Hardware and Engineering

PS4-201-MM1

04/99 AWB 27-1184 GB

1st published 1994, edition 04/94

2nd published 1995, edition 04/94

3rd published 1997, edition 06/97

4th published 1999, edition 04/99

See modifications list on page II

© Moeller GmbH, Bonn

Author:

Werner Albrecht

Editor:

Thomas Kracht

Translator:

Terence Osborn

loading

Related Manuals for Moeller PS4-201-MM1

Summary of Contents for Moeller PS4-201-MM1

  • Page 1
    04/99 AWB 27-1184 GB 1st published 1994, edition 04/94 2nd published 1995, edition 04/94 3rd published 1997, edition 06/97 4th published 1999, edition 04/99 See modifications list on page II © Moeller GmbH, Bonn Author: Werner Albrecht Editor: Thomas Kracht Translator:…
  • Page 2
    No part of this manual may be reproduced in trademarks or registered trademarks of the any form (printed, photocopy, microfilm or owner concerned. any otherprocess) or processed, duplicated or distributed by means of electronic systems without written permission of Moeller GmbH, Bonn. Subject to alterations without notice.
  • Page 3
    List of revisions to AWB 27-1184 GB Edition date Page Description Modifica- Omitted tion 04/99 gen. Sucosoft S 30-S4 → Sucosoft S 4 S 40 AWB 27-1185/1186 → AWB 27-1280-D AWB 2700-1305 D → AWB 27-1281-D AWB 2700-1306 D Legend Slave adress Note 52/53…
  • Page 5: Table Of Contents

    Contents About this Manual Documentation for the PS4-200 Symbols 1 About the PS4-200 Compact PLC Hardware and software requirements Features Setup Elements 2 Engineering Electromagnetic compatibility (EMC) Connections Programming device interface Suconet K interface Setting the bus terminating resistors Local expansion Arrangement of the control cabinet Power supply Avoiding interference…

  • Page 6
    6 Operation Power-up behaviour Shut-down behaviour Operating states of the PLC Start-up behaviour Program transfer Starting the PLC with a program stored in the memory module Programming via Suconet K 7 Testing/Commissioning/Diagnostics Status LEDs Diagnostics Message byte Appendix Optimizing the exchange of send and receive data Accessories Slave addressing…
  • Page 7: About This Manual

    About this Manual Documentation for The documentation for the PS4-201-MM1 compact the PS4-200 PLC (referred to below as PS4-200) is subdivided into four manuals with the following topics: Hardware and engineering User interface for the programming software Programming Training guide Hardware and engineering manual This manual, “Hardware and Engineering”, explains…

  • Page 8: Symbols

    About this Manual Programming manual Information on programming the PS4-200 is contained in the “Language elements of the PS4-150/-200/-300 and PS416” manual (AWB2700-1306GB). Training guide The training guide AWB27-1307GB uses practical examples to illustrate the key functions of the Sucosoft S 40 software. Symbols The symbols in this manual have the following meaning:…

  • Page 9: About The Ps4-200 Compact Plc

    About the PS4-200 Compact PLC Hardware and software Sucosoft S 40 requirements To program the PS4-200 you need a PC (IBM or IBM- compatible) with at least a Pentium processor a Windows 95, Windows 98 or Windows NT 4.0 operating system at least 16 Mbyte RAM ″…

  • Page 10: Features

    About the PS4-200 Compact PLC Features The main features of the PS4-200 compact PLC are as follows: 24 V DC power supply 8 digital inputs, 2 4V DC 6 digital outputs, 24 V DC 2 analog inputs 1 analog output Setup Figure 1 provides an overview of the operating and display elements of the programmable controller as…

  • Page 11
    1=Ready Digital 2=Run Input 3=Not Ready 1 2 3 4 4=Battery Suconet K PS4-201-MM1 Digital Analog Output Input/Output .0 .1 .2 .3 .4 .5 Figure 1: Overview of the PS4-200 24 V DC power supply High-speed counter input (alternative to I 0.0), 3 kHz Alarm input (alternative to I 0.1)
  • Page 12: Elements

    About the PS4-200 Compact PLC Elements Power supply unit The PS4-200 is operated with a rated voltage of 24 V DC. The power supply connection is protected against polarity reversal. The 24 V connection enables the PLC in the control cabinet to be supplied with voltages to industrial standards (IEC).

  • Page 13
    Elements Status LEDs for digital inputs The physical states of the inputs and the diagnostics status word are indicated by LEDs. Status LEDs for outputs The logical states of the outputs are indicated with light-emitting diodes (LEDs). Outputs Q 0.6 and Q 0.7 are only provided as LEDs.
  • Page 14
    About the PS4-200 Compact PLC Suconet K interface The RS 485 interface is galvanically isolated from the CPU. It has the following functions: Networking of Suconet K stations (e.g. EM4… expansion modules) Data exchange with partner devices that have a serial port (printers, terminals, etc.).
  • Page 15
    Elements Programming device interface (PRG) The RS 232 interface is galvanically isolated from the CPU. It has the following functions: Programming the PLC via the PC Data exchange with partner devices that have a serial port (printers, terminals, etc.). This type of communication is used for process data acquisition, visualization etc.
  • Page 16
    About the PS4-200 Compact PLC The 128 Kbyte flash module is subdivided into a 64 Kbyte backup memory (retentive storage of the user program in the event of a voltage failure) and a 64 Kbyte memory for recipe data, for example.
  • Page 17
    Elements Diag. Battery Reset 1 Halt/Diag. 2 Run 3 Run M-Reset Figure 3: Controls and display elements of the PS4-200 (with housing flap open) Back-up battery Reset button Plug connector for local expansion modules Operating mode selector switch Back-up battery The battery backs up the internal RAM and the real- time clock.
  • Page 18
    About the PS4-200 Compact PLC Operating mode selector switch/ reset button You can select the “Halt” (stop), “Run” and “Run M-Reset” modes with the operating mode selector switch. The selected mode is activated when you press the Reset button. The operating states are described in detail in the chapter “Operation”.
  • Page 19: Engineering

    Engineering Electromagnetic Observe the engineering instructions in the manual compatibility (EMC) “EMC Engineering Guidelines for Automation Systems” (AWB27-1287GB). Connections Screened data and signal cables Route screened data and signal cables on the left and the right of the device along the shortest possible distance and connect the screen braid to the ground terminal using a low-impedance connection and large contact areas (See Fig.

  • Page 20
    Engineering Figure 4: Screen connection to reference potential surface…
  • Page 21
    Connections Overview 24V 0V Power Supply Output .0 .1 .2 .3 .4 .5 .6 .7 24V Power Supply Suconet K .0 .1 .2 .3 .4 .5 U Figure 5: Overview of connections Screw terminals: 24 V DC power supply Terminal cross-sections: Flexible with ferrule 0.22 — 2.5 mm Solid 0.22 — 2.5 mm Plug-in screw terminal…
  • Page 22: Programming Device Interface

    Engineering Programming device Connector pin assignments interface Figure 6: Pin assignment of the programming device connector (PRG) (left-hand socket, top view) The housing of the socket is connected to the ground terminal of the power supply for the PS4-200 via a capacitor (only applies to version 03 and earlier).

  • Page 23
    Programming device interface Connecting the programming device (PC) Connect the PC to the PRG interface of the PS4-200 (left-hand socket) using the programming cable ZB4-303-KB1. PS4-201-MM1: PRG interface COM interface (8-pole. DIN pin (9-pole. socket) connector) Figure 7: Pin assignment of the ZB4-303-KB1…
  • Page 24: Suconet K Interface

    Engineering Suconet K interface Connector pin assignments Figure 8: Pin assignment of the Suconet K interface (PRG) (right-hand socket, top view) The housing of the socket is connected to the ground terminal of the PS4-200 power supply via a capacitor (only applies to version 03 and earlier).

  • Page 25: Setting The Bus Terminating Resistors

    Setting the bus terminating resistors Setting the bus Set the bus terminating resistors on the module terminating resistors for the first and last physical stations on a line. To do this, both S1 switches should be set to the “ON” position. Both switches must be set to the “OFF”…

  • Page 26: Arrangement Of The Control Cabinet

    Engineering Arrangement of the The arrangement of the components in the control control cabinet cabinet has a significant influence on the correct operation of the machine or plant. When planning, designing and installing the equipment, ensure that the power section and the control section are separated from one another.

  • Page 27: Power Supply

    Power supply PS 4- 201-MM1 Figure 10: Horizontal installation ″ ) clearance At least 5 cm (2 Power section Cable duct When you use the PS4-200 together with local expansion modules, you must install the controller horizontally. Power supply The next few pages show circuit diagrams for the following power supply arrangements: Figure 11: Common power supply for the PS4-200 and the…

  • Page 28
    Engineering Legend for Figure 11: Main switch Protective device for power supply units Miniature circuit-breakers Power supply for the digital inputs Link (no longer required from PS4-200 version 04) Power supply for the PS4-200 Power supply for the digital outputs Reference potential for the digital inputs/outputs Terminal with PE connection (no longer required from version 04)
  • Page 29
    Power supply I > I > I > +24 V +24 V +24 V 2.5 mm PS 4-201-MM1 Figure 11: Common power supply wired for grounded operation…
  • Page 30
    Engineering Legend for Figure 12: Main switch Protective device for power supply units Capacitive ground Potential equalization rail Earth fault monitoring device Miniature circuit-breaker Power supply for the digital inputs Link (no longer required from PS4-200 version 04) Power supply for the PS4-200 Power supply for the digital outputs Reference potential for the digital inputs/outputs Terminal with PE connection…
  • Page 31
    Power supply I > I > I > +24 V +24 V +24 V 2.5 mm PS 4-201-MM1 Figure 12: Common power supply wired for non-grounded operation…
  • Page 32: Avoiding Interference

    Engineering Avoiding interference Cabling and wiring Cables come under the following categories: Power cables (e.g. cables carrying heavy current or cables to power converters, contactors or solenoid valves) Control and signal cables (e.g. digital input cables) Measuring and signal cables (e.g. field bus cables) Power, control and signal cables must always be laid as far apart from one another as possible, in…

  • Page 33
    Avoiding interference Cover Communication cables Cable duct Measuring cables, analog cables Control cables Power cables Continuous partition Figure 13: Using separate ducts for power and signal cables…
  • Page 34
    Engineering Suppressor circuits for interference sources All suppressor circuits must be installed as close as possible to the interference sources (contactors, relays, valves). Suppressor circuits should be provided for all switched inductances. Screening Only use screened cables for the programming device interface (PRG) and the Suconet K interface of the PS4-200.
  • Page 35
    These measures comprise: Lightning-protection potential equalization Screening Overvoltage protection devices Further information on this subject is provided in the TB27-001GB manual from Moeller entitled “Electromagnetic Compatibility (EMC) of Automation Systems”.
  • Page 37: Mounting

    Mounting Mounting on a top-hat Proceed as follows to mount the PLC on a top-hat rail rail: Place the module on the top-hat rail so that the top edge of the rail latches into the groove. Insert a screwdriver into the slot of the sliding clip and lever the clip down Press the module onto the top-hat rail Release the sliding clip.

  • Page 38: Mounting On Feet

    Mounting Mounting on feet Proceed as follows to mount the PLC on feet: Press in the feet so that they snap into position Check that they are correctly in position. The lug must latch in the hole Fasten the feet to the mounting plate with M4 screws.

  • Page 39: Software Configuration

    Software Configuration General You can configure the PLCs and all the other components you need for your application with the Sucosoft S 40 Topology Configurator. These components are as follows: Master PLC (with local expansion modules for the inputs/outputs) Network stations (slaves for expanding the remote I/O or intelligent slaves) Local expansion modules (LE4-…) LE 4-…

  • Page 40: Topology Configuration Procedure

    Software Configuration Topology configuration Each Suconet K line in an automation system is procedure assigned to a single master. All the other stations on the master’s line are slaves. A separate configuration must be defined for every station with its own CPU, i.e.

  • Page 41
    Topology configuration procedure e.g. PS 4-201-MM1 Line Station 0 e.g. PS 4-201-MM1 Station Module 0 EM 4-201-DX2 e.g. LE 4-… Station Module 0 Module 1 Figure 17: Master configuration If intelligent Suconet K stations have local expansion modules, you only specify the base module (module 0) as a “network station”…
  • Page 42: Configuring And Setting Parameters

    Software Configuration e.g. PS 4-201-MM1 LE 4-… Line Station 0 Module 0 Module 1 Figure 18: Slave configuration Configuration of slaves for expanding the remote inputs/outputs Slaves for expanding the remote inputs/outputs are configured in the master’s configuration file. Configuring and setting The configuration steps for the PS4-200 PLCs parameters described here differ according to the functions the…

  • Page 43
    Configuring and setting parameters Table 1: Station configurations Master Intelligent slave SCO (from ver. 05) Line – Station 1 to 8 – Module – (m) = Master’s configuration (s)=Slave’s configuration Table 2: Station parameters Master Intelligent slave SCO (from ver. 05) Bus status Master –…
  • Page 44
    Software Configuration Line: Number of the network line to which a station is connected. The master is always connected to line 0 and the slaves to line 1. Station: Number of the station connected to a line Module: Number of the module belonging to a station Baud rate: Select 375 kBaud as the data transfer rate if only Suconet K stations are connected to the Suconet K…
  • Page 45
    Configuring and setting parameters Slave address: The station number must be entered here in order to configure an intelligent slave. The station address is always 1 higher than the station number (e.g. slave 1 has address 2). CRC: Method of enhancing data transmission integrity. You should activate CRC (ON) if you attach greater importance to data integrity than to short response times.
  • Page 46
    Software Configuration Maximum values for send and receive bytes The Suconet K protocol allows data with a variable length to be transferred cyclically, whereby the number of bytes is dependent on the settings for the master and the slave (see below). The data length for communication with slaves for expanding the remote inputs/outputs is dependent on the slave type.
  • Page 47: Configuration Example With Local Expansions

    Configuration example with local expansions Defining input and output data First of all you must decide how many bytes an intelligent slave should send to the master and specify this number with the “Input data” parameter in the master’s configuration. When you later specify the slave’s own configuration, you must specify the same number with the “Output data”…

  • Page 48: Configuration Example

    Software Configuration Configuration example This example requires topology configurations for the master (device A) and the intelligent slaves (devices B and C). Note that intelligent slaves are configured twice — once in the master’s configuration and once in the slave’s own configuration. PS 4-201-MM1 Device A PS 4-201-MM1…

  • Page 49
    Configuration example The stations shown in the configuration example are configured as follows: Configuration of device A PS 4-201-MM1 Device A PS 4-201-MM1 LE 4-… LE 4-… LE 4-… Device Station 1 PS 4-151-MM1 Device C Station 2 EM 4-201-DX2 LE 4-…
  • Page 50
    Software Configuration Table 6: Configuration of device A Device Type Line Station Module Parameter PS4-201-MM1 Bus status: master Baud rate: 375 kBaud CRC status for slaves 1 to 3: OFF PS4-201-MM1 Input data: 20 Output data: 10 PS4-151-MM1 Input data: 40…
  • Page 51
    Configuration example Configuration of device C PS 4-151-MM1 Figure 22: Configuration of device C Table 8: Configuration of device C Device Type Line Station Module Parameter PS4-151-MM1 Bus status: slave Slave address: 3 Input data: 38 Output data: 40 Remote control: OFF…
  • Page 53: Slave Addressing

    Slave Addressing Slaves for expanding The PS4-200 master PLC and the slaves for remote inputs/outputs expanding the remote inputs/outputs can communicate with one another using the Sucone tK or K1 protocols. The protocol is selected by the master automatically according to the capabilities of the slaves.

  • Page 54
    Slave Addressing The general syntax rule is as follows: Operand-data type-line-station-module-byte-bit Example You wish to scan the inputs of slaves 1 and 2 marked in the diagram below. PS 4-201-MM1 Master LE 4-116-DX1 EM 4-201-DX2 Slave 1 EM 4-201-DX2 Slave 2 .0 …
  • Page 55: Intelligent Slaves

    Intelligent slaves Table 10: Syntax for addressing slaves for expanding remote inputs/outputs IL program Data Ope- Data Line Station Module Byte/ Bits S 40 syntax in … flow rand type word Master Master LD % I1.1.1.0.7 ↑ Slave 1 Master Byte –…

  • Page 56
    Slave Addressing The general syntax rule is as follows: Operand-data type-line-station-module-byte-bit If the PS4-200 is run as slave, it provides status bytes %ISB0.0.0.0 for device status information and %ISB0.0.0.1 for slave status information. These status bytes cannot be scanned together in one word but must be addressed separately.
  • Page 57
    Intelligent slaves You can derive the syntax for sending and receiving the data from the configuration. Table 12: Syntax for addressing intelligent slaves (data type: word) IL program Data flow Ope- Data Line Sta- Module Byte/ Syntax in … rand type tion word…
  • Page 59
    Operation Power-up behaviour After the power supply is switched on, the PS4-200 carries out its own system test. The PLC then switches to the “Ready” or “Run” status if no hardware errors have been found. The system test consists of the following routines: Memory test User program test The results of the test are indicated by the “Ready”,…
  • Page 60
    Operation Operating states of the The PLC can have the following operating states: “Run”, “Ready”, “Not Ready”. Communication with the PC is possible in all three operating states. Accordingly, the current status of the PLC and the real-time clock can always be read, for example.
  • Page 61
    Operating states of the “Run” status means that the user program is running cyclically. The PLC is switched to the “Run” status: If the “Reset” button is pressed when the operating mode selector switch is set to “Run” or “Run M-Reset”; After the power supply is switched on if the operating mode selector switch is set to “Run”…
  • Page 62
    Operation Overview Table 13: Overview of the operating states Position of PLC status Action PLC status after action operating before Press Power mode action (DSW = diagnostic status word) Reset supply off/ selector button switch 1 (Halt) – Ready Ready –…
  • Page 63
    Start-up behaviour Legend for Table 13: 1) If the programs in the memory module and the RAM of the PLC are not the same, the program in the memory module (backup program) will be copied to the RAM. 2 ) After the user program has been transferred to the PLC or after the memory module has been booted, the PLC is switched to “Not Ready”…
  • Page 64
    Operation A cold start can be initiated as follows: By pressing the “Reset” button if the operating mode selector switch is set to “Run M-Reset”, providing the PLC is currently in the “Ready” or “Not Ready” status; By switching on the power supply if the operating mode selector switch is set to “Run M-Reset”;…
  • Page 65
    Program transfer A warm start can be initiated as follows: By pressing the “Reset” button if the operating mode selector switch is set to “Run”, providing the PLC is currently in the “Ready” status; By switching on the power supply if the operating mode selector switch is set to “Run”, providing the PLC contains a battery in working condition;…
  • Page 66
    Operation → When a program is transferred from the PC to the PLC, the PS4-200 must be in the “Ready” or “Not Ready” status. The setting of the operation mode selector switch on the operator console is not important. Transfer the program to the PLC; refer to the manual “Sucosoft S 40 User Interface”…
  • Page 67
    Starting the PLC with a program stored in the memory module Starting the PLC with a The procedure for starting a user program in the program stored in memory module is as follows: the memory module Plug the memory module into the PLC (the PLC must be switched off).
  • Page 68
    Operation PLC program PS 4-141-MM1 PS 4-201-MM1 LE 4-501-BS1 PS 4-151-MM1 PS 4-151-MM1 Figure 25: Programming via Suconet K *) Programming on the PS4-201-MM1 is possible with Version 05 or higher.
  • Page 69
    Testing/Commissioning/Diagnostics Status LEDs The coloured light-emitting diodes (LEDs) allow fast and simple diagnostics of the PLC functions. The states of the inputs/outputs are easy to monitor. Table 14: Significance of the LEDs Status Significance Ready – On (yellow) Self-test successfully completed and CPU ready to start Blinking…
  • Page 70
    Testing/Commissioning/ Diagnostics Diagnostics Status information is scanned hierarchically using the diagnostics status word and the station’s diagnostics byte as well as the diagnostics bytes of any local expansion modules which are connected to Diagnostics status word The diagnostics status word provides an overview of the various error messages.
  • Page 71
    Diagnostics Table 15: Diagnostics bit display PLC status PLC status Run/ Ready Not Ready – – Table 16: Description of diagnostic (indication) bits (Run/ Ready status) Code Message name Diagnostics message description Diagnostic Remote Error in the status of a remote expansion device. The basic unit’s Suconet K Status interface has encountered a network error with one of the stations.
  • Page 72
    Testing/Commissioning/ Diagnostics Table 17: Description of diagnostic (error) bits (Not Ready status) Code Message name Diagnostics message description Restart only with M- This error appears if you have selected the option “Halt” under “Start after Reset (retentive Not Ready” in the PS4-200 configuration and have tried to carry out a warm marker reset).
  • Page 73
    Message byte The status information indicates, for example, whether: The device ID is incorrect The device has been disconnected from the Suconet bus or does not respond There is a short-circuit at the digital output of the station, etc. The status information and its meaning are described in the manuals for the respective Suconet stations and local expansion modules.
  • Page 75
    Example A PS4-201-MM1 (master) needs to exchange data with three slaves A, B, C (also PS4-201-MM1) as shown in the following figure. The number of bytes received from each slave also includes the diagnostics bytes from the slave and from any local…
  • Page 76
    Appendix 40 Byte Slave A Master 50 Byte 30 Byte Slave B 40 Byte 48 Byte Slave C 38 Byte Figure 26: Data exchange between master and slaves Incorrect station address assignment Slave A: station 1 Slave B: station 2 Slave C: station 3 The subdivision of the communication buffer (COB) in the master is then as follows:…
  • Page 77
    Optimizing the exchange of send and receive data Send Receive free Byte Byte Figure 27: Subdivision of the COB with incorrect station address assignment Sequence of communication: 1. Master sends 40 bytes to slave A: Free COB memory at this stage = 50 bytes 2.
  • Page 78
    Appendix Correct station address assignment: The required amount of data can be sent and received successfully by assigning different slave addresses with the topology configurator as follows: Slave A: station 3 Slave B: station 2 Slave C: station 1 Send Receive free Byte…
  • Page 79
    Accessories Accessories Designation Type Description/application Programming cable ZB4-303-KB1 Adapter for programming the PS4-200 with a PC Memory module ZB4-160-SM1 32 Kbyte RAM module for expanding the user program memory and 128 Kbyte flash EPROM Memory module ZB4-032-SR1 32 Kbyte RAM module for expanding the user program memory Memory module ZB4-128-SF1…
  • Page 80
    RDBx.y.0.2 RDBx.y.0.6 Bit, byte PS4-141-MM1 RDBx.y.0.0 RDBx.y.0.1 RDBx.y.0.2 ..RDBx.y.0.77 Bit, byte, word PS4-151-MM1 RDBx.y.0.0 RDBx.y.0.1 RDBx.y.0.2 RDBx.y.0.77 Bit, byte, word PS4-201-MM1 RDBx.y.0.0 RDBx.y.0.1 RDBx.y.0.2 RDBx.y.0.77 Bit, byte, word PS4-401-MM1 RDBx.y.0.0 RDBx.y.0.1 RDBx.y.0.2 RDBx.y.0.6 Byte, word PS4-401-MM2 RDBx.y.0.0 RDBx.y.0.1 RDBx.y.0.2 RDBx.y.0.83…
  • Page 81
    Slave addressing Slave Byte 1 Byte 2 Byte 3 Last byte Data type SBI-AMD3 RDBx.y.0.0 RDBxBx.y.0.1 RDBx.y.0.2 RDBx.y.0.6 Byte, word SBI-AMX RDBx.y.0.0 RDBx.y.0.1 RDBx.y.0.2 RDBx.y.0.6 Byte, word SIS Type 80D0 RDBx.y.0.0 RDBx.y.0.1 RDBx.y.0.2 ..RDBx.y.0.6 Bit, byte, word SIS Type 80EF RDBx.y.0.0 RDBx.y.0.1 RDBx.y.0.2…
  • Page 82
    SDBx.y.0.1 SDBx.y.0.2 SDBx.y.0.5 Bit, byte PS4-141-MM1 SDBx.y.0.0 SDBx.y.0.1 SDBx.y.0.2 SDBx.y.0.77 Bit, byte, word PS4-151-MM1 SDBx.y.0.0 SDBx.y.0.1 SDBx.y.0.2 SDBx.y.0.77 Bit, byte, word PS4-201-MM1 SDBx.y.0.0 SDBx.y.0.1 SDBx.y.0.2 SDBx.y.0.77 Bit, byte, word PS4-401-MM1 SDBx.y.0.0 SDBx.y.0.1 SDBx.y.0.2 SDBx.y.0.5 Byte, word PS4-401-MM2 SDBx.y.0.0 SDBx.y.0.1 SDBx.y.0.2 SDBx.y.0.83…
  • Page 83
    Technical Data Technical Data General Standards EN 61 131-2, EN 50 178 Ambient temperature 0 to 55 °C Storage temperature –20 to 70 °C Vibration resistance 1 g/0 to 150 Hz Shock resistance 15 g/11 ms Vibration Constant 1 g, f = 0 up to 150 Hz see page 83 Programming interface…
  • Page 84
    Appendix Power supply for CPU Rated voltage U 24 V DC Permissible range 20.4 to 28.8 V DC Residual ripple of input voltage < 5% Polarity reversal protection Rated current I Normally 250 mA + 300 mA per LE Inrush current and duration 4 A <…
  • Page 85
    Technical Data Galvanic isolation Galvanic isolation between inputs Input status indication Yes (LEDs) Terminals Plug-in screw terminals Conductor cross-section Flexible with ferrules 0.22 to 1.5 mm Solid 0.22 to 2.5 mm High-speed counter input I0.0 Clock frequency 3 kHz Pulse shape Square Pulse duration 50 %…
  • Page 86
    Appendix Outputs No. of outputs Rated voltage U 24 V DC Permissible range 20.4 to 28.8 V DC Polarity reversal protection ≤ Max. ripple Galvanic isolation in groups Rated current I For “1” signal 0.5 A DC for 24 V DC Lamp load 4 W without series resistor Utilization factor…
  • Page 87
    Technical Data Output status indication Yes (LEDs) Terminals Plug-in screw terminals Conductor cross-section Flexible with ferrules 0.22 to 1.5 mm Solid 0.22 to 2.5 mm Analog output Bit resolution 12 (4096 increments) Total error Normally 0.4% of full scale Output variables 0 to 10 V DC/2 mA Connection type Two-wire connection…
  • Page 89
    Index Addressing Slaves …………..49, 76 Alarm input …………… 8 Analog inputs/outputs …………9 Arrangement of the control cabinet ……. 22 Backup battery …………13, 75 Backup memory …………. 12 Base module (i.e. module 0) ………. 36 Battery Backup …………… 13 Baud rate ……………
  • Page 90
    Index CRC …………….41 Data cable …………..75 Data exchange …………10, 11 Data integrity …………..41 Data plug connector …………75 Data transfer LEDs …………….62 Daylight savings time …………. 14 Device arrangement …………22 Diagnostics …………… 65, 66 Diagnostics byte for Suconet K stations ……
  • Page 91
    Index Suconet K …………..10 Interference …………..22 LED …………….65 LED display …………..9 LEDs …………….9, 13 Status …………….. 12 Light-emitting diodes …………. 65 Lightning protection …………31 Limit values, send and receive bytes ……42 Line …………….40 Local expansion modules ……….
  • Page 92
    Index Operating states (PLC), overview ……..58 Output data …………..41 Parameters, setting …………38 PC, connections …………. 19 Peripheral command …………9 Pin assignments Programming device interface (PRG) ……18 Suconet K interface ………… 20 Plug-in screw terminal ………… 75 Potential equalization ………….
  • Page 93
    Index RS 485 …………….10 Run …………….. 57 Screen connection to reference potential surface ..16 Screen grounding kit …………75 Screening …………… 30 Send bytes …………..41 Setpoint potentiometers ……….10 Setting parameters …………38 Setting the bus terminating resistors ……21 Setup, PS 4-200 ……………
  • Page 94
    Index Summer/winter …………14 Topology configuration, procedure …….. 36 Transfer …………….61 Transfer of program to PLC ……….. 61 Twin-level terminal block ……….75 Up counter ……………. 8 User program test …………55 Ventilation …………… 22 Warm start …………..60 Wiring …………….

a 24 V DC power supply

b Input high-speed counter (3 kHz)

c Alarm input

d 8 24 V DC digital inputs and 24 V DC supply

for the outputs

e Plug-in screw terminal

f LED status display for the inputs

g LED status display for the outputs

h 6 24 V DC/0.5 A digital outputs; short-circuit proof

and overload protectetd 2 analog inputs (0 to 10 V)

1 analog output (0 to 10 V)

i Suconet K interface/serial transparent (RS 485)

j Setpoint potentiometer P1, P2

k S1 Switch for bus terminating resistors

l Programming device interface (PRG)/

serial transparent (RS 232)

m Memory module

n LED status display of the PLC

a Battery

b Reset button

c Terminal for local expansion

d Mode selector switch S2

a 24 V DC alimentazione

b Ingresso contatore veloce 3 kHz

c ingresso interrupt

d 8 ingressi digitali 24 V DC e 24 V DC

alimentazione per uscite

e Morsetto a vite sfilabile

f Visualizzazione di stato a LED degli ingressi

g Visualizzazione di stato a LED degli uscite

h 6 uscite digitali 24 V DC/0,5 A;

protetto da cortocircuito e sovraccarico

2 ingressi analogici (0 a 10 V)

1 uscita analoga (0 a 10 V)

i Interfaccia Suconet K/in serie transparente (RS 485)

j Potenziometro P1, P2

k Interruttore S1 resistenze di terminazione bus

l Interfaccia di programmazione (PRG)/

in serie transparente (RS 232)

m Modulo di memoria

n Visualizzazione a LED di PLC

a Batteria

b Tasto di reset

c Connettore per espansioni locali

d Selettore modo di funzionamento S2

For Immediate Delivery call KMParts.com at (866) 595-9616

a Alimentation secteur 24 V CC Terre de protection

b Entrée compteur rapide (3 kHz)

c Entrée d’alarme

d 8 entrées digitales 24 V CC et 24 V CC

alimentation pur sorties

e Bornier à vis enfichable

f Afficheur d’état DEL entrées

g Afficheur d’état DEL sorties

h 6 sorties digitales 24 V CC/0,5 A;

protection courts-circuits et surchages

2 entrées analogiques (0 à 10 V)

1 sortie analogique (0 à 10 V)

i Liaison Suconet K/séquentiel transparent (RS 485)

j Module d’entrées de consignes

k S1 interrupteur pour résistance de terminaison

de bus

l Liaison pour appareils de programmation (PRG)/

séquentiel transparent (RS 232)

m Module de mémoire

n Afficheur d’état DEL de l’automate

a Pile

b Bouton RAZ

c Connecteur pour extensions locales

d Sélecteur modes de fonctionnement S2

a 24 V DC alimentación

b Entrada de contador rapido 3 kHz

c Entrada de alarma

d 8 entradas digitales 24 V DC y

24 V DC alimentación para las salidas

e Terminal roscado enchufable

f LED visualización entradas

g LED visualización salidas

h 6 salidas digitales 24 V DC/0,5 A; a prueba de

cortocircuitos y seguridad contra sobrecargas

2 entradas analógicas (0 a 10 V)

1 salida analógica (0 a 10 V)

i Interface Suconet K/en serie transparente (RS 485)

j Encoder

k Interruptor S1 para bus resistancias terminales

l Interface aparatos de programmación (PRG)/

en serie transparente (RS 232)

m Módulo de memoria

n LED visualización del PLC

a Pila

b Pulsador Reset

c Regleta de bornes para extensiones locales

d Selector de modo de servicio S2

3/10

1/10

A

06/01 AWA27-1589

Montageanweisung

Installation Instructions

Notice d’installation

Istruzioni per il montaggio

Instrucciones de montaje

PS4-201-MM1

Abmessungen – Dimensions – Dimensioni – Dimensiones [mm]

UL/CSA

1) p. d. Pilot Duty/Maximum operating temperature 55 °C/

Tightening torque 0.6 Nm/AWG 12-28

Power

Supp

ly

# of channels and

Input Rating

# of channels and

Output Rating

24 V DC

0.8 A

8 digital

24 V DC

2 analog

6 digital

24 V DC, 0.5 A

24 V DC, 0.5 A p. d.

1)

1 analog

A

AWB27-1184…

AWB27-1287…

h

Das Gerät ist für den industriellen Einsatz

geeignet (l EN 55011/22 Klasse A).

The device is suitable for use in industrial

environments (l EN 55011/22 Class A).

L’appareil a été conçu pour l’emploi en milieu

industriel (l EN 55011/22 classe A).

L’apparecchio è adatto per uso in ambienti

industriali (l EN 55011/22 Classe A).

El aparato es adecuado para uso en ambiente

industrial (l EN 55011/22 clase A).

79

86

45

134.5

85

87.5

15890601.FM Seite 1 Montag, 15. Januar 2007 3:22 15

Table of Contents for Moeller ps4-201-mm1:

  • 1/10 A 06/01 AWA27-1589 Montageanweisung Installation Instructions Notice d’installation Istruzioni per il montaggio Instrucciones de montaje PS4-201-MM1 Abmessungen – Dimensions – Dimensioni – Dimensiones [mm] UL/CSA 1) p. d. Pilot Duty/Maximum operating temperature 55 °C/ Tightening torque 0.6 Nm/AWG 12-28 Power Supp ly # of channels and Input Rating # of channels and Output Rating 24 V DC 0.8 A 8 digital 24 V DC 2 analog 6 digital 24 V DC, 0.5 A 24 V DC, 0.5 A p. d. 1

  • 10/10 Moeller GmbH, Industrieautomation, D-53115 Bonn © 1997 by Moeller GmbH Änderungen vorbehalten 06/01 AWA27-1589 DE13 Doku/Eb Printed in Germany (01/07) 06/01 AWA27-1589 Bohrschablone M 1 : 1 Template for holes, scale 1 : 1 Gabarit de perçage, échelle 1 : 1 Dima di foratura, scala 1 : 1 Plantilla para taladros, escala 1 : 1 100 40.25 94.25 15.25 100 19.25 M4 EM4/PS4 15890601.FM Seite 10 Montag, 15. Januar 2007 3:22 15 For Immediate Delivery call KMParts.com at (866) 59

  • 7/10 06/01 AWA27-1589 Alternative Schirmerdung – Alternative screen earth – Mise à la terre du blindage au choix – Collegamento alternativo dello schermo a terra – Puesta a tierra alternativa de la pantalla Falls die Schirmerdung auf Seite 6/10 aus Platzgründen nicht möglich ist. In the event that the screen earthing arrangement on Page 6/10 is not possible due to lack of space. Au cas où la

  • 6/10 06/01 AWA27-1589 Schirmerdung – Earthing the screen – Mise à la terre du blindage – Collegamento alla terra dello schermo – Conexión a tierra de pantalla * Signalleitungen (abhängig vom Modul) – Signal cable (depending on module) – Ligne de signaux (en fonction du module) – Conduttore del segnale (dipendente dal modulo) – Línea de señalización (en función del módulo) a für H utschiene – for top-hat rail – pour profilé- support – per guida – para guía simétri

  • 3/10 06/01 AWA27-1589 a 24 V DC power supply b Input high -speed counter (3 kHz) c Al arm input d 8 24 V DC digital inputs and 24 V DC supply for the outputs e Pl ug-in screw terminal f LED status display for the inputs g LED status display for the outputs h 6 24 V DC/ 0.5 A digital outputs; short-circuit proof and overload protectetd 2 analog inputs (0 to 10 V) 1 analog output (0 to 10 V) i Suconet K interfa

  • 2/10 06/01 AWA27-1589 Frontansicht – Front view – Face avant – Vista frontale – Vista de frente Offene Gehäuseklappe Housing cover open Courvercle ouverte Calotta della custodia aperta Tapa abierta a Batterie b Re set-Taste c Stiftleiste für Lok ale Erweiterung d Be triebsarten-Vorwahlschalter S2 a 24-V- DC-Stromversorgung b Eingang: „Sc hneller Zähler“, (3 kHz) c Alar meingang d 8 Digital- Eingänge 24 V DC und 24-V-DC-

  • 4/10 06/01 AWA27-1589 Anschlüsse – Connections – Raccordements – Collegamenti – Conexiones a Schraubklemmen 24-V-DC-Netzanschluss, A nschlussquerschnitt – flexibel mit Aderendhülse 2 x 0, 75 mm 2 bis 1,5 mm 2 – massiv 2 x 0,75 mm 2 bis 2,5 mm 2 b Steckbare Schraubklemme c Anschlussquerschnit te: Alle Klemmen sind für 1 x 1,5 mm 2 oder 2 x 0,75 mm 2 mit Aderendhülse ausgelegt. d Stiftleiste für Lok ale Erweiterungen LE4 e Su conet-K-Anschluss (RS 485)

  • 8/10 06/01 AWA27-1589 Busabschlusswiderstände – Bus terminating resistors – Résistances de terminaison de bus – Resistenci di terminazione bus – Resistencias terminales de bus Batterie – Batery – Pile – Batteria – Pila Speichermodul – Memmory Module – Module de mémoire – Modulo di memoria – Módulo de memoria Schalterstellung im Auslieferungszustand Factory setting Position à la livraison Impostazione di fabbrica Posición de entrega S1: 1 ON 2 ON

  • 9/10 06/01 AWA27-1589 Montage – Fitting – Montaggio – Montaje auf Montageplatte mit 35-mm-Hutschiene a (senkrecht ohne LE oder waagerecht) on mounting plate with 35 mm top-hat rail a (vertical without LE or horizontal) sur plaque de montage avec profilé-support 35 mm a ( vertical sans LE ou horizontal) su piastra di montaggio con guida DIN 35 mm a (verticale senza LE o orizzontale) sobre placa de montaje con guía simétrica de 35 mm a (vertical sin LE ó horizontal) auf Montageplatte (senkre

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of Moeller ps4-201-mm1 device using right now.

AlexTihon

Posts: 7
Joined: Wed Jan 27, 2016 6:35 pm

moeller ps4-341-mm1

Привет всем.
есть в наличии данный ПЛК.
скачал софт Sucosoft S40 (demo).
в контроллере крутиться какой то проект.
как мне его выгрузить на компьютер (сделать бэкап)?
захожу в transfer manager и там не нахожу как скачать исполняемый файл на компьютер


Ryzhij

Posts: 406
Joined: Mon Mar 31, 2008 11:29 am
Location: Ryazan, Russia

Re: moeller ps4-341-mm1

Post

by Ryzhij » Sat Jan 30, 2016 6:00 am

Адаптер от Мёллера Вы подключали?


bugorka

Posts: 19
Joined: Tue Jul 25, 2006 10:58 am
Location: Russia

Re: moeller ps4-341-mm1

Post

by bugorka » Mon Feb 01, 2016 7:41 am

Из этого контроллера (или из его флэш памяти) Вы сможете выкачать (а потом назад закачать) только оттранслированный загрузочный код программы…
Редактировать Вы его из под редактора S40 не сможете… Для выгрузки нужно установить S40 (лучше ставьте самую последнюю со всеми апдейтами)
— спаять кабель для подключения к COM порту компьютера … ну дальше все в Help описано…


AlexTihon

Posts: 7
Joined: Wed Jan 27, 2016 6:35 pm

Re: moeller ps4-341-mm1

Post

by AlexTihon » Tue Feb 02, 2016 5:44 pm

bugorka wrote:Из этого контроллера (или из его флэш памяти) Вы сможете выкачать (а потом назад закачать) только оттранслированный загрузочный код программы…
Редактировать Вы его из под редактора S40 не сможете… Для выгрузки нужно установить S40 (лучше ставьте самую последнюю со всеми апдейтами)
— спаять кабель для подключения к COM порту компьютера … ну дальше все в Help описано…

мне и нужен оттранслированный (скомпилированный) файл, редактирование не нужно. установил S40. спаял кабель, подключился. вижу диагностическую информацию о контроллере. не могу найти как выгрузить программу.
может быть проблема в том что я установил S40 v5 ДЕМО версии? у вас случайно нет рабочей версии данного софта и key для него?


bugorka

Posts: 19
Joined: Tue Jul 25, 2006 10:58 am
Location: Russia

Re: moeller ps4-341-mm1

Post

by bugorka » Wed Feb 03, 2016 5:40 pm

Скачать можно с ftp.moeller.net … да и в интернете полно…и на этом форуме…
ключ 778297899217…
зачем Вам оттранслированный файл? … если в контроллере флешка… можете через нее перетащить программу в другой контролер


AlexTihon

Posts: 7
Joined: Wed Jan 27, 2016 6:35 pm

Re: moeller ps4-341-mm1

Post

by AlexTihon » Wed Feb 03, 2016 7:35 pm

интересно же. тогда вопрос как активировать демо версию Sucosoft? куда вводить этот ключ?


bugorka

Posts: 19
Joined: Tue Jul 25, 2006 10:58 am
Location: Russia

Re: moeller ps4-341-mm1

Post

by bugorka » Thu Feb 04, 2016 6:28 am

Я не очень понимаю что Вы там установили…? S40 v5 без ключа просто не ставится…- там нет демо версии…при установке он требует серийник…
Для чего Вам это? Я уже писал что для загрузки/выгрузки оттранслированного кода можно и флешкой обойтись…


AlexTihon

Posts: 7
Joined: Wed Jan 27, 2016 6:35 pm

Re: moeller ps4-341-mm1

Post

by AlexTihon » Thu Feb 04, 2016 6:47 pm

bugorka тут Вы не правы. вот скачал очередной раз Sucosoft. по вашей ссылке ftp://ftp.moeller.net/AUTOMATION/DOWNLO … O_VERSION/. устанавливается только Демо версия и не требует при установке никаких ключей. можете попробовать для интереса. в интернете тоже не нашел ссылок на рабочую НЕ демовскую версию. если у вас есть ссылка или сама прога поделитесь ?


vlad2006gr

Posts: 1032
Joined: Tue Nov 20, 2007 7:08 pm
Location: Belarus

Re: moeller ps4-341-mm1

Post

by vlad2006gr » Fri Feb 05, 2016 11:11 am

AlexTihon wrote:устанавливается только Демо версия

Так ее и ставьте. Потом в реестре по пути HKEY_LOCAL_MACHINESOFTWAREMoeller SoftwareSucosoft5.0Module
измените «DEMO»=»DEMOVERSION» на «Full»=»VOLLVERSION»
Скачайте , откуда демку брали, апдейт 5,05 и установите. при установке укажите ключ 776296179657
Теперь у вас полная версия.


AlexTihon

Posts: 7
Joined: Wed Jan 27, 2016 6:35 pm

Re: moeller ps4-341-mm1

Post

by AlexTihon » Sat Feb 06, 2016 3:54 pm

vlad2006gr wrote:
Теперь у вас полная версия.

Спасибо ) активировалась.
только скачать файл с контроллера так и не получилось. открыл Test and Comisioning, выполнил коннект, открыл окно Transfer file manager. на карте памяти отображается файл «*.pcd». в справке нашел, что можно передать файл с флешки на комп но только не с расширением pcd. а на вкладке Controller можно сделать только рестарт и больше никаких функций. то есть, если нет флешки из самого плк вообще нельзя скачать файл? в ps4-201 из под дос можно хоть с шлешки , хоть из оперативки (если нет флешки) выгрузить проект, а тут никак


vlad2006gr

Posts: 1032
Joined: Tue Nov 20, 2007 7:08 pm
Location: Belarus

Re: moeller ps4-341-mm1

Post

by vlad2006gr » Sat Feb 06, 2016 7:44 pm

AlexTihon wrote: можно передать файл с флешки на комп но только не с расширением pcd

*.PCD это и есть код программы. *.OSF — операционная система ПЛК. У moeller без карточки не обойтись. Можно с контроллера на пустую карту записать программу, см- http://www.plctalk.net/qanda/showthread.php?t=78467 , или с карты в контроллере в ПК. С самим контроллером можно только сравнить программу, если она у вас есть.
С карты памяти вроде так- Transfer/File Manager->Memory medium-> выбираем MC->выбираем файл на МС *.PCD-> Transfer to PRG
Не забываем, что форум это не руководство к действию, все делаем на свой страх и риск. Простое выключение и включение контроллера, как по ссылке выше, может вызвать потерю программы.



nemo852

Posts: 1
Joined: Wed Jun 20, 2018 9:56 am

Re: moeller ps4-341-mm1

Post

by nemo852 » Wed Jun 20, 2018 10:09 am

Добрый день. Подскажите, на контроллере PS4-341-MM1 мигают 1(Ready) и 3(Not Ready) светодиоды, что это означает? я так подозреваю, контроллер говорит что программы нет и он готов программироваться. Но вот беда, собрав кабель для подключения по RS232, скачав программу как сказано выше, не могу подключиться к контроллеру. Подскажите, возможно что контроллер совсем заглючил, стёр рабочую программу и ушел в стопор по операционной системе, что я не могу к нему подключиться?

Кому интересно: поменяв Rx/Tx (2 и 5 контакты) местами — связь с контроллером получил. При проверки программы и карты памяти выскакивала надпись «PLC in BOOT status» вылечилось это Transfer/File Manager -> programmer-> операционная система -> загрузить в PLC, по окончанию загрузки 1(Ready) и 3(Not Ready) прекратили мигать, загорелась 1(Ready). Дальше как описывалось выше, из карты памяти загрузил программу в плк.


ovy1983

Posts: 1
Joined: Tue Oct 05, 2021 5:14 am

Re: moeller ps4-341-mm1

Post

by ovy1983 » Tue Oct 05, 2021 5:27 am

Здравствуйте! Прошу помочь с настройкой контроллера Moeller PS4-341.Есть софт, есть исполняемый файл. Контроллер без карты памяти. После заливки исполняемого файла, контроллер переходит в режим ready, а как перевести в режим run не могу понять.


and1534

Posts: 2
Joined: Sun Mar 27, 2022 1:46 pm

Re: moeller ps4-341-mm1

Post

by and1534 » Sun Mar 27, 2022 1:57 pm

Добрый день!
Случайно на включенном moeller ps4-341-mm1 вытащили флеш-память. Ушел в Ready, ни на что больше не реагирует..
Подскажите, насколько этот казус критичен для ПЛК? Можно ли восстановить работоспособность?


andreyit

Posts: 176
Joined: Wed Dec 26, 2018 5:39 pm

Re: moeller ps4-341-mm1

Post

by andreyit » Sun Mar 27, 2022 6:03 pm

and1534 wrote: ↑

Sun Mar 27, 2022 1:57 pm


Добрый день!
Случайно на включенном moeller ps4-341-mm1 вытащили флеш-память. Ушел в Ready, ни на что больше не реагирует..
Подскажите, насколько этот казус критичен для ПЛК? Можно ли восстановить работоспособность?

А вы сперва пытались мануал почитать (страница 59 или 62)? Перевести в run? Там есть переключатель чтобы сперва его в run переключить (среднее положение 2), а потом один раз нажать кнопку reset — если после этого он не ушел в работу, но только подключившись можно сказать что с ним.


and1534

Posts: 2
Joined: Sun Mar 27, 2022 1:46 pm

Re: moeller ps4-341-mm1

Post

by and1534 » Thu Mar 31, 2022 7:11 am

Да, пришлось перезалить программу через Sucosoft S40 и получилось сделать Coolstart


Понравилась статья? Поделить с друзьями:
  • Mokeru красящий шампунь инструкция по применению
  • Modi лаванда инструкция для выращивания
  • Moisture meter user guide инструкция на русском языке
  • Modet турецкие таблетки инструкция по применению на русском языке
  • Moisture intensive illuminating lotion ампулы инструкция по применению