recommended for cast iron boilers. Recommendation: If a condensing boiler is used, the parameter should be set to 60°F (15°C) in order to make optimum use of the condensing technology. NOTE: The GB125BE requires a pumplogic of 104°F (40°C) due to its cast iron primary heat exchanger. Changing the pumplogic temperature Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "BLR TEMP" is shown. Press "Display" to call up a submenu. "FREEZE TEMP" appears. Turn the dial until "PUMPLOGIC" is shown. PUMPLOGIC °F 104 Hold down the "Display" key and turn the dial until the required value appears (in this case 122°F (50°C)). + PUMPLOGIC °F 122 Release "Display" to store your input. Press "ENTER" to return to the next higher level. Pump logic for 1-stage 2-stage Modulating burners 26 Input range Factory setting 60°F – 140°F (15°C – 60°C) 104°F (40°C) 113°F (45°C) 122°F (50°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. General data 7.7 7 Maximum boiler temperature The maximum boiler temperature is the highest target temperature the boiler will reach. The burner should switch off no later than when this temperature is reached (this applies to heating mode and DHW mode). The factory default is 176°F (80°C). Changing the maximum OFF temperature Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "BLR TEMP" is shown. Press "Display" to call up a submenu. "FREEZE TEMP" appears. Turn the dial until "MAXTEMP 1" is shown. MAXTEMP 1 °F 176 Hold down "Display" and turn the dial until the required value appears (in this case 167°F (75°C)). + MAXTEMP 1 °F 167 Release "Display" to store your input. Press "ENTER" to return to the next higher level. USER NOTE Ensure that the boiler water aquastat dial is set above the maximum boiler temperature, as it will overwrite the maximum boiler temperature. Maximum OFF temperature Input range Factory setting 158°F – 210°F (70°C – 99°C) 176°F (80°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 27 5 7 General data 4 7.8 Language selection AMERICAN 28 Press the "Display" key and "Install" key at the same time to call up the service level. Release both keys. The selected language, e.g. "AMERICAN", is displayed in the first main menu. The factory setting for the language is "AMERICAN". Now hold down the "Display" key and turn the dial to set the language. Release the "Display" key to store the set language. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Heating circuit data 8 Heating circuit data 8.1 Heating system 8 The controls is designed for 2 heating circuits. The basic 2107 supports 1 heating circuit, which can be upgraded to 2 heating circuits using the FM241card. – Circuit 01 = unmixed heating circuit, no heating circuit, perimeter heating – Circuit 02 = mixed heating circuit, no heating circuit, perimeter heating, radiant floor heating The factory setting is: Circuit Circuit 01 02 Perimeter heating Radiant floor heating If the right heating system is selected, the other heating circuit parameters are preset. They must still be verified, however. Further information on this can be found on the next page. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 29 5 8 Heating circuit data 4 Changing the heating system + Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed. "CIRCUIT 01" setting (heating circuit without mixing valve) CIRCUIT 01 Press "Display" to call up a submenu. "PERIM HTG" appears. PERIM HTG + Hold down the "Display" key and turn the dial until the required value appears (in this case "NO SYSTEM") is displayed. NO SYSTEM Press "ENTER" to return to the next higher level. USER NOTE If there is only one heating circuit with mixing valve present (HK2), circuit 1 must be set to "NO SYSTEM". If the "NO SYSTEM" setting is used, all of the following settings are hidden for this circuit. 30 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Heating circuit data + 8 Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed. "CIRCUIT 02" setting (heating circuit with mixing valve) CIRCUIT 02 Press "Display" to call up a submenu. "RADIATOR" appears. FLOOR HTG Input range Factory setting Heating circuit 1 NO SYSTEM PERIM HTG PERIM HTG Heating circuit 2 NO SYSTEM FLOOR HTG FLOOR HTG Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 31 5 Heating circuit data 8 4 8.2 Reference design temperature The reference design temperature is the boiler supply temperature required by the structure and the heating system to achieve the target room temperature at an outdoor temperature of 14°F (-10°C). The reference design temperature helps define the characteristic heating curve which is the basis for outdoor reset. It follows the idea that the colder the weather, the greater the heat loss of a structure, and the higher a boiler supply temperature needed to compensate for the resulting losses. REF TEMP °F Boiler supply temperature [°F(°C)] 167 The factory default setting results in a characteristic heating curve as shown (Fig. 8, Item 1). 2 194 (90) 176 (80) 167 (75) 158 (70) 1 140 (60) The reference design temperature (Fig. 8, Item 2) is used to adjust the heating curve. Depending on the measured outdoor temperature, the boiler supply temperature is changed in order to keep the room temperature stable and save as much on fuel as possible (Fig. 8). 122 (50) When changing the reference design temperature, the gradient of the heating curve is adjusted. 104 (40) 86 (30) 68 (20) 68 60 50 41 32 (+20) (+15) (+10) (+5) (±0) 23 14 +5 (-5) (-10) (-15) Outdoor temperature [°F(°C)] Fig. 8 Determining the heating curve Boiler supply temperature [°F(°C)] Example (Fig. 9): 176 (80) 167 (75) 158 (70) A boiler temperature of 140°F (60°C) is achieved by setting the reference design temperature to 133°F (56°C) (at an outdoor temperature of 14°F (-10°C)), 140 (60) The reference design temperature can be set from 86 to 194°F (30 to +90°C). 122 (50) 104 (40) 86 (30) 68 (20) 68 60 50 41 32 (+20) (+15) (+10) (+5) (±0) 23 14 +5 (-5) (-10) (-15) Outdoor temperature [°F(°C)] Fig. 9 32 Design temperature 140°F (60 °C) for +5°F (-15 °C) outdoor temperature. 194 (90) Determining the heating curve Further information on this can be found on the next page. The factory setting is: With PERIM HTG: With FLOOR HTG: 167°F (75°C) 113°F (45°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Heating circuit data 8 Changing the reference design temperature Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed. Press "Display" to call up a submenu. "PERIM HTG" or "FLOOR HTG" appears. Turn the dial until "REF TEMP" is shown. REF TEMP °F 167 Hold down the "Display" key and turn the dial until the required value appears (in this case 133°F (56°C)). + REF TEMP °F 133 Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting Reference design temperature for PERIM HTG 86 – 194°F (30 – 90°C) 167°F (75°C) Reference design temperature for FLOOR HTG 86 – 140°F (30 – 60°C) 113°F (45°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 33 5 8 Heating circuit data 4 8.3 DHW priority For the heating circuit 02 with mixing valve (if installed), you can set the DHW priority or DHW heating in parallel to the heating mode. Please note that if you select DHW heating in parallel to heating mode, it will take longer to recharge the tank. The factory setting is: For DHW priority: "ON" USER NOTE For heating circuit 01 the DHW priority is always ON and cannot be disabled. Changing the DHW priority Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "CIRCUIT 02" is displayed. Press "Display" to call up a submenu. "PERIM HTG" or "FLOOR HTG" appears. Turn the dial until "DHW PRIOR" is shown. DHW PRIOR ON Hold down the "Display" key and turn the dial until the required value appears (in this case "OFF"). + DHW PRIOR Release "Display" to store your input. OFF Press "ENTER" to return to the next higher level. DHW priority 34 Input range Factory setting ON OFF ON Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Heating circuit data 8.4 8 Maximum heating circuit temperature The maximum heating circuit temperature is a target temperature that should not be exceeded in the heating circuit. The factory setting is: With PERIM HTG system: With FLOOR HTG system: 194°F (90°C) 122°F (50°C) This setting is only available for heating circuit 2. Changing the maximum heating circuit temperature Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "HEAT CIRC 2" is displayed. Press "Display" to call up a submenu. "PERIM HTG" or "FLOOR HTG" appears. Turn the dial until "MAX TEMP" is shown. MAX TEMP °F 194 Hold down the "Display" key and turn the dial until the required value appears (in this case 140°F). + MAX TEMP °F 140 Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting Maximum heating circuit temperature for PERIM HTG 68 – 194°F (20°C – 90°C) 194°F (90°C) Maximum heating circuit temperature for FLOOR HTG* 68 – 140°F (20°C – 60°C) 122°F (50°C) * This function does not replace the safety thermostat for switching of the pump for radiant heating circuit. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 35 5 8 Heating circuit data 4 8.5 Remote control ON/OFF A BFU (accessory) remote control allows to easily control a heating system from the living space. If the controller is equipped with a BFU remote control, the remote control must be activated and assigned to the appropriate heating circuit. Instructions for assigning the remote control to the required heating circuit (HK1 or HK2) can be found in the remote control operating instructions. The factory setting is: For remote control: "OFF" USER NOTE Faulty communication is indicated by the LEDs flashing on the remote control. Activating the remote control Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "HEAT CIRC 1" or "HEAT CIRC 2" is displayed. Press "Display" to call up a submenu. "RADIATOR" or "UND-FLOOR" appears. Turn the dial until "REMOTE 1" for heating circuit 1 or "REMOTE 2" for heating circuit 2 is displayed. REMOTE 1 OFF Hold down the "Display" key and turn the dial until the required value appears (in this case "ON"). + REMOTE 1 ON Release "Display" to store your input. Press "ENTER" to return to the next higher level. Further information on this can be found on the next page. 36 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Heating circuit data 8 If the remote control is active, the desired room temperature for day and night mode must be entered on the remote control, rather than via the controls. The "AUT", "Day mode" and "Night mode" keys on the controls also are disabled for this heating circuit with remote control. If you press the "Temp", "AUT", "Day mode" or "Night mode" key, "REMOTE" appears on the display if the remote control is active. All settings can then only be made via the remote control. Remote control Input range Factory setting OFF ON OFF Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 37 5 8 Heating circuit data 4 8.6 Maximum room temperature compensation The room temperature compensation adjusts the calculated outdoor reset heating curve according to the measured room temperature. Any deviations from the room setpoint are then corrected immediately by adjusting the boiler setpoint temperature accordingly. USER NOTE The maximum room temperature hook-up determines the range within which deviations from the room setpoint value may be corrected. Influencing factors such as open windows or additional heat sources, e.g. wood burning stove, open fireplace, are thus eliminated in the area where the remote control is installed. If other rooms are supplied with heat via this heating circuit, then the aforementioned influencing factors can cause these near-by rooms to be supplied with insufficient heat. The function should be set to "OFF" to eliminate the chance of insufficient supply. The maximum differential temperature can only be entered if the remote control has been activated. The influence of the room temperature on the DHW temperature (heating curve) is thus limited. USER NOTE If you entered "OFF", the room temperature no longer has any influence on the supply temperature (heating curve). This setting is generally recommended for FLOOR HTG systems. The factory setting is: With FLOOR HTG system: 6°F (3°C) Further information on this can be found on the next page. 38 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Heating circuit data 8 Changing the differential temperature Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed. Press "Display" to call up a submenu. "PERIM HTG" or "FLOOR HTG" appears. Turn the dial until "ROOM COMP" is shown. ROOM COMP °F 6 + ROOM COMP OFF Hold down the "Display" key and turn the dial until the desired value appears (in this case "OFF"). Release "Display" to store your input. Press "ENTER" to return to the next higher level. Differential temperature Input range Factory setting OFF 2 – 18°F (1°C – 10°C) 6°F (3°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 39 5 8 Heating circuit data 4 8.7 Setback mode selection The Logamatic 2107 control contains night setback capability and allows you to select from 4 different types or modes of night setback for customized operation. These setback modes differ in their operation. Night Setback Options 1 Boiler Off ("BLR OFF") BLR OFF In this mode the heating system shuts down completely during the night time as long as the outdoor temperature exceeds the "FREEZTEMP" setting. Below the "FREEZTEMP" value, the circulators run in freeze protection mode. The boiler only fires if the water temperature drops below 41°F (5°C). No room sensors are used in this setback mode. 2 General Setback ("SETBACK") SETBACK The heating circulators continue operation in the "SETBACK" mode; the boiler operates on a lower heating curve and fires the burner as needed. This mode is generally used when no room sensors are present and individual zones are controlled by conventional thermostats. 3 Room Setback ("RMSETBACK") RMSETBACK This setback mode should only be selected when a room sensor is installed and activated. The system operates to maintain the desired night time temperature as specified on the room sensor. The circulators will operate continuously when the outdoor temperature is below the "FREEZTEMP" setting; the circulators shut down when the outdoor temperature is above the "FREEZTEMP" setting and the actual room temperature exceeds the night time setting. 4 Outdoor Air Setback ("OASETBACK"), factory default OASETBACK The heating system (burner and heating circulators) shuts down in night mode if the outdoor temperature exceeds the "FREEZTEMP"; if the outdoor temperature drops below the "FREEZTEMP", the heating system operates on a setback curve. This mode should only be used on buildings not occupied in the night mode; i.e. commercial and daytime use only buildings. A room sensor is generally not used in this application. Recommended setting Heating circuit with constant circulation zone: RMSETBACK (Requires room sensor) Heating circuit with ONlOFF thermostats: SETBACK (No room sensor present) Commercial (day use only) buildings: OASETBACK 40 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Heating circuit data + 8 Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed. Press "Display" to call up a submenu. "PERIM HTG" or "FLOOR HTG" appears. Turn the dial until "OASETBACK" is displayed. OASETBACK + RMSETBACK Hold down the "Display" key and turn the dial until the required value appears (in this case "OASETBACK"). Release "Display" to store your input. Press "ENTER" to return to the next higher level. Type of setback Input range Factory setting Outdoor setback Room setback Setback Boiler off Outdoor setback Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 41 5 8 Heating circuit data 4 8.8 Room temperature offset If no remote control is installed in the living area, the room temperature compensation (see Chapter 8.6 "Maximum room temperature compensation" page 39) cannot be used. The room temperature values set on the controls then simply provide a specification for calculating the boiler setpoint temperature. If the room temperature shown on the display differs from the room temperature measured with a thermometer mounted nearby, the values can be adjusted using "OFFSET". Do not take the measurements while the system is heating up, e.g. after the night setback, but only after it had time to stabilize for several hours. The adjustment causes a parallel shift in the heating curve. The factory setting is: Offset: for . example: 0°F (0°C) Displayed room temperature Measured room temperature Offset 72°F (22°C) 75°F (24°C) -3°F (-2°C) Matching temperature values Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed. Press "Display" to call up a submenu. "PERIM HTG" or "FLOOR HTG" appears. Turn the dial until "OFFSET" is shown. OFFSET °F 0 Hold down the "Display" key and turn the dial until the required value appears (in this case "-3°F"). + OFFSET °F Release "Display" to store your input. -3 Press "ENTER" to return to the next higher level. OFFSET 42 Input range Factory setting -9 – +9°F (-5°C – +5°C) 0°F (0°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Solar data 9 Solar data 9.1 Solar function ON/OFF (with FM 244 only) 9 The Solar function menu option is used to optimize the solar gain and minimize the use of fossil fuel. To achieve this, the controllers for the solar heating system and the conventional heating boiler are combined in a single unit. The controls monitors the current solar gain and the stored heat in the DHW tank, and reduces the setpoint temperature in the standby part of the DHW tank to prevent it being reheated unnecessarily. Switching off the solar function + Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until the "SOLAR" main menu appears. Press "Display" to call up a submenu. "SOLAR ON" appears. SLRFN ON + SLRFN OFF Hold down the "Display" key and turn the dial until the required value appears (in this case "SLRFN OFF"). Release "Display" to store your input. Press "ENTER" to return to the next higher level. SOLAR Input range Factory setting ON OFF ON Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 43 5 9 Solar data 4 9.2 Maximum storage tank temperature in solar mode The solar heating system will collect all solar heat that can be harvested. It will only stop when there is not sufficient insolation or to protect the tank from overheating. When "MAX SOL T" is reached at the top tank sensor FB, the solar pump is switched off. RISK OF SCALDING The DHW temperature can be set to a maximum of 194°F (90°C). At DHW temperatures over 122°F (50°C) there is a risk of scalding at the taps if no thermostatic mixing valve (anti-scald device) has been installed. WARNING! z If the DHW temperature is set above 122°F (50°C), you should only draw off mixed hot and cold water. Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until the "SOLAR" main menu appears. Press "Display" to call up a submenu. "SOLAR ON" appears. Turn the dial until "MAX-SL SR" appears. MAX-SL SR °F 167 Hold down the "Display" key and turn the dial until the required value appears (in this case "194°F"). + MAX-SL SR °F Release "Display" to store your input. 194 Press "ENTER" to return to the next higher level. USER NOTE Take the lime content of the local drinking water into consideration when determining the "MAX-SL SR" setting in order to prevent the tank scaling up. Max sol T 44 Input range Factory setting 140 – 194°F (60°C – 90°C) 167°F (75°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Solar data 9.3 9 Minimum storage tank temperature in solar mode The DHW temperature to be generated by the boiler for a given solar gain (DHW setpoint, see operating instructions for the settings) may be automatically reduced so that the tank can be charged the solar heating system. The "MIN SOL T" parameter contains the lower limit to which the temperature may fall. If the temperature of the DHW in the tank (FB sensor) falls below the value set here, then it is recharged by the boiler. The DHW setpoint temperature to be generated by the boiler is lowered no further than "MIN SL SR". The lowering function is deactivated in the "OFF" position (factory default). Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until the "SOLAR" main menu appears. Press "Display" to call up a submenu. "SLRFN ON" appears. Turn the dial until "MIN SL SR" appears. MIN SL SR °F 100 Hold down the "Display" key and turn the dial until the required value appears (in this case "130°F"). + MIN SL SR °F Release "Display" to store your input. 130 Press "ENTER" to return to the next higher level. MIN SL SR Input range Factory setting 86 – 130°F (30°C – 54°C) OFF OFF Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 45 5 10 DHW production ON/OFF 4 10 DHW production ON/OFF If the heating system is equipped with a DHW tank, DHW heating must be activated. The factory setting is "ON". If no DHW heating is installed, it should be disabled to avoid the DHW SENSR ERR error message. The controls starts the burner if necessary in order to heat the DWH. The DHW tank charging pump runs. Once the burner has been switched off, the controls uses the residual heat in the boiler to heat the DHW. Once the set DHW temperature is reached, the DHW tank charging pump is switched off. Normal heating mode is resumed at the end of the DHW heating cycle. A recirculation pump (if installed) may be controlled if the DHW heating is activated. Switching off the DHW heating Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "DHW PROD" is shown. DHW PROD ON Hold down the "Display" key and turn the dial until the required value appears (in this case "OFF"). + DHW PROD Release "Display" to store your input. OFF Press "ENTER" to return to the next higher level. DHW production 46 Input range Factory setting OFF ON ON Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. DHW recirculation pump 11 11 DHW recirculation pump The DHW recirculation pump ensures a constant supply of hot water to the taps. It is automatically activated with DHW heating and the pump runs in intermittent or continuous mode if at least one heating circuit is in normal heating mode (day mode), or if DHW heating is in day mode. The DHW recirculation pump runs continuously in the "ON" position. The factory default is "2", i.e. 2 pump runs per hour, running for 3 minutes each time (Fig. 10). 3 minutes 3 ON OFF 1 hour Fig. 10 Illustration of the DHW recirculation pump running time with factory setting 2 The intermittent mode may be set to 1 to 6 pump starts per hour in order to minimize the operating costs of the recirculation pump. This setting saves energy while ensuring comfort. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 47 5 11 DHW recirculation pump 4 Changing the recirculation pump run time Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until the "RECIRCPUMP 2" main menu is displayed. RECIRCPUMP 2 Hold down the "Display" key and turn the dial anti-clockwise until the required value appears (in this case "4"). + RECIRCPUMP Release "Display" to store your input. 4 Press "ENTER" to return to the next higher level. DHW recirculation pump 48 Input range Factory setting OFF 1 2 3 4 5 6 ON 2 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Heating curve 12 12 Heating curve DHW temperature in °F (°C) The heating curve test is used to display the DHW temperature for the current operating status at external temperatures 50°F (+10°C), 32°F (±0°C) and 14°F (-10°C). The heating curve displayed here (Fig. 11) is calculated by the controls on the basis of the values set for design temperature, offset and setpoint room temperature, and corresponds to the currently active characteristic. To ensure that there is no shift during commissioning, ensure during commissioning that: Heating curve 167 (75) the heating circuit is in "day mode" (press the "Day" key), 144 (62) 113 (45) the heating circuit is in "automatic mode" ("WWSD" key). 50 (+10) 32 (0) 14 (-10) The heating curve changes when room temperature hook-up is activated. Outdoor temperature in °F (°C) Fig. 11 Heating curve test + Displaying the heating curve Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until "HTG CURVE 01" for heating circuit 1 or "HTG CURVE 2" for heating circuit 2 (mixed circuit) is displayed. HTG CURVE 01 + Hold down "Display" and turn the dial. The first display contains the DHW temperature at 50°F (+10°C), the second at 32°F (±0°C) and the third at 14°F (-10°C). HTG CURVE °F 113 50 HTG CURVE °F 144 32 HTG CURVE °F 167 14 Release the "Display" key to return to the next higher level. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 49 5 13 Running the relay test 4 13 Running the relay test The relay test is used to check that the switching relays in the controls are working correctly. SYSTEM DAMAGE CAUTION! due to controller functions being deactivated for the duration of the relay test. The heat supply to the system is not guaranteed, so it is essential to press the "ENTER" key at the end of the relay test to exit the relay test function and thus avoid damaging the system. The displays differ according to which modules are installed in the controls. The following relays can be called up: z Burner 1st stage / 2nd stage z Modulation open/closed OFF z Boiler system pump HK1 z Heating circuit pump HK 2 z Mix valve open/closed/OFF z Tank DHW pump z DHW recirculation pump z Solar pump 50 Logamatic 2107 controls - We reserve the righ to make any change due to technical modifications. Running the relay test 13 Steps of the relay test + Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until "RELAY" is shown. RELAY Press "Display" to call up a submenu. "BURNER" appears. + Hold down the "Display" key and turn the dial, until "BURNER ON" appears in the display. Release the "Display" key. The burner starts up. BURNER h ON If the burner is working correctly and the operating hours signal has been returned by the burner, an "h" appears in the display. Turn the dial to display all the relay functions in succession. Press "ENTER" to return to the next higher level. The relay switching states are represented by symbols, e.g. for the recirculation pump (left, 1st symbol) or for DHW tank filling pump / solar pump (right, 2nd symbol). USER NOTE The pump symbol lights up continuously if the DHW tank filling pump is running. If the solar pump and DHW tank filling pump are running, then the solar pump symbol flashes. Safety instructions All available relays can be manually activated and deactivated in the relay test. With the solar pump it should be noted that a safety override may prevent activation if there is a risk of damage to the system (collector, DHW tank). Specifically this means that it will not be switched on if: z the solar module is defective z a defective collector (FSK) or DHW heating sensor (FB) was detected z the collector temperature has reached the maximum permitted temperature z the tank temperature has reached the maximum permitted temperature Press "ENTER" to return to the next higher level. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 51 5 14 Performing an LCD test 4 14 Performing an LCD test The LCD test is used to check whether all the figures and symbols are displayed in full. Carrying out an LCD test Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "LCD TEST" is shown. LCD TEST Hold down "Display" and turn the dial. All the numbers and symbols must appear on the display. + °F°C 1 2 Release the "Display" key. 1234567 Press "ENTER" to return to the next higher level. 52 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Time, correcting the accuracy 15 15 Time, correcting the accuracy Here you can set the time accurately to the second. The factory setting is "0" seconds/day. Define the deviation in seconds/day. Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "TIME" is shown. TIME 0 + TIME -10 Hold down "Display" and turn the dial until the identified deviation appears in the display, e.g.: if it is 10 s/day fast, then set to -10 s/day. Release "ENTER" to store your input. Press the "Display" key to return to the next higher level. Input range Time -30 seconds/day – +30 seconds/day Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Factory setting 0 53 5 16 Reset 4 16 Reset "RESET" is used to return all the controls settings to their factory settings. Any previously programmed heating times as well as burner and solar hours remain unchanged, however. Reset steps Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. + Turn the dial until "RESET" and 7 eights are displayed. RESET 8888 888 Hold down the "Display" key until all the numbers in the display have disappeared. RESET Release the "Display" key. The preset factory settings are now restored. The numbers appear in the display once more. No "RESET" is carried out if you release the "Display" key before all the numbers have disappeared. Press "ENTER" to return to the next higher level. 54 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Version number 17 17 Version number The version number is an encoded number that represents the production release of the controls. The version number must be specified in the event of troubleshooting or questions about upgrades to the controls. Displaying the version number + Press the "Display" key and "Install" key at the same time to call up the service level. "AMERICAN" appears as the first main menu. Turn the dial until "VERSION" and the version number (in this case "3.24") are displayed. VERSION 3.24 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 55 5 18 Sensor curves 4 18 Sensor curves Always take the comparative temperature measurement (room, supply, external and flue gas temperatures) in the vicinity of the sensor. RISK OF LIFE from electric shock. WARNING! z Disconnect the system from the power supply before opening the cover of the controls. The curves depict mean values and are subject to tolerances. z Remove the plug for the sensor to be measured from the controls (FB, FA, FK, FV, FG, FSK, FSS). Measure the resistance at the connector terminals. Resistance [k:] Outdoor temperature sensor (FA) 5 ((-1 15) 14 ((-1 10) 23 ((-5 5) 32 ((0 0) 41 ((5 5) 50 ((1 10) 60 ((1 15) Outdoor temperature [°F (°C)] 56 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Sensor curves 18 Resistance [k:] Boiler water (FK), supply (FV), DHW (FB) and solar water tank (FSS) temperature sensors 68 (20) 86 (30) 104 (40) 122 (50) 140 (60) 158 (70) 176 (80) 194 (90) Water temperature [°F (°C)] Resistance [k:] Collector sensor (FSK) . . -58 (-50) 32 (0) 122 (50) 212 (100) 302 (150) Collector temperature [°F (°C)] 392 (200) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 482 (250) 57 5 19 Operating values at the service level/setup report 4 19 Operating values at the service level/setup report Input range Factory setting American American -4 – 50°F (-20°C – 10°C) 41°F (5°C) 1, 2, 3 2 1-stage/2-stage/modulating 1-stage 10 %–60 % 30 % 5 s–60 s 12 s Pump logic 59 – 140°F (15°C – 60°C) 104°F (40°C) Maximum temperature 158 – 210°F (70°C – 99°C) 176°F (80°C) Heating circuit 01 None/PERIM HTG PERIM HTG Heating circuit 02 None/PERIM HTG/FLOOR HTG FLOOR HTG Reference temperature (PERIM HTG 1 or 2) 86 – 194°F (30 °C – 90°C) 167°F (75°C) Reference temperature (FLOOR HTG 2 only) 86 – 140°F (30°C – 60°C) 113°F (45°C) Remote control for heating circuit 1 OFF/ON OFF Remote control for heating circuit 2 OFF/ON OFF Offset circuit 1 OFF/2 – 18°F (1 – 10°C) 6°F (3°C) Offset circuit 2 OFF/2 – 18°F (1 – 10°C) 6°F (3°C) Setback type for heating circuit 1 Outdoor setback Room setback Setback Switch-off Outdoor setback Setback type for heating circuit 2 Outdoor setback Room setback Setback Switch-off Outdoor setback Language Building response Type of construction Burner system Modulating output Operating time of the burner actuator Setting Further information on this can be found on the next page. 58 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Operating values at the service level/setup report Input range Factory setting Offset for heating circuit 1 -9 – +9°F (-5°C – +5°C) 0°F (0°C) Offset for heating circuit 2 -9 – +9°F (-5°C – +5°C) 0°F (0°C) ON/OFF ON Maximum heating circuit temperature for heating circuit 2 (PERIM HTG) 68 – 140°F (20°C – 60°C) PERIM HTG 194°F (90°C) Maximum heating circuit temperature for heating circuit 2 (FLOOR HTG) 68 – 194°F (20°C – 90°C) FLOOR HTG 113°F (45°C) ON/OFF ON MAX-SL SR 140 – 194°F (60°C – 90°C) 167°F (75°C) MIN-SL SR 86 – 130°F (30°C – 54°C)/OFF OFF DHW PROD ON/OFF ON OFF/1/2/3/4/5/6/ON 2 -30 seconds/day – +30 seconds/day 0 seconds/day DHW priority Solar function DHW recirculation pump Time Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 19 Setting 59 5 20 Troubleshooting 4 20 Troubleshooting Only one error is displayed at a time, so the following table indicates the priority of each error. Fault Possible cause of the fault Effects on control characteristics Remedy Burner fault BURNER ERROR Burner control Boiler not working Central heating stays cold Eliminate the burner fault as described in the boiler or burner documentation. Boiler sensor error BLR SENSOR ERROR Sensor defective. Connecting cable interrupted The boiler is enabled with maximum output (emergency mode via thermostat is possible). Check the sensor connection. Replace the sensor Outdoor sensor error OA SENSOR ERROR Sensor defective. Connecting cable interrupted The minimum outdoor temperature is expected (outdoor temp.: 14°F (-10°C)) Check the sensor connection. Replace the sensor DHW sensor error DHW SENSOR ERROR Sensor defective. Connecting cable interrupted DHW tank no longer being topped up Solar pump is switched off Check the sensor connection. Replace the sensor Collector sensor error SL SENSOR ERROR Sensor defective. Connecting cable interrupted Solar module (FM 244) defective Solar pump is switched off Check the sensor connection. Replace the sensor Replace the module Solar hot water sensor error DHW-SL ERROR Sensor defective. Connecting cable interrupted Solar module (FM 244) defective Solar pump is switched off Check the sensor connection. Replace the sensor Replace the module Heating error HEATING ERROR Boiler water thermostat set too low. Manual reset high limit (STB) tripped No fuel Sensor not arranged correctly No boiler protection Boiler stays cold Set boiler water thermostat to "AUT" Manual reset high limit (STB) Check the fuel Check the sensor position DHW error DHW PROD ERROR Sensor not mounted correctly Filling pump is connected incorrectly or defective. Constant attempts are made to top up the DHW, but with a reduced boiler supply setpoint temperature. Check sensor and pump Manual mode Remote control 1 error REMOTE1 ERROR Remote control has wrong address Incorrect wiring Remote control is defective Connecting cable interrupted There is no current room temperature measurement, so the ambient influence, switch-on and switch-off optimization and automatic adaptation do not apply. Check the address Check the wiring Replace the remote control Remote control 2 error REMOTE2 ERROR Remote control has wrong address Incorrect wiring Remote control is defective Connecting cable interrupted There is no current room temperature measurement available, so the ambient influence does not apply Check the address Check the wiring Replace the remote control 60 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Troubleshooting Fault Possible cause of the fault Effects on control characteristics Remedy Supply temperature sensor 2 error MIX SENSOR ERROR Sensor defective. Connecting cable interrupted The mixer is no longer being controlled. Check the sensor connection. Replace the sensor FM 241 error (mixing card) FM 241 ERROR Module no longer present Module defective Module is no longer being addressed Log the module off Plug the module in again Replace the module FM 242 error (burner card) FM 242 ERROR Module no longer present Module defective Module is no longer being addressed Log the module off Plug the module in again Replace the module FM 244 error (solar card) FM 244 ERROR Module no longer present Module defective Module is no longer being addressed Log the module off Plug the module in again Replace the module Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 20 61 5 20 Troubleshooting 4 20.1 Troubleshooting "NO HEAT" call “BRENNER” (burner) wiring block – Terminal 4 – 120V Neutral – Terminal 8 – 120V input clocks hours run meter (must be field wired) – Terminal 9 – 120V input displays “BURNER ERR” message (must be field wired) – Terminal 10 / 11 – “dry” contacts close to energize burner – Terminal 12 – 120V power (drops out when manual reset limit is tripped) Burner operation The R2107 is not a cold start control. It does not reply on a call for heat from an end switch or thermostat to fire the boiler. The boiler will maintain a range of water temperature based on outdoor temperature. The differential of this range is dynamic, Example: Outdoor temperature at 32°F, based on heating curve the water temperature required is 140°F with a 26°F burner differential. The differential (26°F) is split (13°F) above & (13°F) below the target temperature. 140°F target + 13°F = 153° high limit 140°F target - 13°F = 127° low limit This 127°F to 153°F becomes the range of temperature that the boiler will maintain. As zones call and pull heat from the boiler, eventually the temperature in the boiler drops. Once the temperature in the boiler hits the low limit (127°F) the R2107 control closes a switch (dry contacts) between terminals 10 & 11 to fire the boiler (this is indicated by a flame symbol displayed on the LDC screen of the R2107). When the boiler temperature reaches the high limit (153°F), the contacts open and the boiler stops firing. Once the outdoor temperature drops below the WWSD setting, the boiler begins to maintain temperature. Above WWSD the boiler will only fire on a call for DHW. meaning that it is not fixed, and will adjust based on outdoor temperature and current system load. The starting point of the differential is 27°F (15°C) and will adjust from there. The differential will generally be wider at milder outdoor temperatures and narrower at colder outdoor temperatures. The differential is split above & below the current target temperature. 62 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Troubleshooting Oil burners – factory jumper between terminals 12 & 10, brings 120V from 12 to 10. When contacts close between terminals 10 & 11, 120V power is sent from terminal 11 to Hot on the burner (terminal 4 is the neutral). 20 Gas burners – remove factory installed jumper between terminals 10 & 12. The contacts between terminals 10 & 11 are now “dry” (no voltage present) and switching to the burner is now low voltage between terminals 10 & 11 on the R2107 and TT (or RW) on the boiler aquastat. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 63 5 20 Troubleshooting 4 64 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Troubleshooting 20 20.2 Troubleshooting „INSUFFICENT HEAT“ call A call for insufficient heat is generally a simple matter of adjusting the heating curve. The water temperature required for any heating system is determined by any number of factors but the biggest influence we see is the amount of radiation in comparison to the actual heat loss. Buildings with less radiation in relation to there actual heat loss require higher water temperature than buildings that are overradiated. Every house is unique in terms of it’s heat requirements. Some of the many factors include, construction, exposure to sun, elevation, surroundings (trees, other structures, etc), furnishings, internal heat gain (computers, lights, people, appliances, etc) and the expectations and comfort level of the individual. The heating curve on a R2107 can be adjusted in several ways: REF TEMP – the reference temperature adjusts the slope of the heating curve. The REF temperature in the R2107 references a boiler water temperature at 14°F outdoor temperature. In general, if the homeowner complains that they can never get the house up to temperature, adjust the REF temperature up. A rule of thumb would be: for every 1 degree you want to raise the room temperature, increase the REF temp by 2.5 degrees. For example: Customer says they can’t get the house above 65°F. We need to increase the room temperature by 5°F…5 x 2.5 = 12.5. You would increase the REF temperature by 12 or 13 degrees. The default setting in the R2107 is 167° REF temperature. OFFSET – the OFFSET setting is used to raise the starting water temperature of the system. Another way to say this is, raising the OFFSET setting will give you higher water temperature at milder outdoor temperatures. Common applications for adjusting the OFFSET setting include, hydro-air, fan coils, unit heaters, etc. These types of heating units typically require some amount of minimum water temperature. Occasionally, you may have a call for insufficient heat but only in milder weather. Even with fin-tube radiation, cast-iron radiators or panel radiators. With this type of a call, you will want to increase the OFFSET setting. USE THE QUICK REFERNECE GUIDE FOR INITIAL PROGRAMMING Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 65 5 20 Troubleshooting 4 20.3 Troubleshooting Domestic Hot Water TROUBLESHOOTING A “NO DHW” CALL: A “DHW PROD ERR” message will appear on the LCD screen of the R2107 control with regard to domestic hot water production. DHW ERR - when the tank temperature drops to the low limit (9°F below the set point), the R2107 goes into DHW priority mode. During DHW priority, the R2107 raises the boiler water temperature to it’s high limit, interrupts power to the space heating circuit {terminals 61(N) & 63 (H)} and energizes the DHW pump circuit {terminals 24 (N) & 25 (H)}. The pump circuit symbol is displayed on the LCD screen. In DHW priority, if the R2107 does not sense a rise in DHW temperature in 30 minutes, it will display a DHW PROD ERR message. At this point, the control will go back to space heating mode and lock out the DHW to avoid freezing the building. This message is general in nature and the R2107 control is essentially telling you, “I tried to make domestic hot water but nothing happened”. IN MOST CASES THE PROBLEM IS NOT WITH THE R2107 CONTROL. To rule out the R2107, turn power off to the R2107 to reset. The R2107 will again try to make DHW. Check terminals 24 & 25 for 120V. If power is present and boiler fires the R2107 is o.k. Check the following: 1 - bad circulator 2 - stuck flow check 3 - piping is air bound 4 - closed valve 66 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Wiring diagrams 21 21 Wiring diagrams Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 67 5 Wiring diagrams 4 68 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Index 22 Index B Boiler water temperature sensor . . . . . . . . . . 57 Burner system . . . . . . . . . . . . . . . . . . . 23 C Collector sensor . . . . . . . . . . . . . . . . . . 57 Controls on the 2107 . . . . . . . . . . . . . . . . 11 D Design temperature . . . . . . . . . . . . . . . . 32 DHW priority . . . . . . . . . . . . . . . . . . . . 34 DHW recirculation pump . . . . . . . . . . . . . . 47 E Emergency shutoff switch – heating system . . . . 6 F Frost protection . . . . . . . . . . . . . . . . . . . 6 H Heat storage capacity . . . . . . Heating circuit temperature . . . . Heating curve . . . . . . . . . . Heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 . . . . 35 . . . .49 . . .29 L Language selection . . . . . . . . . . . . . . . . . 28 LCD test . . . . . . . . . . . . . . . . . . . . . . 52 M Manual reset high limit (STB) . . . . . Maximum room temperature hook-up Menu . . . . . . . . . . . . . . . . . Modulating output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 . 38 . 17 . 24 . . . . . . . . . . . . . . . . . . . . . . . . . 27 . 26 . 25 . 56 O OFF temperature . . . . . . . . . . . ON temperature . . . . . . . . . . . Operating time of the burner actuator Outdoor temperature sensor . . . . . P Password . . . . . . . . . . . . . . . . . . . . . . 16 Pump kick . . . . . . . . . . . . . . . . . . . . . 1 9 Pump logic . . . . . . . . . . . . . . . . . . . . . 26 R Relay test . . . . . . . . Remote control . . . . . Reset . . . . . . . . . . Room temperature offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 . 36 . 54 . 42 . . . . . . . . . . . . . . . . . . . . Safety instructions . . . . . . . . . . . Sensor curves . . . . . . . . . . . . . Service level . . . . . . . . . . . . . . Setting parameters . . . . . . . . . . . Setup report . . . . . . . . . . . . . . Solar function . . . . . . . . . . . . . . System frost protection, frost protection . . . . . . . . . . . . . . . . . . . . . . . . 5 . . . 56 . . . 16 . . . 18 .58, 60 . . . 43 . . . 20 S T Type of construction . . . . . . . . . . . . . . . . 21 Type of setback . . . . . . . . . . . . . . . . . . . 40 V Version number . . . . . . . . . . . . . . . . . . . 55 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 69 Notes 70 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. Notes Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 71 United States and Canada Bosch Thermotechnology Corp. 50 Wentworth Avenue Londonderry, NH 03053 Tel. 603-552-1100 Fax 603-965-7581 www.buderus.us U.S.A. Products manufactured by Bosch Thermotechnik GmbH Sophienstrasse 30-32 D-35576 Wetzlar www.buderus.com Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances.
- Manuals
- Brands
- Buderus Manuals
- Network Router
- Logamatic 2107
Manuals and User Guides for Buderus Logamatic 2107. We have 5 Buderus Logamatic 2107 manuals available for free PDF download: Applications Manual, Installation And Service Instructions Manual, Operating Instructions Manual, Start-Up
(скачивание инструкции бесплатно)
Формат файла: PDF
Доступность: Бесплатно как и все руководства на сайте. Без регистрации и SMS.
Дополнительно: Чтение инструкции онлайн
6303 9023 – 09/2002 RU
Уровень пользователя
Внимательно прочитайте перед обслуживанием
Инструкция по эксплуатации
Системы
управления
Logamatic 2107,
Logamatic 2107 M
AUT
90
70
60
50
I
0
1…7
Tag
Zeit
Temp
Urlaub
Auswahl
So/Wi
Anzeige
Install
Zurück
PROG
ABTOPEЖUM
11:15
21
Страница:
(1 из 64)
навигация
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Оглавление инструкции
- Страница 1 из 65
6303 9023 – 09/2002 RU Уровень пользователя Инструкция по эксплуатации Системы Logamatic 2107, управления Logamatic 2107 M ABTOPEЖUM 11:15 21 1…7 Tag Urlaub Anzeige 90 Zeit Temp PROG Auswahl So/Wi Install Zurück AUT 7 0 60 50 I 0 Внимательно прочитайте перед обслуживанием - Страница 2 из 65
Предисловие Оборудование соответствует основным требованиям нормативных документов и предписаний. Соответствие подтверждено. Необходимые документы и декларация о соответствии хранятся на фирмеизготовителе. Эта инструкция по эксплуатации распространяется только на системы управления Logamatic - Страница 3 из 65
Содержание 1 Введение 2 Что нужно знать об отопительной установке . 3 Советы по экономичному отоплению . 4 Техника безопасности при работе с системой управления . 4.1 4.2 4.3 4.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Применение по - Страница 4 из 65
Содержание 10 Устранение ошибок и неисправностей. 11 Работа в случае неисправности . . . . . . . . . . . . . . . . . . . . . . . . 55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 12 Протокол настройки. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 - Страница 5 из 65
Введение 1 1 Введение Останавливая свой выбор на системе управления Logamatic 2107 или 2107 M, Вы приобретаете простой в использовании прибор, с помощью можно регулировать работу отопительной установки. При минимальном потреблении энергии Вы достигаете оптимальный тепловой комфорт. Система - Страница 6 из 65
1 Введение Об этой инструкции В главе 2 некоторые пояснения о том, как работает отопление, которые дают представление об отопительных установках и их регулировании. Глава 3 приведены советы по экономичному отоплению. В главе 4 даны указания по технике безопасности при работе с системой управления. - Страница 7 из 65
Что нужно знать об отопительной установке 2 2 Что нужно знать об отопительной установке Почему нужно ближе познакомиться с отопительной установкой? Отопительные установки нового поколения предлагают множество функций, используя которые Вы экономите энергию без ущерба собственному комфорту. Первый - Страница 8 из 65
2 Что нужно знать об отопительной установке На рисунке 1 изображен отопительный контур с принудительной циркуляцией. Горелка (2) подогревает воду в котле (1). Насос (3) перекачивает эту котловую воду по подающей линии (4) к отопительным приборам (6). Вода проходит через отопительные приборы и - Страница 9 из 65
Что нужно знать об отопительной установке 2 Зачем нужна система регулирования отопления? Система регулирования отопительной установки обеспечивает поддержание теплового комфорта и при этом следит за экономным расходом топлива и электроэнергии. При потребности в горячей воде или для повышении - Страница 10 из 65
2 Что нужно знать об отопительной установке Регулирование в зависимости от наружной температуры При этом виде регулирования определяющим показанием для температуры подающей линии является только температура, измеренная наружным датчиком. Колебания комнатной температуры из-за инсоляции, - Страница 11 из 65
Что нужно знать об отопительной установке 2 Зачем нужен таймер? Что такое отопительные контуры? Современные отопительные установки оснащены таймером для экономии энергии. Используя таймер, Вы можете установить, чтобы переключение с одного режима на другой происходило автоматически в определенное - Страница 12 из 65
3 3 Советы по экономичному отоплению Советы по экономичному отоплению Здесь приведены советы по экономичному и комфортному отоплению: – Топите только тогда, когда Вам необходимо тепло. Пользуйтесь программами, предустановленными в системе управления (стандартными программами) или Вашими - Страница 13 из 65
Техника безопасности при работе с системой управления 4 Техника безопасности при работе с системой управления 4.1 Применение по назначению 4 Система управления Logamatic 2107 предназначена для осуществления управления и контроля за отопительными установками в домах на одну семью или в домах рядовой - Страница 14 из 65
5 5 Работа системы управления Работа системы управления Вы можете выполнять настройки отопительной установки на системе управления Logamatic 2107. Наглядное расположение элементов управления упрощает работу с прибором. Элементы управления Logamatic 2107 и 2107 M 9 8 10 7 ABTOPEЖUM 11:15 21 6 0 9 A - Страница 15 из 65
Работа системы управления 5 Предохранительный ограничитель температуры Предохранительный ограничитель температуры (STB) служит для того, чтобы отопительная установка не работала со слишком высокой температурой, на которую она не рассчитана. Регулятор температуры котловой воды Обычно регулятор - Страница 16 из 65
5 Работа системы управления Кнопки основных функций Этим кнопками управляются основные функции. 1 Рис. 5 2 3 4 Кнопки основных функций Поз. 1: автоматический режим по таймеру Поз. 2: нормальный отопительный режим (дневной режим) Поз. 3: тест дымовых газов (для замеров параметров дымовых газов) Поз. - Страница 17 из 65
Работа системы управления 5 Кнопки дополнительных функций Эти кнопки нужны для установки, например, дня недели, времени, температуры и т.д. 1 2 3 4 5 6 7 8 11 Рис. 6 10 9 Кнопки дополнительных функций Поз. 1: кнопка «День недели» – ввод дня недели Поз. 2: кнопка «Отпуск» – ввод функции Отпуск Поз. - Страница 18 из 65
5 Работа системы управления Дисплей На дисплее показываются заданные и измеренные параметры и температуры, например, при закрытой крышке измеренная комнатная температура. 1 2 °F°C 1 2 1234567 5 Рис. 7 Поз. 1: 4 3 Дисплей текст индикации Поз. 2: летний режим радиочасы °F °C единицы измерения - Страница 19 из 65
Основные функции 6 6 Основные функции В этой главе приведена информация о пуске в эксплуатацию системы управления Logamatic 2107, ее выключении и об основных принципах работы с ней. ABTOPEЖUM 11:15 21 0 9 A U T 7 0 0 6 50 I 90 0 AUT 7 0 60 50 2 4 1 3 Рис. 8 6.1 Кнопки, необходимые для пуска в - Страница 20 из 65
6 6.2 Основные функции Выключение системы управления Установите пусковой выключатель в положение «0» (рис. 8, поз. 4). ПОВРЕЖДЕНИЕ КОТЛА вследствие замерзания установки. ОСТОРОЖНО! Оставляем за собой право на изменения! 20 Функция защиты от замерзания активна только при включенной системе - Страница 21 из 65
Основные функции 6.3 6 Стандартная индикация и рабочие параметры Das neue Displ ay! ABTOPEЖUM °C 7 16:30 22 В нормальном режиме на дисплее показаны день недели, время, режим работы и требуемая комнатная температура. Вывод на дисплей других рабочих параметров Поворачивая ручку переключателя, можно - Страница 22 из 65
6 6.4 Основные функции Изменение режима работы ABTOPEЖUM 11:15 21 Кнопки на системе управления 2107 (см. рисунок), имеют такие же функции, как и кнопки на дистанционном управлении. На пульте дитанционного управления можно задать режим работы для отопительных контуров, которые оснащены таким - Страница 23 из 65
Основные функции 6 Выбор автоматического режима Вместе с зеленым светодиодом (LED) над кнопкой «AUT» также горит светодиод над кнопкой «Дневной режим» или «Ночной режим» – в зависимости от того, какой режим отопления в данный момент включен. Смена нормального режима на режим с пониженной - Страница 24 из 65
6 6.5 Основные функции Установка комнатной температуры YΠPΠYλbT 1 Если подключено дистанционное управление, то комнатную температуру для нормального (дневного) режима и для режима с пониженной температурой (для ночного режима) можно установить только на дистанционном управлении для соответствующего - Страница 25 из 65
Основные функции 6 Ввод комнатной температуры (отопительные контуры без дистанционного управления) Если комнатная температура для Вас высока, то можно уменьшить ее значение. При слишком низкой комнатной температуре ее можно повысить. Нажать кнопку «Отопительный контур» и, удерживая ее нажатой, - Страница 26 из 65
6 6.6 Основные функции Установка температуры горячей воды ABTOPEЖUM 11:15 21 С помощью системы управления Logamatic 2107 можно экономично нагревать воду для контура горячего водоснабжения. Для этого предусмотрено приготовление горячей воды по таймеру. Вы можете включить приготовление горячей воды, - Страница 27 из 65
Основные функции 6 Установка температуры горячей воды Удерживать нажатой кнопку «Гор.вода» и ручкой управления установить нужную температуру горячей воды (здесь: «50 °C»). + ГOP BODA °C 50 Теперь температура горячей воды установлена на 50 °C. Отпустить кнопку «Горячая вода». Температура горячей - Страница 28 из 65
7 7 Дополнительные функции Дополнительные функции В этой главе приведена информация по дополнительным функциям. К ним относится, например, информация по настройкам солнечного коллектора и по отопительным программам. 7.1 Изменение рабочих режимов солнечного коллектора Если система управления - Страница 29 из 65
Дополнительные функции 7 Ручной режим работы солнечного коллектора Функциональный тест солнечного коллектора. В этом режиме установка не работает автоматически. Насос солнечного коллектора включается вручную, если это позволяет состояние установки (например, если коллектор не достаточно горячий). - Страница 30 из 65
7 7.2 Дополнительные функции Выбор стандартной программы Что значит программа отопления? ABTOPEЖUM 11:15 21 Программа отопления заботится об автоматической смене режимов работы: нормального (дневного) и режима с пониженной температурой (ночного) в определенное время. Автоматический переход - Страница 31 из 65
Дополнительные функции 7 Обзор стандартных программ Выберите стандартную программу, которая наилучшим образом соответствует Вашим потребностям. Если Вы хотите иметь индивидуальную программу, то задайте собственные значения времени включения и выключения. На выбор предлагаются следующие восемь - Страница 32 из 65
7 Дополнительные функции Выбор стандартной программы (выбор программы для отопительного контура) Открыть крышку. Удерживать нажатой кнопку «Отопительный контур» до появления, например, «Отопительный контур 1». + Отпустить кнопку «Отопительный контур». Нажать кнопку «PROG» и повернуть ручку - Страница 33 из 65
Дополнительные функции 7.3 7 Ввод программы Отпуск Вы можете прервать установленную отопительную программу, если, например, на следующий день отправляетесь в отпуск. В этот период Вы хотите топить меньше. ABTOPEЖUM 11:15 21 Преимущество отопительного режима с пониженной температурой (ночного - Страница 34 из 65
7 Дополнительные функции Удаление программы Отпуск Для удаления действующей программы Отпуск и перехода к нормальному режиму работы выполните следующие действия: Открыть крышку. + Удерживать нажатой кнопку «Отпуск» и повернуть ручку управления до появления на дисплее строк «OTПYCK 00». Отпустить - Страница 35 из 65
Дополнительные функции 7.4 7 Установка программы переключения режима лето/зима ABTOPEЖUM 11:15 21 В системе управления Logamatic 2107 переключение с летнего режима на зимний и наоборот происходит с некоторым запаздыванием по времени, так как сигнал от датчика наружной температуры поступает уже с - Страница 36 из 65
7 Дополнительные функции Установка переключения режима лето/зима Открыть крышку. Удерживать нажатой кнопку «Лето/зима» и повернуть ручку управления до появления «ЛETO C» и нужной «демпфированной наружной температуры». + λETO C °C 21 Отпустить кнопку «Лето/зима» для сохранения введенных данных. Этот - Страница 37 из 65
Дополнительные функции 7.5 7 Настройка постоянного режима приготовления горячей воды Установка постоянного режима ABTOPEЖUM 11:15 21 Открыть крышку. Удерживать нажатой кнопку «Отопительный контур» и повернуть ручку управления до появления строки «ГOP BODA». + ГOP BODA Отпустить кнопку «Отопительный - Страница 38 из 65
7 7.6 Дополнительные функции Изменение стандартной индикации Выберите, какая индикация должна появляться на системе управления в спокойном режиме. ABTOPEЖUM 11:15 21 Заводская настройка: Das neue Displ ay! ABTOPEЖUM °C 7 06:30 22 «ABTOPEЖUM», время, день недели, актуальная заданная комнатная - Страница 39 из 65
Дополнительные функции 7.7 7 Установка времени и дня недели Если установлено дистанционное управления со встроенным приемником радиосигналов (BFU/F), то настройка или корректировка дня недели и времени происходит автоматически. ABTOPEЖUM 11:15 21 Открыть крышку. + Удерживать нажатой кнопку «День - Страница 40 из 65
7 7.8 Дополнительные функции Переключение летнего/зимнего времени Ручной ввод летнего/зимнего времени Переустановка происходит по установленным законом правилам: ABTOPEЖUM 11:15 21 – на зимнее время: в выходные дни последней недели октября: в воскресенье в 03:00 часа на 02:00 часа (-1 час). – на - Страница 41 из 65
Дистанционное управление BFU, BFU/F 8 8 Дистанционное управление BFU, BFU/F Дистанционное управление BFU или BFU/F (дополнительное оборудование) позволяет комфортабельно регулировать работу отопительной установки из жилого помещения. 8.1 Общая информация по BFU, BFU/F Дистанционное управление имеет - Страница 42 из 65
8 8.4 Дистанционное управление BFU, BFU/F Отопительный режим с пониженной температурой (ночной режим) Отопительный режим с пониженной температурой вводится в виде разницы температур между нормальным режимом и режимом с пониженной температурой. Настройку должен выполнять специалист отопительной - Страница 43 из 65
Дистанционное управление BFU, BFU/F 8 Автоматический режим Вместе с зеленым светодиодом на кнопке «AUT» горит также светодиод на кнопке «Дневной режим» или на кнопке «Ночной режим» — в зависимости от актуального отопительного режима. Если имеются два отопительных контура, и только один из них имеет - Страница 44 из 65
8 Дистанционное управление BFU, BFU/F Ручной режим Отопительный режим с пониженной температурой (ночной режим) Вы переключаетесь на ручной режим, чтобы изменить нужную температуру. Режим индицируется зеленым светодиодом на кнопке «Ночной режим». В этом режиме отопление работает с пониженной - Страница 45 из 65
Дополнительные возможности программирования 9 9 Дополнительные возможности программирования 9.1 Изменение стандартной программы Если стандартная программа Вам не очень подходит, то ее можно изменить или поручить это специалисту отопительной фирмы. Измененная стандартная программа сохраняется под - Страница 46 из 65
9 Дополнительные возможности программирования Перенос времени переключения Если Вы внесли изменения в стандартную программу или ввели полностью новую программу, то система управления сохраняет введенные данные под названием «COGCTB. 1» для отопительного контура 1 и «COGCTB. 2» для отопительного - Страница 47 из 65
Дополнительные возможности программирования 9 Установка времени переключения. Можно ввести точки переключения (установив день недели, время и температуру) в существующую отопительную программу, например, для того, чтобы прервать фазу отопления. ABTOPEЖUM 11:15 21 1…7 УКАЗАНИЕ ДЛЯ ПОТРЕБИТЕЛЯ - Страница 48 из 65
9 Дополнительные возможности программирования CEMbЯ 1 05:30 °C 21 На дисплее появится первое время переключения стандартной программы «CEMbЯ». Повернуть налево ручку управления до появления на дисплее строки «HOB T ПEP». HOB T ПEP °C 7 —:— —Удерживать нажатой кнопку «День недели» и повернуть - Страница 49 из 65
Дополнительные возможности программирования 9 Отмена отопительного периода Отопительный период подразумевает два значения времени переключения: одного включения и одного выключения. Если Вы хотите отменить отопительный период, то нужно отменить оба времени переключения. ABTOPEЖUM 11:15 21 До - Страница 50 из 65
9 Дополнительные возможности программирования Повернуть ручку переключателя до появления времени переключения отопительного периода, который Вы хотите отменить, например, «11:30». Удерживать нажатой кнопку «Время» и ручкой управления установить нужное значение (здесь: «13:00»). + ΠOλDEHb 1 13:00 - Страница 51 из 65
Дополнительные возможности программирования 9.2 9 Объединение отопительных периодов Отопительный период подразумевает два значения времени переключения: одного включения и одного выключения. Чтобы объединить два отопительных периода, идущих один за другим, установите время выключения первого - Страница 52 из 65
9 Дополнительные возможности программирования Повернуть ручку переключателя до появления времени выключения отопительного периода, который нужно объединить с другим отопительным периодом (здесь: «13:00»). Удерживать нажатой кнопку «Время» и ручкой управления установить нужное значение (здесь: - Страница 53 из 65
Дополнительные возможности программирования 9.3 9 Создание новой программы отопления Можно также создать новую отопительную программу, которая полностью соответствует Вашим потребностям. Новая программа сохраняется под названием «COGCTB. 1». ABTOPEЖUM 11:15 21 Ввод времени переключения, например, - Страница 54 из 65
9 Дополнительные возможности программирования Удерживать нажатой кнопку «Темп.» и повернуть ручку управления до появления нужной комнатной температуры для нормального отопительного режима, например, «21 °C». + HOB T ΠEP 1 05:00 °C 21 HOB T ΠEP °C 7 —:— — Отпустить кнопку «Темп.». Время - Страница 55 из 65
Устранение ошибок и неисправностей 10 10 Устранение ошибок и неисправностей При возникновении неисправностей отопительной установки на дисплее системы управления появляются сообщения об этом. Некоторые неисправности можно устранить самостоятельно (см. главу «Таблица неисправностей» на стр. 56). Для - Страница 56 из 65
10 Устранение ошибок и неисправностей Таблица неисправностей Сообщение о неисправности Фактическая ситуация Рекомендации – Не работает отопление. Устранить неисправность в соответствии с указаниями в документации на отопительный котел или горелку. – Не работает отопление. Вызвать специалиста - Страница 57 из 65
Устранение ошибок и неисправностей Сообщение о неисправности 10 или YΠPΠYλbT 2 Err. DATTEMKOT Err. DATHAPTEM Err. DAT ГBC Err. DATΠODλUH Err. DATOTXГA3 Err. DAT CОλH Err. DAT ГВС С Err. Рекомендации Неисправности дистанционного управления YΠPΠYλbT 1 Err. Фактическая ситуация Вызвать специалиста - Страница 58 из 65
11 Работа в случае неисправности 11 Работа в случае неисправности При неисправности в управлении можно продолжать эксплуатировать систему отопления. ABTOPEЖUM 11:15 21 ОПАСНО ДЛЯ ЖИЗНИ 0 9 AT U 7 0 60 I 50 ПРЕДУПРЕЖДЕНИЕ! из-за возможного поражения электрическим током. 0 Никогда не вскрывайте - Страница 59 из 65
Работа в случае неисправности 11 При возникновении неисправностей нужно сразу же уведомить специалистов отопительной фирмы, обслуживающей котел. Они обеспечат квалифицированное техническое обслуживание. Вы сможете им помочь, если точно опишите характер неисправностей. Ручной режим В ручном режиме - Страница 60 из 65
12 Протокол настройки 12 Протокол настройки Рабочие параметры Диапазон ввода Заводская установка Заводские программы CEMbЯ PAHbШE ΠO3ЖE YTPO BEЧEP ПОЛДЕНЬ XOЛOCTЯK HOBAЯ COGCTB. CEMbЯ Горячая вода 30 °C–90 °C 60 °C Переключение лето/зима постоянно лето постоянно зима 10 °C–30 °C 17 °C Дневная - Страница 61 из 65
Тест дымовых газов 13 13 Тест дымовых газов Тест дымовых газов должен проводить только мастер из службы контроля за дымовыми трубами. Этот тест проводится один раз в год. ABTOPEЖUM 11:15 21 0 9 AT U 7 0 60 50 90 0 AUT 7 0 50 1 I 60 Мастер проводит замеры на отопительной установке. Отдельные - Страница 62 из 65
14 Алфавитный указатель 14 Алфавитный указатель А Аварийный режим . . . . . . . . . . . . . . . . . 58 Автоматический режим . . . . . . . . . . . .23, 42 Автоматический режим солнечного коллектора . . . . . . . . . . . . . . . . . . . . . 28 Б Бак-водонагреватель . . . . . . . . . . . . . . . 7 В - Страница 63 из 65
Алфавитный указатель 14 Ручка управления . . . . . . . . . . . . . . . . . 15 Ручной режим . . . . . . . . . . . . . . . . . . . 59 Ручной режим солнечного коллектора . . . . . 29 С Система регулирования . . . . . . . . . . . . . . 7 Солнечный коллектор Выкл. . . . . . . . . . . . 29 Стандартные - Страница 64 из 65
Специализированная отопительная фирма: Buderus Heiztechnik GmbH, 35573 Wetzlar http://www.heiztechnik.buderus.de E-Mail: info@heiztechnik.buderus.de - Страница 65 из 65
Предложите, как улучшить StudyLib
(Для жалоб на нарушения авторских прав, используйте
другую форму
)
Ваш е-мэйл
Заполните, если хотите получить ответ
Оцените наш проект
1
2
3
4
5