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
Спасибо. Мы свяжемся с вами как можно скорее.
•
Language independent
•
Simple configuration via the backlit display
•
Input for external setpoint device
Optigo OP10 is a pre-programmed controller that can
be used for control of temperature in air handling and
heating applications. It is a stand-alone controller for
simpler applications. Optigo is extremely easy to install,
commission and control.
Optigo uses a display with an encoder knob, making
its built-in menu system very easy to use. Settings
are entered by turning the encoder knob to a desired
parameter/value. A value is then approved by pressing the
knob.
Models
The Optigo series comprises two different models, OP5U
and OP10.
OP5U has 5 in-/outputs and OP10 has 10 in-/outputs.
OP10 is available in two models:
• OP10 with 24 V AC supply voltage
• OP10-230 with 230 V AC supply voltage
Applications for OP10 and OP10-230
Optigo OP10 is pre-programmed with a choice of five
different control modes:
1. Supply air control
2. Supply air control with outdoor compensation
3. Cascaded room / extract air temperature control
4. Radiator circuit control
5. Domestic hot water control
Optigo OP10
OP10
Pre-programmed, configurable controller for
simple applications
The Optigo OP10 range of controllers controls
temperature. They are intended for DIN-rail mounting.
•
Pre-loaded with several application modes
•
24 V or 230 V AC supply voltage
•
Week-based clock / calendar function
Inputs and outputs
Optigo OP10 has:
• 2 analogue inputs, PT1000
• 1 SPI input for an external setpoint device
• 1 universal input, PT1000 or digital
• 2 digital inputs
• 3 digital outputs
• 2 analogue outputs, 0…10 V DC
Internal clock
Optigo OP10 has a built-in week-based real time clock
with a number of different scheduler alternatives.
Easy to install
Optigo is suitable for DIN-rail or cabinet mounting. Since
the terminals are detachable, all connections can be made
before Optigo is installed.
Optigo has been developed in accordance to our Ready-
Steady-Go concept, simplifying every step from installation to
management.
revision
06 2017
Display and encoder knob
All setting and configuration is performed using the
display and encoder knob on the front of the controller.
The menu information shown on the display is organised
in a tree fashion. By using the knob you can move in
between menus, set values etc.
In any of the configuration menus, pressing the encoder
knob will activate change mode. You can then turn the
knob to move between choices or set values. A second
press of the knob will accept the choice.
The menu system is divided into three levels:
• Base level: view mode
• The 3 second level: clock and scheduler program
• The 10 second level: configuration menus
Display information
The display can show the following information
Outdoor compensation
configured
Cascade control
Temperature control
Radiator circuit control
Domestic hot water control
Fan run indicator
2
Turn: move up/down in
the menus
Press: enter new menu
or accept new setting
Press for 3 seconds
for time menu,
or 10 seconds for
configuration menu.
Alarm indicator
Menu holds
Active 0…10V
changable values
input signal
or 3-position output
indicator
Optigo OP10
Display — Base level
This is an example of the display when in Base level view
mode. It is normally shown when there is no operator
activity.
The Base display shows current time and actual value.
There are bar-graphs showing the current output levels
together with symbols showing how the outputs have
been configured (Heating, Cooling or Damper etc).
There is also a symbol showing which of the five control
modes is configured, as well as an alarm symbol that is
displayed in the event of an alarm condition. The fan
symbol (control modes 1, 2 and 3 only) is lit as long as
the fan indication input is activated.
To see the values and status of all in- and outputs, simply
turn the knob counter-clockwise until the text I/O is
displayed and then press it. To return to the Base display,
click on the knob and then turn it clockwise.
Configuration level
Menu number
AO1 Graphic output signal
Control mode 1 only
Bargraph AO1 output level
Bargraph AO2 output level
AO2 Graphic output signal
Control mode 1 only