Secop 105n4627 контроллер инструкция на русском

  • Contents
    Table of Contents

  • Bookmarks

Quick Links

1 Purpose

In this procdeure we describe the task to control the released Setup values which are programmed

into the Secop GP electronic device

2 Area of Application

Is relevant for all divisions which are working with the Secop GP electronic controller

3 Terms

4 Responsibility

Contents

5.1

5.1.1

5.1.2

5.2

5.2.1

5.2.2

5.2.3

5.2.4

responsible department:

Labor

electronic device Secop GP 105N4627

creator:

latest change:

P. Moderer

04.12.2012

A p r i n t e d v e r s i o n o f t h i s d o c u m e n t i s n o t p a r t o f t h e r e v i s i o n s e r v i c e !

authorized by:

M. Horn

typ — number — version

page

WI-550_en — 8

Seite 1 von 21

loading

Summary of Contents for AHT Secop GP 105N4627

5 Procedure

Test procedure (controller must be connected to power supply):

To check the set desired value, press the «+/-» key briefly once. The menu item «desired

1 step.

temperature» appears in the display for approx. 5 secs. The set temperature is displayed as a

hexadecimal value, e.g. «A1». By pressing the «+/-» key again, in a «U»-shaped unit for

example you can switch to another set desired value, e.g. «A3». The last hex value shown in

the display is always considered to be the set desired value.

2 step.

Wait until the display again shows the current temperature in the display.

To get into the address menu of the controller, the «standby/reset» key should be pressed

3 step.

briefly once. In the display, «Adr» is shown alternating, for example, with «1» for bus address 1.

By pressing the key «+/-» (up) or «standby/reset» (down), the bus address can be adjusted

between 1 and 247.

To store the bus address, press the «man. defrost» key once to quit the address menu and get

4 step.

back to the current temperature.

To get into the main menu, press the «+/-» key three times to get to the code input for the

5 step.

main menu. «Cod» and «0» are displayed. The correct code should be entered using the key

«+/-» (up) or «standby/reset» (down). The code can be a number between «-999 and +999». If

the correct code is shown in the display, this should be confirmed using the «man. defrost»

key in order to get into the main menu. The first enabled menu item is then displayed.

To change a selected value, the parameter must be confirmed using the «man. defrost» key in

6 step.

order get to the parameter value. This should then be changed using the key «+/-» (up) or

«standby/reset» (down). To store the set value, the «man. defrost» key must be pressed.

Following this you return to the set parameter.

7 step.

If you are in the main menu, you can be switched through the parameter level using the key

«+/-» (up) or «standby/reset» (down). If no change occurs for approx. 30 seconds, the

controller returns from the main menu to the current temperature display.

8 step.

Following this the controller will again function normally.

responsible department:

Labor

creator:

latest change:

P. Moderer

04.12.2012

A p r i n t e d v e r s i o n o f t h i s d o c u m e n t i s n o t p a r t o f t h e r e v i s i o n s e r v i c e !

authorized by:

M. Horn

typ – number — version

page

WI-550_en — 8

Seite 2 von 21

Table of Contents for AHT Secop GP 105N4627:

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 8 von 21 Program Number delivery Setpoint High alram limit Low alarm limi Weighting for alarm thermostat S4 Application Selection Applic

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 21 von 21 6 Related Documents Archiving of all documents is generally regulated in SP-303. Abbreviation Name 7 Changes Version Date Person Change WI-550-1 25.06.2012 M. Horn Newly created WI-550-2 05.09.2012 M.

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 1 von 21 electronic device Secop GP 105N4627 1 Purpose In this procdeure we describe the task to control the released Setup values which are programmed into the Secop GP electronic device 2 Area of Application Is rele

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 3 von 21 5.1 Setups for Cabinets with Plastic Tank 5.1.1 Setups for Cabinets with AD Function and with Buzzer Program Number delivery Setpoint High al

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 16 von 21 Program Number delivery Setpoint High alram limit Low alarm limi Weighting for alarm thermostat S4 Application Selection Application enable A1 Application enable A2 Application enable A3 Applicatio

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 6 von 21 Program Number delivery Setpoint High alram limit Low alarm limi Weighting for alarm thermostat S4 Application Selection Application enable A1 Application enable A2 Application enable A3 Application enable A4 Application enable A5 Allow local display to sta

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 10 von 21 5.2 Setups for Cabinets with ALU Tank 5.2.1 Setups for Cabinets with AD Function and with Buzzer Program Number delivery Setpoint High alram limit Low alarm limi Weighting for alarm thermostat S4 App

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 5 von 21 Program Number delivery Setpoint High alram limit Low alarm limi Weighting for alarm thermostat S4 Application Selection Application enable A1 Application enable A2 Appl

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 18 von 21 5.2.4 Setups for Cabinets without AD Function and without Buzzer Program Number delivery Setpoint High alram limit Low alarm limi Weighting for alarm thermostat S4 Application Selection Application enable A1

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 13 von 21 Program Number delivery Setpoint High alram limit Low alarm limi Weighting for alarm thermostat S4 Application Selection Application ena

  • A printed version of this document is not part of the revision service! responsible department: creator: latest change: authorized by: typ – number — version page Labor P. Moderer 04.12.2012 M. Horn WI-550_en — 8 Seite 4 von 21 5.1.2 Setups for Cabinets with AD Function and without Buzzer Program Number delivery Setpoint High alram limit Low alarm limi Weighting for alarm thermostat S4 Applicat

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of AHT Secop GP 105N4627 device using right now.

Download Setup of AHT Secop GP 105N4627 Control Unit for Free or View it Online on All-Guides.com.

AHT Secop GP 105N4627 Setup - Page 1

1

AHT Secop GP 105N4627 Setup - Page 2

2

AHT Secop GP 105N4627 Setup - Page 3

3

AHT Secop GP 105N4627 Setup - Page 4

4

AHT Secop GP 105N4627 Setup - Page 5

5

AHT Secop GP 105N4627 Setup - Page 6

6

AHT Secop GP 105N4627 Setup - Page 7

7

AHT Secop GP 105N4627 Setup - Page 8

8

AHT Secop GP 105N4627 Setup - Page 9

9

AHT Secop GP 105N4627 Setup - Page 10

10

AHT Secop GP 105N4627 Setup - Page 11

11

AHT Secop GP 105N4627 Setup - Page 12

12

AHT Secop GP 105N4627 Setup - Page 13

13

AHT Secop GP 105N4627 Setup - Page 14

14

AHT Secop GP 105N4627 Setup - Page 15

15

AHT Secop GP 105N4627 Setup - Page 16

16

AHT Secop GP 105N4627 Setup - Page 17

17

AHT Secop GP 105N4627 Setup - Page 18

18

AHT Secop GP 105N4627 Setup - Page 19

19

AHT Secop GP 105N4627 Setup - Page 20

20

AHT Secop GP 105N4627 Setup - Page 21

21

A printed version of this document is not part of the revision service!

electronic device Secop GP 105N4627

1 Purpose

In this procdeure we describe the task to control the released Setup values which are programmed

into the Secop GP electronic device

2 Area of Application

Is relevant for all divisions which are working with the Secop GP electronic controller

3 Terms

4 Responsibility

Contents

5.1 Setups for Cabinets with Plastic Tank ……………………………………………………………. 3

5.1.1 Setups for Cabinets with AD Function and with Buzzer ………………………………. 3

5.1.2 Setups for Cabinets with AD Function and without Buzzer ………………………….. 4

5.2 Setups for Cabinets with ALU Tank …………………………………………………………….. 10

5.2.1 Setups for Cabinets with AD Function and with Buzzer …………………………….. 10

5.2.2 Setups for Cabinets with AD Function and without Buzzer ………………………… 11

5.2.3 Setups for Cabinets without AD Function and with Buzzer ………………………… 17

5.2.4 Setups for Cabinets without AD Function and without Buzzer ……………………. 18

SLV ControLLer 105n46xx SerieS 4 | Manualzz

With more than 50
years of experience in
compressor technology
and highly committed
employees, our focus is
to develop and apply the
advanced compressor
technologies to achieve
standard setting
performance for leading
products and businesses
around the world.
SLV Controller
105N46xx Series
Operating Instructions
4
TOOL COOL
Flexible control settings
www.secop.com
SETTING THE STANDARD
2
3
Table
of Contents
1.
Introduction................................................................................................ 5
1.1 Applications............................................................................................5
1.2 Capabilities ............................................................................................5
1.3 Operating Conditions .............................................................................5
1.4 Programming Interface .........................................................................5
1.5 Hardware Interface Description.............................................................6
1.6 Functions................................................................................................7
2.
Installation................................................................................................. 8
2.1 Checklist.................................................................................................8
2.2 Connect Cables.......................................................................................9
2.3 General Wiring........................................................................................9
2.4 Display...................................................................................................10
2.5 Modbus RTU..........................................................................................10
2.6 Mains / Earthing / Compressors..........................................................10
2.7 General System Design Hints..............................................................11
3.
User Interfaces......................................................................................... 12
3.1 Display CRA 172 Operations.................................................................12
3.2 Operating using TOOL4COOL...............................................................12
3.3 Operation using ADAP-KOOL®............................................................12
3.4 Operating using Third Party Software..................................................12
4.
5. Description of Functions . ........................................................................ 13
4.1 Application Selector.................................................................................13
4.2 Modbus Addressing..................................................................................14
4.3 Temperature Acquisition .........................................................................15
4.4 Temperature Logger................................................................................17
4.5 Temperature Alarms................................................................................18
4.6 Reference for the Capacity Controller.....................................................19
4.7 Compressor Capacity Control..................................................................20
4.8 Safety Function.........................................................................................22
4.9 Emergency Cooling Function...................................................................23
4.10 Defrost Control Function........................................................................24
4.11 Melt Function..........................................................................................29
4.12 Case Cleaning Function.........................................................................30
4.13 Condenser or Compressor Compartment Fan Control........................31
4.14 Evaporator Can Control..........................................................................32
4.15 Blind Control Function...........................................................................34
4.16 Light Control Function...........................................................................35
4.17 Real Time Clock and Control Timer......................................................36
4.18 Alarm Handler........................................................................................37
4.19 Event Logging System............................................................................38
4.20 Service Mode..........................................................................................41
4.21 Local Display Indications and Menu Structure.....................................43
4.22 Configuration of Relays..........................................................................44
4.23 Configuration of low Voltage I/O............................................................48
4.24 Storing and Restoring to Factory Settings............................................49
Parameters............................................................................................... 50
6. Modbus..................................................................................................... 88
7.
Technical Data.......................................................................................... 91
7.1 SLV15CNK.2 Compressor R290...........................................................91
7.2 SLV12CLK.2 Compressor R404A/R507................................................94
7.3 SLV 105N46xx Series Controller..........................................................95
7.4 Dimensions...........................................................................................97
8. Ordering................................................................................................... 98
4
1.
Introduction
1.1
Applications
The SLV General Purpose controller 105N46xx regulates temperatures in refrigeration appliances,
including supermarket refrigeration, freezer cabinet systems and industrial kitchens.
1.2
Capabilities
The controller is fully functional in every operation required for modern refrigeration control. The
controller connects to a range of interfaces such as potentiometers, LED displays, PC software and
bus monitoring systems. The controller features an internal temperature and event logging system and
general purpose interface for broad and flexible application.
1.3
Operating Conditions
The compressor should be operated under the following conditions:
⋅⋅ Line voltage: 230 V AC 50 Hz
⋅⋅ Ambient temperature: 0 to 43°C
The controller should not be used in ambient air containing acid or alkaline. To ensure an optimal service
life, the ambient temperature should be kept as low as possible (ambient temperature range for operation:
0 to 38°C compartment temperature, humidity 30 – 90%). The ventilation holes on the control units should
not be covered and no objects should be lent up against the enclosure. The control system should not
come into contact with dust or water. Ambient temperature range for storage: - 20°C to 70°C
1.4
Programming
Interface
The controller can be accessed via:
⋅⋅
⋅⋅
⋅⋅
⋅⋅
The local display CRA 172
The Secop PC Service tool TOOL4COOL® together with a Bluetooth® gateway
The Danfoss software tool, ADAP KOOL® via Modbus
A custom interface - please contact Secop for further information regarding custom interfaces.
5
1.5
Hardware Interface
Description
Supply
These are the supply lines.
The L and N supply terminals must be from the main supply.
The E must be connected to protective earth.
Please refer to the hardware specifications for the approved operating conditions.
Relay section
There are 5 relays which can be used for several purposes; they can be configured by the software
parameters. The R1, R2, R3 and R4 are active outputs that direct the supply voltages to the output
terminals. The R5 is galvanic separated and can be used for either switching external supply voltage or
switching external auxiliary signals.
Please refer to the hardware specifications for approved operating conditions.
Modbus
This galvanic insulated terminal is used to connect a bus system according to the Modbus standard.
Please refer to the hardware specifications for approved operating conditions.
Sensors
There are up to 5 temperature sensor inputs available. The use of the sensor can be configured by the
software parameters. Generally the S3 and S4 sensors are used to measure the product’s temperature, S5
for controlling defrost, S3b for auxiliary functions and S6 for the temperature logger system.
Please refer to the hardware specifications and accessory listings for specification, approved operating
conditions and sensors.
Digital Input DI
The digital input can be used to connect the auxiliary contact device, external for the door sensor and light
switch. The controlling function can be selected by the software parameters.
Please refer to the hardware specifications for approved operating conditions.
Display
The display connection is used to connect the Secop display CRA 172.
Please refer to the hardware specifications for approved operating conditions.
Safety hint:
Sensors, DI and Display connectors are not insulated. Each appliance needs an insulation which is
acceptable for 230 V environment.
6
1.6
Functions
The main functions of the SLV compressor are:
⋅⋅ Motor control for the energy-optimised variable speed brushless DC motor used in the Secop SLV
compressor
⋅⋅ Management of minimum and maximum run times
⋅⋅ Condenser and compressor fan control
⋅⋅ Temperature measurement and algorithms for determining the temperatures in the cooling application
⋅⋅ PI control to determine the required cooling capacity
⋅⋅ Display control (optional)
⋅⋅ Control menus to change the operating status or set parameters
⋅⋅ Alarm system reporting faults on the display, with a buzzer, via the Modbus interface, or via the alarm
relay
⋅⋅ Data logging system to store events in the memory of the control unit. Data logs can be read via the
system bus
⋅⋅ Hot gas defrost system
⋅⋅ Cold storage fan control module
⋅⋅ Modbus communication for supermarket monitoring systems
The controller also features integrated monitoring of the operating conditions and takes corrective action
to prevent any damage to the electronics, which may occur in the event of an overload.
The following monitoring functions ensure that operating conditions remain within the acceptable range:
⋅⋅ Temperature sensor on the printed circuit boards to monitor the temperature of the electronics in the
enclosure.
⋅⋅ Temperature sensor to monitor temperature in the motor inverter.
⋅⋅ Monitoring for correct motor speed; motor speeds outside the permissible range can damage the
valves and bearings.
⋅⋅ Inadequate line voltage due to fluctuations in the line supply.
⋅⋅ Locked rotor caused by excessive pressure.
Other advantages:
⋅⋅ Minimal start current required due to non-simultaneous compressor and fan start up schedules.
⋅⋅ Controlled restart.
⋅⋅ Control of the pressure equalization time.
7
2.
Installation
Installation involves the following steps:
⋅⋅ Checklist
⋅⋅ Connect cables
⋅⋅ Install gateway driver
⋅⋅ Set Modbus address in controller
⋅⋅ Software installation and configuration
2.1
Checklist
Check that you have the following before starting installation:
Secop SLV 105N46xx series controller
Tool4Cool LabEdition software installation CD
Service Product key for SLV controller
NTC temperature sensors (colour-coded)
Display CRA 172
(cable must be ordered separately)
Secop Bluetooth gateway with
USB power supply
⋅⋅ Gateway
⋅⋅ USB power supply
⋅⋅ DSUB-9 / RJ45 adaptor
⋅⋅ RJ45 Ethernet patch cable
(not available from Secop)
8
- on request -
2.2
Connect Cables
The maximum cable length should not exceed 3 metres for all internal and external applications. A cable
length of more than 3m could alter the EMI performance. In this case, the customer must make application
specific inquiries to determine requirements for the certification of cooling applications. Under normal
circumstances the supply line and the communication lines are longer; it is recommended to follow the
installation guideline for the Modbus.
All protective earth lines, PE, in the application must be collected to one star point. This prevents loop
currents which could cause problems concerning the electronic components, communication lines and
sensors. The star-point is normally a screwed terminal on the chassis.
The compressor must be connected directly to PE; due to the low voltage decree. The PE connection by the
motor cable shield has a more functional cause and is not sufficient as a safety relevant connection, so in
case of an error it is not able to carry the whole current.
The cable shield of the motor cable must have a low impedance connection to the compressor. The connection
should be made to the compressor where the shield has a large surface area. The newer compressors will
come with a clamp instead of a plug for the shield.
Signal and data lines can be put together but divided from the 230 Vac power lines, including those lines
which are switched by the internal relays.
The relay switched lines may be put together with the supply line as long as the other lines are not
carrying current disturbances. The preferred way of installation heavily relies on the switched loads. In
case of doubt the lines should be installed separately; to avoid coupling of disturbance between the lines.
Connecting the Modbus communication line between two devices when the cable is installed outside the
building or between two buildings is not allowed. This prevents potential induction problems, in case of
lightning.
2.3
General Wiring
9
2.4
Display
The controller has a connection port for a CRA 172 display for local operation and temperature readouts.
Furthermore it’s possible to use the display for alarm indication, depending on whether the function is
enabled.
As well as the 3½ digit LED display, the CRA 172
also has 3 buttons.
2.5
Modbus RTU
The bus can be connected to a bus monitoring system based on the Modbus specification for
RS-485 based interfaces. The bus connection can be used for remote monitoring of the cabinet or for local
service by means of the Tool4Cool® service tool.
For further information, please refer to section 6, Modbus
2.6
Mains / Earthing /
Compressor
10
2.7
General System
Design Hints
Airflow
3 m/s
Operating conditions
-10 °C to 43 °C - humidity < 90 % rH non condensing
Storage conditions
-20 °C to 70 °C - humidity < 90 % rH non condensing
Supply voltage
230 V (+15 % / - 20 %)
Frequency
50/60 Hz
Input power rating
max 1000 W at 230 V (+15 % / - 20 %)
11
3.
User Interfaces
3.1
Display CRA 172
Operations
The different parameters of the SLV controller can be accessed via the local display or via the Modbus. In
this section, only the local display interface will be described.
The display CRA 172 performs the following functions:
Daily operation of the cooling appliance, readout of measurements and status of the refrigeration system,
actual temperature, alarms, defrost activation, stop mode, setting of parameters, reset of alarms and
more.
By entering the correct access code, it’s also possible to get into the service level of the controller.
Besides the numeric display, there are 4 additional LED’s which show the status of Alarm, Defrosting,
Service and Cooling.
To access the different parameters of the SLV controller for the local display interface, there are three
different access levels. Each level can be protected with an individual access code, defined by the
manufacturer of the cooling appliance. If a level is protected with an access code, this code must be
entered first.
If the SLV controller is accessed via both the CRA 172 and the Modbus at the same time, the latest
modified value for a setting will be stored as the final.
3.2
Operating using
TOOL4COOL®
The controller can be programmed and optimized via the Bluetooth® gateway from a PC using the
Tool4Cool® software. An example of the Tool4Cool® user interface showing the main parameter groups of
the SLV compressor is shown below. For details please look into the separate documentation
Example:
3.3
Operation using
ADAP-KOOL®
The Danfoss ADAP-KOOL® software is used to control supermarket refrigeration systems. Please refer
to existing documentation for operating instructions and further information. The literature number (in
brackets) might change according to version and language:
⋅⋅ Data communication between ADAP-KOOL® refrigeration controls – Installation guide (RC8AC602)
⋅⋅ Service Tool AK-ST 500 Software for operation of AK controllers – Manual (RS8ES402)
⋅⋅ ADAP-KOOL® Refrigeration control systems – Catalogue (RK0YG402)
3.4
Operating using
Third Party Software
12
The SLV controller can also be accessed from a third party front end. For details please contact
[email protected] and refer to separate documentation available from Secop.
4.
Description of Functions
4.1
Application selector
4.1.1 Purpose
Many light commercial cooling applications are supposed to cool a variety of goods.
The cooling of different types of goods requires specific temperature settings and functions of defrosting,
fan control etc. These settings are considered to be application dependent.
The selection of the application can be done by the end user, timer based or pre defined from the factory.
4.1.2 Functional description
Using the application selector, it is possible to select up to five different sets of settings which provide the
SLV controller with different functions or simply different temperature settings.
The selection of the actual application can be done by the daily user via the local operation display, the
internal control timer, digital input or as a factory selection at the OEM.
In the parameter overview the default settings for all parameters are shown for each of the five possible
applications. Furthermore, the overview indicates whether a setting can be set differently for each of
the five applications or if this setting is one common setting for all applications. If different settings are
possible in the particular applications, this is indicated with an “x” in the column “Multi apps”
Before an application can be selected, this application must be enabled.
Application selection by the daily user:
If more than one application is enabled, the daily user can select one of the enabled applications by
pressing the middle button on the display. If more than two applications are enabled, repeatedly pressing
the middle button switches between the applications.
If the digital input DI1 is configured for application change over, the predefined application will be selected,
as soon as the DI1 is closed. As soon as the DI1 is disconnected, the selection of application depends on
the remaining settings.
If automatic application change over is desired, this can be achieved by using the control timer to select
another application during the active timer. As an alternative, it is possible to force each application into
another application, as long as the controller is in night mode.
4.1.3 Restrictions
For all the settings which can be programmed differently in the five applications, this is only made possible
if the application has first been selected. This means that each application has to be programmed
separately, by enabling and selecting the application prior to the programming.
4.1.4 Dependencies
None
13
4.2
Modbus Addressing
4.2.1 Purpose
The SLV controller can be mounted in a Modbus network of up to 247 controllers. To recognize the different
controllers on the network, each controller must have its own, unique address.
4.2.2 Functional description
The Modbus address can be set either via the T4C service tool or the local display CRA 172. If the
controller has a password, this must be entered first.
The address range can be set in the range from 1 to 247. Parameter 'Modbus address' (o03).
4.2.3 Restrictions
If the Modbus address is modified via the T4C, the user must ensure that the new address is within the
setting range of the T4C, otherwise the communication to the controller will be lost, until the correct
address range has been selected on T4C and the network has been scanned again.
4.2.4 Dependencies
None
14
4.3
Temperature
acquisition
4.3.1 Purpose
The temperature acquisition system handles all the temperature measuring related issues, such as
sensor selection, weighting of sensors and sensor error detection.
4.3.2 Functional description
The SLV controller has 5 sensor inputs. The S3, S3b, S4 and S5 sensors are compatible with the 5K NTC
sensors. The S6 sensor uses a Pt1000 sensor.
Important remark: The sensor inputs are not galvanic separated and the sensor inputs are connected
directly to the mains supply! For that reason only double isolated sensors must be used.
Weighting of sensors
In some cases it might be necessary to use 2 sensors, to achieve the correct temperature measurement. For
measuring the cabinet temperature, the sensors S3 & S4 can be used, or a mix of these. Furthermore, it’s
possible to use different weighting of the 2 sensors during the day and night time. The parameters “S3/S4.
Weighting for Tact at day” (r15) and “S3/S4 Weighting for Tact at night” (r61) give the weighting for day and
night respectively. If set to 100% only the sensor S4 is used. If set to zero, only the S3 sensor is used.
In the same way, it’s possible to weight the S3/S4 sensor for the alarm thermostat, ”Weighting for alarm
thermostat S4” (A36) and for the internal parameter “S3/S4” (U98), which amongst others can be used as
input for the read out on the display.
15
4.3
Temperature
acquisition
(continued)
Offset adjustment of temperature measurements
To compensate for measuring errors or wrong placement of the sensor, all sensors include an offset
adjustment. With the parameter “Sx offset” (r09), (r10), (r55), (r56) and (r57) it is possible to adjust the
respective temperature measurements from -10 to 10 K.
Filtering of temperature measurements
Furthermore all temperature measurements can be filtered with the parameter “Filter constant for
Txx”(o90 to o96)), which can be used for very unstable or fluctuating temperatures.
0:No damping, (fastest updating of the read out)
1: 0,10 K/sec
2: 0,09 K/sec
3: 0,08 K/sec
4: 0,07 K/sec
5: 0,06 K/sec
6: 0,05 K/sec
7: 0,04 K/sec
8: 0,03 K/sec
9: 0,02 K/sec
10: 0,01 K/sec (slowest updating of the read out)
Read out on the display
It’s possible to select between a variety of different parameters to be shown on the CRA 172 display,
“Display temperature” (099).
With “Minimum limitation of Display read out” (r06) the minimum read out can be limited downwards.
Furthermore, it’s possible to select, whether the temperature read out on the display must be in °C or °F.
The parameter “Temperature unit” (r05) is default set to °C.
Restrictions
All sensor inputs include a detection of open or shorted sensors. A sensor alarm will only be reported and
sent out if the sensor is being used by a function. If a sensor fails the sensor readout will be set to -300 °C
for an open circuit and +300 °C for a shorted sensor.
If the sensors S3/S4 are used in a weighted combination and one of the sensors fails, the sensor without
failure will be used and the weighting is disabled.
An alarm will be sent out for the defective sensor.
4.3.3 Dependencies
The step resolution for the display will be defined by the parameter “Display temperature step resolution”
(o15). See chapter for “Local display indication and menu structure”
16
4.4
Temperature logger
4.4.1 Purpose
The SLV controller has an internal temperature logger, which can log a predefined temperature directly
into the memory of the SLV controller. It is possible to attach an alarm to the logger, which will warn when
the upper or lower alarm limits are exceeded and when the alarm delay timer has elapsed.
4.4.2 Functional description
Using the parameter “Selection of sensor for the logger function” (h11), it is possible to select a
temperature sensor or an internal temperature calculation for the temperature logger. If no sensor is
selected, the logger will not begin. The speed of logging is determined by “Log interval” (h01). The number
of logs is limited to 1000. This means that the duration of the logging period depends on the number of
logs. For logging duration, please see the following table.
Logging interval
Maximum log duration in hours
Maximum log duration in days
15 minutes
250
10 days
30 minutes
500
20 days
60 minutes
1000
40 days
As soon as the logger is full, the oldest logs will be deleted and overwritten with a new log.
To limit at a certain number of logs, it is possible to set up thresholds for the logging range.
Logging of temperatures outside a predefined range:
If the “High Threshold” (h02) is set higher than the “Low Threshold” (h03), only temperatures outside
these limits will be logged.
Logging of temperatures inside a predefined range:
If the “Low Threshold” (h03) is set higher than the “High Threshold” (h02), only temperatures inside these
limits will be logged.
If the “Low Threshold for logging” and “High Threshold for logging” are set equal, no logging will be
performed.
Furthermore the temperature logger contains a separate high alarm function (h12) with adjustable alarm
delay (h13)
4.3.3 Restrictions
The maximum number of logs is limited to 1000.
In the event of a sensor error on the selected temperature probe, there will be no logging, but a sensor
error alarm will be generated.
4.4.4 Dependencies
None
17
4.5
Temperature alarms
4.5.1 Purpose
The SLV controller contains a temperature monitoring function, which will generate temperature alarms,
depending on if the temperature has exceeded some predefined limits. For some of the alarms a delay
timer can be set up.
4.5.2 Functional description
For the temperature alarm function, it is possible to use a different weighting of the temperature sensors
S3 and S4, compared to the one for the control thermostat (A36). This measurement will be compared
with the High and Low alarm limits. If the limits are exceeded, a delay timer will begin. The controller
has two different alarm delays, depending on whether the controller is in normal running mode (A03) or is
starting up after the initial start, end of defrosting or case cleaning etc (A12).
An alarm will be generated after the delay timer has elapsed. Depending on the settings for the Alarm
Handler, chapter 4.22, an alarm will be shown on the local display, or the local alarm relay will be
activated.
4.5.3 Restrictions
None
4.5.4 Dependencies
In case of a sensor error the temperature monitoring will stop and a sensor error will be sent out. If the
alarm thermostat is only using S3 or S4, the sensor error monitoring is only enabled for the active sensor.
18
4.6
Reference for the
capacity controller
4.6.1 Purpose
The purpose of the reference function is to generate a reference for the compressor capacity controller
and to create the limits for the temperature setting range during the day and night time. Based on the
deviation between the actual temperature Tact , compared to the temperature reference Tref, the capacity
controller will increase or decrease the requested compressor capacity. The bigger the deviation, the
faster the requested compressor capacity will be adapted.
As an option, the reference can also be obtained by using the digital input DI1 as an analogue input.
4.6.2 Functional description
Measurement and calculation of actual cabinet temperature Tact
The cabinet temperature can be measured with either S3, S4 or in special applications as a weighted
combination of both. In the event of wrong temperature measurements, due to wrong placement of the
sensors, both temperature inputs include an offset adjustment possibility. “Offset calibration of the S4
sensor” (r09) and “Offset calibration of the S3 sensor” (r10).
For the cabinet temperature measurement, with S3 and S4, a weighting of these 2 sensors is
implemented. The weighting can be different for the day and night time. “S3/S4 weighting for Tact at day
(100%=S4, 0%=S3)” (r15) and “S3/S4 weighting for Tact at night (100%=S4, 0%=S3)” (r61).
If the weighting is set to 100%, the temperature acquisition module only uses the S4 sensor. If set to 0%,
only the S3 sensor is used. If set to 50%, a 50/50 mix is used etc.
Calculation of Tref
The temperature reference Tref for calculating the reference for the PID controller is calculated as follows:
Tref = Tset + “Night setback” (r13)
The setting range of Tset can be limited with the 2 parameters “T set max” (r02) and “T set min” (r03)
To avoid a temperature reference too high or too low, the allowed temperature reference band is limited
with the following 2 set points:
“Tref min “(r25) and “Tref max.”(r26)
Besides this limitation of the temperature reference, the actual temperature Tact is calculated on
temperature measurements of S3 (U12) and S4 (U16). Both measurements can be offset adjusted (r10 and
r09), before a weighting is performed. This weighting can be different during the day and the night time
(r61 and r15). Finally a filtering of the calculated value can be performed, to avoid fluctuations of the Tact.
(O90)
Reference via external signal???
Description of parameter (r98), GIO Setpoint reference, is missing
4.6.3 Restrictions
None
4.6.4 Dependencies
If a weighted sensor signal for the Tact is chosen and one of the sensors S3 or S4 is detected to be
defective, a sensor error for that sensor will be generated. For the calculation of Tact the contribution from
this sensor will be ignored and the Tact will only be based upon the remaining functioning sensor.
19
4.7
Compressor capacity
control
4.7.1 Purpose
The purpose of this function is to calculate the requested compressor capacity, which is needed to cool
down or maintain the correct cabinet temperature during normal temperature control.
During the pull up/down of the cabinet, after the initial start or after a defrosting sequence, the capacity
controller will be over ruled by predefined capacity requests.
4.7.2 Functional description
The reference “T ref” for the controller is given by the reference function, based upon either the
temperature sensor S3, S4 or a mix of both. The ratio between them is set by the setting “S4 weight %”.
100 % means sole usage of S4 while 0% means solely S3 etc.
The determination of the actual requested compressor capacity is based on a PI controller, which
compares the actual temperature with the reference temperature. The bigger the deviation of the
temperature, the faster the adaptation of the compressor capacity is performed.
The SLV compressor can be speed controlled in the range from 50% to 100%, corresponding to 2000 to
4000 revolutions per min. If the requested compressor capacity is less than 50%, the compressor will start
and stop at 2000 rev-1 on a PWM basis. As default, the “Compressor Period time” (g05) is set to 15 minutes.
This means that the compressor will be running for a shorter or longer time within this period.
Requested Compressor capacity
Compressor speed, Period time = 15 minutes
0%
Compressor constantly stopped
25%
Pulse width modulation, PWM
7,5 minutes ON (2000 rev-1)
7,5 minutes OFF
50%
Compressor constantly running 2000 rev-1
75%
Compressor constantly running 3000 rev-1
100%
Compressor constantly running 4000 rev-1
The capacity controller contains compressor protection settings to prevent the start/stop of the
compressors from occuring too often (g02, g03 and g04).
After initial start the compressor capacity will be set to 100%, until the reference temperature Tref has
been reached. In some applications it might be an advantage to run the compressor at the pull down
capacity for some extra time. Although the air temperature in the cabinet has reached the set point, the
goods will still be too warm. For that reason, the pull down period can be extended, until the “Tact below
Tref to end Pull Down” (n48) has been reached. After this the PI controller will be preset to a default value,
depending on whether the controller is in day or night mode (n53 and n54).
Depending on the size of the deviation between the reference temperature Tref and the actual
temperature, the requested capacity will now be increased or decreased faster or slower. The speed of
adapting the requested capacity depends on the settings for the PI controller.
Due to different load profiles for the different applications, the controller has a “smart setting for PI
control” (n30) application. The default setting is medium control, but if a faster adaptation of the requested
compressor capacity is needed, this can be changed to fast or even very fast control. On the other hand,
this can also be set to slow or very slow, if the cooling application requests this. In situations, where one
of these settings is not suitable for the application, the PI settings can be adjusted by the customer (n35
to n43). It is recommended to contact the supplier of the controller for optimal adjustment. Although, the
right smart setting or individual adaptation of the PI controller has been chosen, it might happen from
time to time, that the cabinet temperature exceeds a pre defined minimum or maximum limit, compared
to the temperature reference Tref.
As soon as the temperature reaches the limit of “Tact above Tref to start Pull Down limit” (n47) or the limit
of “Tact below Tref to start Pull up limit” (n46), a timer “Temperature out of range timeout” (n50) begins.
After this timer has elapsed, a forced Pull up or Pull down starts. The timer will be reset, as soon as the
temperature is back within the min and max limits.
If a pull down is requested, the compressor capacity will be preset to "Optimised pull down capacity" (n52).
This capacity will be applied, until the time "Optimised pull down time" (n51) has elapsed. Hereafter the
compressor will run at 100%, until the setpoint has been reached.
If a forced pull up has been initiated, the compressor will stop, until the temperature exceeds “Tact above
Tref to end Pull up” (n49).
If the digital input DI1 is defined to be used as a door switch, it is possible to stop the evaporator fan during
open doors. It is also possible to override the capacity controller at the same time. The compressor can be
stopped “Compressor Capacity switching on door open” (n22) or the compressor capacity can be preset by
“Compressor Capacity at door open” (n23). As soon as the door is shut again, the capacity controller will
resume with the same capacity as prior to the door opening.
20
4.7
Compressor capacity
control
(continued)
4.7.3 Restrictions
Defrosting:
The PI controller is suspended during a defrosting sequence. Prior to a defrosting, the actual requested
compressor capacity is stored in the memory. After the end of defrosting and following pull down of
the temperature to a set point, the normal capacity control is resumed, based upon the previous stored
capacity.
Emergency cooling:
In the event of sensor errors, the capacity controller stops and the compressor capacity is preset to a
customer specified value, “Emergency cooling Capacity during S3 / S4 error” (n21). For more information
see the chapter “Emergency cooling”
4.7.4 Dependencies
The compressor capacity control can be overridden by an analogue signal on the DI depending on that the
parameter “I/O function” (o02) is set to 16.
A 500 kΩ logarithmic potentiometer connected to pin 31 and pin 33 is now representing a requested
compressor capacity between 0% and 100%.
All remaining control functions are not affeted by this!
21
4.8
Safety function
4.8.1 Purpose
The purpose of the “safety function” is to stop the compressor, if the pull down after a defrosting fails, due
to an open hot gas valve.
4.8.2 Functional description
The safety function monitors a predefined temperature after a defrosting sequence. The temperature
is selected with the parameter “Check temperature” (P50). If the compressor is running and the hot
gas valve is closed properly, this temperature is expected to be below the “Maximum Check value”
(P50), within a predefined time, “Time after compressor start to check” (P51). If this isn’t the case, the
compressor will stop and an alarm generated.
4.8.3 Restrictions
None
4.8.4 Dependencies
None
22
4.9
Emergency cooling
function
4.9.1 Purpose
The purpose of this function is to ensure a reasonable level of refrigeration in case of a reference
temperature sensor error.
For low temperature applications, it is better to run at a high compressor capacity while high temperature
applications prefer a reduced capacity, to prevent freezing of the chilled gds.
4.9.2 Functional description
If the sensor required by the application input setup is in a sensor error state, an emergency cling function
takes over and presets the requested compressor capacity to “Emergency cling capacity during S3 / S4
error” (n21). The emergency cling function takes over the normal capacity control, while all remaining
functions will run unaffected.
When normal compressor capacity control resumes, the PI controller will be “released” from the
emergency cling level and the requested compressor capacity will adapt to the actual needed capacity,
4.9.3 Restrictions
The function is overruled by the main switch off, service mode, case clean mode, loading of cabinet,
dr function cut out or the defrost mode, which do not contribute to the calculation of the requested
compressor capacity.
4.9.4 Dependencies
If a weighting of S3 and S4 is to be used for the input to the temperature reference, the emergency cooling
function will only be enabled when both sensors are detected to be defective. If only 1 sensor is defective,
the calculation of the cabinet temperature will be based upon the remaining sensor.
23
4.10
Defrost control
function
4.10.1 Purpose
The purpose of the defrost control function is to manage all aspects related to the defrosting of the
appliance. The start of the defrosting can be based on an internal real time clock, remotely controlled or
manually initiated by the end user.
4.10.2 Functional requirement description
Depending on the chosen cooling application, different defrosting sequences apply. In the following a
“worst case scenario” for a defrosting sequence is described. Depending on the different defrosting
modes, some of the functions can or will be omitted. Through settings, the user can choose between
Passive, Electrical or Hot gas defrost. The setting, “Defrost stop Sensor” (d10), allows the customer to
define, which temperature sensor must be used for termination of the defrosting on temperature. When
no sensor is chosen, the defrosting will only be terminated on time and the mentioned safety function
below will be disabled.
24
4.10
Defrost control
function
(continued)
4.10.2.1 Passive defrost:
1. Defrost starts according to internal schedule, manually via display or DI, remotely or via Front end
2.The actual requested compressor capacity is stored in the memory and the compressor is set to
OFF, depending that the setting “Compressor capacity during drain preheat” (d39) is set to 0%. If an
evaporator fan is mounted, this is set to ON. The parameter “Evaporator fan running during defrost”
(d09) must be set to 1!
3.The drain heater (if mounted) is energized for a preset time “Drain pre heating time” (d40). The heater
is kept ON during the whole defrost period and until the timer “Drain post heating time” (d20) has
elapsed, after the defrost stops.
4. The compressor remains off, dependent that the “Compressor capacity during defrost“ (d42) is set to
0% and the relay for heater/valve is activated.
5. Defrosting continues, until the “Defrost stop temperature” (d02) has been reached, measured with
S5. If the temperature has not been reached before the “Max defrost time” (d04) has elapsed, the
defrosting is terminated anyway and an alarm is sent out. If no stop defrost sensor is selected, the
defrosting terminates with the timer only.
6. Before starting the compressor for new “Pull down”, the evaporator fan, if mounted, remains stopped
for a preset time, to drain the evaporator. “Drip off time” (d06). During drip off, the “Compressor
capacity during drip off time” (d43) forces the compressor capacity to a preset value. After this timer
has elapsed, the compressor is released for a new pull down. The fan remains stopped for another
preset time, “Additional delay for evaporator fan start after drip off” (d07), to “tie” water drips to the
evaporator. In some cases it might be desired to control the starting point according to the evaporator
temperature only. In such cases the “Additional delay for evaporator fan start after drip off” (d07)
must be set to a very high temperature, so that the start is controlled according to the evaporator
temperature “Evaporator fan start temperature” (d08).
7.Evaporator fan starts
8.The compressor continues the “Pull down” until the set point has been reached, thereafter normal
capacity control resumes with the same capacity as before the defrost started.
25
4.10
Defrost control
function
(continued)
26
4.10.2.2 Electrical defrost:
1. Defrost starts according to internal schedule, manually via display or DI, remotely or via Front end
2.The actual requested compressor capacity is stored in the memory and the compressor is set to
OFF, depending that the setting “Compressor capacity during drain preheat” (d39) is set to 0%. If an
evaporator fan is mounted, this is set to OFF. The parameter “Evaporator fan running during defrost”
(d09) must be set to 0!
3.The drain heater (if mounted) is energized for a preset time “Drain pre heating time” (d40). The heater
is kept ON during the whole defrost period and until the timer “Drain post heating time” (d20) has
elapsed, after the defrost stops.
4.The compressor remains off, dependent that the “Compressor capacity during defrost“ (d42) is set to
0% and the relay for heater/valve is activated.
5. Defrosting continues until the “Defrost stop temperature” (d02) has been reached, measured with S5.
If the temperature has not been reached before “Max defrost time” (d04) has elapsed, the defrosting
is terminated and an alarm is sent out. If no defrost stop sensor is selected, the defrosting terminates
with the timer only.
6. Before starting the compressor for new “Pull down”, the evaporator fan, if mounted, remains stopped
for a preset time, to drain the evaporator, “Drip off time” (d06). During drip off, the “Compressor
capacity during drip off time” (d43) forces the compressor capacity to a preset value. After this timer
has elapsed, the compressor is released for a new pull down. The fan remains stopped for another
preset time, “Additional delay for evaporator fan start after drip off” (d07), to “tie” water drips to the
evaporator. In some cases it might be desired, to control the starting point according to the evaporator
temperature only. In such cases the “Additional delay for evaporator fan start after drip off” (d07)
must be set to a very high temperature, so that the start is controlled according to the evaporator
temperature “Evaporator fan start temperature” (d08).
7.Evaporator fan starts
8.The compressor continues the “Pull down” until the set point has been reached, thereafter normal
capacity control resumes with the same capacity as before the defrost started.
4.10
Defrost control
function
(continued)
4.10.2.3 Hot-gas defrosting:
1. Defrost starts according to internal schedule, manually via display or DI, remotely or via front end
2.The actual requested compressor capacity is stored in the memory and the compressor capacity
is preset to the setting “Compressor capacity during drain preheat” (d39). If an evaporator fan is
mounted, this is set to OFF. The parameter “Evaporator fan running during defrost” (d09) must be set
to 0! This can prepare some hot gas in the system.
3.The drain heater (if mounted) is energized for a preset time “Drain pre heating time” (d40). The heater
is kept ON during the whole defrost period and until the timer “Drain post heating time” (d20) has
elapsed, after the defrost stops.
4.The compressor capacity is set to a preselected setting “Compressor capacity during defrost“ (d42) to
generate hot gas for the defrosting. The relay for heater/valve is activated.
5. Defrosting continues, until the “Defrost stop temperature” (d02) has been reached, measured with S5.
If the temperature has not been reached before the “Max defrost time” (d04) elapses, the defrosting is
terminated and an alarm is sent out. If no defrost stop sensor is selected, the defrosting terminates
with the timer only. Hereafter the hot gas valve is closed.
6. Before starting a new “Pull down”, the evaporator fan, if mounted, remains stopped for a preset time,
to drain the evaporator. “Drip off time” (d06). During drip off, the “Compressor capacity during drip
off time” (d43) forces the compressor capacity to a preset value. After this timer has elapsed, the
compressor is released for a new pull down. The fan can remain stopped for another preset time,
“Additional delay for evaporator fan start after drip off” (d07), to “tie” water drips to the evaporator. In
some cases it may be desired, to control the starting point according to the evaporator temperature
only. In such cases the “Additional delay for evaporator fan start after drip off” (d07) must be set
to a very high temperature, so that the start is controlled according to the evaporator temperature
“Evaporator fan start temperature” (d08).
7.Evaporator fan starts
8.The compressor continues the “Pull down” until the set point has been reached, thereafter normal
capacity control resumes with the same capacity as before the defrost started.
27
4.10
Defrost control
function
(continued)
4.10.2.4 Defrosting start
The SLV controller includes a real time clock and a defrosting schedule which can start the defrosting. It is
possible to set up a defrosting schedule on a daily or weekly basis. “Number of defrosts” (d90).
0 =Never, No automatic defrost,
Only manual or remote defrost start is possible.
1 =One pr. Day, based on the real time clock
The start time for each day in hours, (d71) to (d77) and minutes, (d81) to (d87)
2 =Multiple defrost per day at fixed hour, based on the real time clock
The SLV controller can initiate up to 8 defrosts per day. The first to last daily defrost start time in hours,
(d71) to (d77) and minutes, (d81) to (d87)
3 =Multiple per day, timer based with fixed interval, set via d03.
Every time a defrosting has been performed, a new defrosting will be initiated with a fixed interval after
the termination of the previous one.
4 =Defrost on demand
Interval between defrost, when multiple defrost per day has been chosen. (d90 = 3)
To prevent defrosts from occurring too often, the parameter “Min interval between defrost” (d62) can
be set in the range of 0 to 168 hours. This protection timer can only be reset by switching OFF and ON
the mains supply to the controller. The controller must be de energized, until the light in the display is
switched off!
Apart from the defrosting schedule, it is also possible to start and stop a defrosting either locally on the
control display “Allow local display to start defrost” (d61) or remotely via the Modbus, “Allow remote start
of defrost” (d60)
4.10.2.5 Drain heater
The drain heat output is intended for the connection of an optional, electrical drain heater. The function of
this heater is to prevent the draining pipes for the melted ice from sticking up, before and during defrost.
This function will most likely not be used on cooling applications (plus temperatures) but occasionally on
freezing applications. The relay will only be activated in connection with a defrosting sequence, the rest of
the time, it will be OFF. Please see the defrosting sequence.
4.10.2.6 Coordinated Defrosting
If the SLV controller and compressor are used in a cabinet together with another SLV set, on 1 common
cooling cabinet, it will be necessary to coordinate the defrosting. This secures that both cooling circuits
have terminated the defrosting, before a new pull down is performed on 1 cooling circuit, while the other
one still is defrosting. Otherwise there will be a high risk of ice build up on the cold evaporator, while the
second one is still defrosting. The maximum delay of a new started pull down after defrost is set with “Max
hold time after coordinated defrost” (o16). After this timer has elapsed, the cooling will restart and an
alarm “A05 Max hold after defrost exceeded“ will be sent out.
The coordination of this defrosting must be controlled via the Master on the Modbus.
4.10.3 Restrictions
⋅⋅ A new defrost is not initiated if the compressor isn’t running, due to a compressor error prior to a new
defrost sequence, in order to prevent heating of the cabinet.
⋅⋅ If a sensor error is detected on the defrost stop sensor, prior to start of defrost, the next defrost will be
started and terminated on time. A sensor error alarm is generated.
⋅⋅ If the defrost stop sensor is detected as faulty during the defrosting, the ongoing defrost is terminated
on time and a sensor error alarm is generated.
⋅⋅ If the temperature is not below the “check temperature” (P50) before the timer “Time after compressor
start to check” (P51) has elapsed, an alarm is sent out and the compressor and evaporator fan stop.
⋅⋅ The sensor error detection functionality on the “Defrost stop sensor” (d10) is only enabled when a
sensor is selected.
4.10.4 Dependencies
The coordinated defrost function will only work, if a master is present on the Modbus!.
28
4.11
Melt function
4.11.1 Purpose
On high temperature cabinets, there is a risk of ice flakes forming on the evaporator which could block
the air flow, when the thermostat has not made cut out for a certain time period. In order to avoid this, the
melt function will initiate a forced stop of the compressor with regular time intervals.
During the stop period the ice flakes will be transformed into solid ice and therefore prevent the air
passage through the evaporator from blocking up.
During the melting, the display will show the “DeF” code.
4.11.2 Functional description
The melt function is divided into two parts.
⋅⋅ The melting part, where the compressor stops and the evaporator fan, if present, continues to run. The
stop period is determined with “Duration of melt period” (r17).
⋅⋅ The cool down period, where the compressor is running at 100%, until the temperature set point has
been reached. After this the capacity controller resumes with the same compressor capacity as before
the start of a melting cycle.
The condition to start a melt period is as follows:
⋅⋅ The melting interval “Time between melt periods “(r16) is set different to zero.
⋅⋅ The compressor has been running continuously during the melting interval.
⋅⋅ The sensor for Tact has been without fault
⋅⋅ The Tact (U17) is between the lower limit “Lower temperature limit to start melt“(r19) and the upper
limit “Higher temperature limit to start melt “(r20).
⋅⋅ The temperature controller must be in range at this time
During the melting and cooling action, the following conditions must terminate the sequence:
⋅⋅ the sensor for Tact has a fault
⋅⋅ the melt function is overruled by an operation mode with a higher priority
⋅⋅ the Tact (U17) is not between the lower limit (r19) and the upper limit (r20)
⋅⋅ The melting interval (r16) is set to zero.
4.11.3 Restrictions
The melt function is inactive if “Time between melt periods” (r16) = 0 or “Duration of melt period” (17) = 0.
At thermostat air sensor error, the melt function is inactive.
Furthermore the function will be inactive, when “The air” (u17) is above the “High Lim air” (a13) or when
the SLV is in Pull down mode.
4.11.4 Dependencies
This function only makes sense on applications running with evaporator fans.
29
4.12
Case cleaning
function
4.12.1 Purpose
The purpose of the case cleaning function is to assist the daily user in the cleaning of the cabinet. If the
function is enabled, the daily user can initiate and terminate a case cleaning by pushing a button on the
cabinet.
4.12.2 Functional description
If the DI1 is defined to be used for case cleaning, the following sequence will start, as soon as the button is
activated:
First activation:
⋅⋅ The actual compressor capacity is stored in the SLV memory, to be resumed at the end of the cleaning
sequence.
⋅⋅ De icing of the evaporator starts. Depending on the setting of the “De icing method” (o47), this can
either:
1: Stop the compressor and the evaporator fan (if present) continues to run, until the defrost stop temperature has been reached.
2: Start a defrosting sequence, until the defrost stop temperature has been reached. This can be electrical, hot gas or natural.
At the end of manual cleaning, the daily user activates the button a second time.
Second activation:
⋅⋅ A new pull down of the cabinet temperature is initiated, until the set point has been reached.
⋅⋅ Normal temperature control resumes with the same compressor capacity as before the start of a
cleaning sequence.
The parameter “Case cleaning status” displays the status of the sequence:
0:No cleaning initiated
1: De icing of the evaporator is in progress. This can be either electrical, natural or hot gas defrosting.
2: Waiting for the daily user, to finish the cleaning and to activate the button a second time.
Display readout:
Readout on the display during the cleaning cycle and after following pull down: “deF”
Alarm handling:
During case cleaning all alarm messages are disabled (except for the case cleaning message and sensor
errors). The alarm delay for High Temperature alarms is set by the parameter “Delay timer for High
temperature alarms, after initial start up or defrosting” (A12).
Defrost:
A normal defrost sequence cannot be started, and an ongoing defrost will stop during case cleaning.
Stop of case cleaning:
The user can stop a case cleaning procedure using the same signals as for initiation. A case cleaning
procedure can also be terminated by setting the main switch to OFF.
4.12.3 Restrictions
None
4.12.4 Dependencies
None
30
4.13
Condenser or
compressor
compartment fan
control
4.13.1 Purpose
The purpose of this function is to control the condenser fan during the different running conditions and
different SLV states. Depending on the application, this fan can be a combined condenser and compressor
compartment fan or a dedicated condenser fan.
4.13.2 Functional requirement description
Before using the condenser fan control block, one of the relay outputs must be defined to be used as a
condenser fan relay. “Relay x configuration” (L01 to L059) must be set to 5. The condenser fan can be
controlled in four different ways, determined by the parameter “Condenser fan mode” (F11).
0: No control at all, always OFF
1: The fan runs continuously, as long as the compressor is running
2: Hysteretic control of the fan, based upon temperature measurement with S3b. Cut in temperature is
set with “Condenser fan start temperature” (F12). Cut out temperature is set with “Condenser fan stop
temperature” (F13).
3: Always ON, unless in stopped mode.
In some applications, it might be an advantage to pulse the fan during the night condition, to save further
energy or to reduce the noise emission to the surroundings. The function is enabled with “Condenser fan
pulsing” (F15). If set to ON, the fans will be pulsed during the night. The pulsing period time is set with
“Condenser Fan period time for pulse mode” (F16), while the “Condenser Fan On-time in % of period time”
(F17) is giving the duty cycle during pulsing.
Besides the above mentioned functions, it is possible to set up an alarm thermostat “Condenser Fan
Alarm temperature (S3b)” (F14) for monitoring the maximum temperature, in case of a blocked condenser
fan or dirt on the condenser surface.
If the temperature limit has been exceeded, an alarm A37 will be sent out.
4.13.3 Restrictions
None
4.13.4 Dependencies
None
31
4.14
Evaporator fan
Control
4.14.1 Purpose
The purpose of the evaporator fan control is to establish the necessary airflow through the evaporator and
to distribute the air into the cooling application. In applications with skin evaporators, running on fresh
meat applications etc, this fan may be used internally in the cabinet, to improve the cooling inside of the
cabinet. On passive or natural defrosting, the fan is also used to circulate the necessary airflow during the
defrosting.
4.14.2 Functional description
The mounting of an evaporator fan is optional for many of the SLV applications. For applications with skin
evaporators it is most likely that the fan will not be mounted. On the other hand, in most cases the finned
evaporators will need the fan.
Before using the evaporator fan control block, one of the relay outputs must be defined to be used as an
evaporator fan relay. “Relay x configuration” (L01 to L059) must be set to 6.
The parameter “Evaporator Fan mode” (F01) makes it possible to select the most appropriate evaporator
fan control mode.
0 =No evaporator fan control.
The relay output can be used for other purposes,
1= Fan control is enabled.
The fan will run during the different control states, over ruled by the defrosting, the door control and
compressor state. For details see parameter F03 to F07
2 =The fan control is enabled, with temperature check.
Same function as for 1, but with a safety function, which will stop the fan if the evaporator temperature
exceeds the safety level “Evaporator Fan stop temperature” (f04). The fan will start again, when the
evaporator temperature 2 K is below the safety limit again. The evaporator temperature is measured
with the same sensor as for the defrost stop function. Parameter “Defrost stop sensor” (d10).
During cooling (when the compressor is running) the fan must run, but during thermostat cut out (or PWM
control of the compressor) the fans can be pulse controlled, to save energy. The parameter “Evaporator
Fan mode” (F01) must be set different to 0 (enabled).
If the Digital input is defined as a door switch, it is possible to stop the evaporator fan during door opening.
The compressor capacity during open doors is set in the compressor capacity section. The parameter
“Evaporator fan stop on door open” (F03) must be set to 1 (enabled). If set to 0, the fan will continue
running at open doors.
During defrosting, the evaporator fan control is over ridden by the defrost sequence controller. On cabinets
with night set back, the fans can be pulsed at thermostat cut out in order to save energy.
When the cabinet is set to “cleaning mode”, the status of the fans depends on the cleaning routine.
“Evaporator Fan mode” (F01) must be set to 1.
Fan pulsing control
Function
Via the set point “Evaporator fan pulsing” (F05) it is possible to select how to control the fan:
⋅⋅ “Evaporator fan pulsing” (F05) = 0:
No fan pulsing – fan is always running, unless in stopped mode, cleaning mode or defrosting etc.
⋅⋅ “Evaporator fan pulsing” (F05) = 1:
Fan always runs together with the compressor, but will be pulsed at thermostat cut out
⋅⋅ “Evaporator fan pulsing” (F05) = 2:
Fan always runs together with the compressor, but will be pulsed at thermostat cut out, during night
condition or night blinds activated.
⋅⋅ “Evaporator fan pulsing” (F05) = 3:
The fan is always pulsed during night condition.
32
4.14
Evaporator fan
control
(continued)
If pulsing is active, the fan is pulsed according to a duty cycle pattern. Within a duty cycle the fan is set
to ON for a set period of time (set in percent of the duty cycle time) “Evaporator fan period time for pulse
mode” (F06).
The minimum duration of the time period must be adapted according to the type of output used to control
the fan (on relay outputs the lifetime has to be taken into account).
Each period starts with an ON period followed by an OFF period.
The output ‘Relay’ is ON during the ‘ON period’ and OFF during the ‘OFF period’.
4.14.3 Restrictions
When the compressor is not running, due to a compressor error, the evaporator fan will stop, to prevent
heating of the cabinet and unnecessary cold dissipation.
4.14.4 Dependencies
None.
33
4.15
Blind control
function
4.15.1 Purpose
The purpose of the blind control function is to manage the blinds in front of the cabinet in sync with the
day / night mode of the controller. The function can be over ridden by the digital input, which will put the
curtain into day position at closed DI.
4.15.2 Functional description
The relay for the blind control will be engaged during night mode. For some control systems, a 1 pole
change over relay will be needed, to run the curtain motor in 2 different ways. This option is possible on
relay 4 and 5. To activate the blind function, the parameter “Blind function” (o62) must be set ON.
The SLV can be set into night mode via one of the following methods:
⋅⋅ Manually via settings in the controller
⋅⋅ Via a signal on the digital input, if the DI is defined for Day / Night control
⋅⋅ Via the “Day / Night function” in the Master Control system.
4.15.3 Restrictions
If the DI is defined for curtain control, a closed DI will over ride the above mentioned inputs and force the
curtain into day position.
4.15.4 Dependencies
None
34
4.16
Light control function
4.16.1 Purpose
The purpose of the light control function is to manage the lights in the cabinet.
4.16.2 Functional description
The relay output for Light / Curtains is a 1 pole change over relay. The relay is engaged during night mode.
The SLV can be set to night mode via one of the following methods:
⋅⋅ Manually via settings in the controller
⋅⋅ Via a signal on the digital input, depending on settings in the controller
⋅⋅ Via the “Day / Night function” in the Master Control system.
4.16.3 Restrictions
Safety functions during day / night control:
When the night setting signal is lost, the controller will revert back to the default day condition. For that
reason, the night signal from the front end must be retransmitted (Master control block) to keep the night
mode in the SLV. Otherwise the SLV goes into day mode (light on and curtain up)
4.16.4 Dependencies
None
35
4.17
Real Time Clock and
control timer
4.17.1 Purpose
The SLV controller contains a real time clock with battery backup. This RTC is used for the control timer,
which can operate different functions. Furthermore the RTC is used for the defrosting schedule. For
defrosting, please see section 1.11 Defrost control function.
4.17.2 Functional description
The real time clock is powered from the internal SLV supply. In case of a power drop out, the RTC will be
powered from the internal battery back up.
The RTC can be set up in one of the following ways via the local display, the T4C or remotely via the Front
end system. If the set up is done via the local display, please follow the instructions in section 1.25, Local
Display indications and menu.
When T4C is used for setting up the RTC, you don’t have to enter a value for each RTC parameter. Instead
it’s possible to push the “Set PC time to SLV” in the T4C menu structure.
Based on the RTC, the SLV controller also has a control timer, with a daily schedule.
With this control timer, it is possible to intervene into the normal control of the SLV. The parameter
“Control timer Function” (t84) has the following options:
0 =None. No override of the SLV
1 =Do not use
2 =Stop mode. The SLV is put into the Stop mode as long as the Control Timer is active..
3 =Night operation. Selection of day / night mode via the internal control timer
4 =Light. Light ON / OFF as function of the control timer.
5 =Application changeover. Selection of an application as a function of a pre defined schedule in the
control timer.
6 =Relay out. ON / OFF control of a pre selected relay, as function of the control timer.
4.17.3 Restrictions
None
4.17.4 Dependencies
None
36
4.18
Alarm Handler
4.18.1 Purpose
The alarm handler manages the alarms, in case of different types of errors. The alarms can be indicated
on the local display, and activated by relay or via the Modbus.
4.18.2 Functional requirement description
All possible alarms in the SLV controller are split into 5 different groups, depending on type of error:
Group
Name
Description
0
User Application Faults
Application faults are faults that are caused by trouble in the application shouts
as the cooling circuit or missing air to the machinery room
1
System related Errors
System faults are related to trouble emerging from external condition to the
cabinet. E.g. over voltage on the mains
2
Sensor Errors
Sensor faults are faults that are detected on the sensors if they are used
3
Electronic Faults
Electronic faults are trouble caused by the electronics
4
Motor Faults
Motor faults are all troubles influencing the motor causing it to fail to operate.
It can be caused by overloading the cooling system or very big deviations on the
mains power supply.
4.18.2.1 Application related alarms
The application alarms are alarms that relate to the cabinet and are caused by using the cabinet in a
wrong way.
The 2 columns “T4C event listing Value 1” and “T4C event listing Value 2” show useful information,
concerning the alarm. Depending on the alarm number, this can be:
⋅⋅ Setting value for the alarm threshold
⋅⋅ Actual value at time for alarm occurrence
⋅⋅ Maximum value of the parameter during the alarm
37
4.18
Alarm Handler
(continued)
T4C event listing
Text
T4C event listing
Value 1
T4C event listing
Value 2
A04
Door alarm
A05
Max hold after defrost
exceeded
Max hold minutes
A06
Tact temperature
Max defrosting time exceeded
Maximum
temperature
A15
Alarm on DI
Manual text
Alarm
Group
The door has been detected open for too long (A04)
0
During the remote control of a coordinated defrost,
the maximum defrost hold time has been exceeded
(o16)
0
The temperature to stop the defrost heating has
taken too long (d04)
0
When the DI is selected to be an alarm or separate
alarm open input, the switch has been open for more
than the (A27) time.
If the DI is configured to separate alarm open, the
system will be put in emergency stop mode.
0
Fatal alarm on DI
A20
High Temperature alarm
Tact temperature
The actual temperature Tact has been over the maximum limit (A13) for longer time than (A03) or (A12)
0
A37
Condenser temperature too
high
Condenser Max temperature Tact temperature
The condenser temperature has exceeded the maximum limit (F14)
1
A43
Low Temperature alarm
Tact temperature
The actual temperature Tact has been below the
minimum limit (A14) for longer time than (A03) or
(A12)
0
A60
Temperature logger high
alarm
Tact temperature
The temperature logger temperature has been above
the maximum limit (h12) for longer time than (h13)
0
A75
Evaporator temperature too
high
Separate alarm temperature Max temperature
The separate alarm temperature, selected by (P50),
has been over the allowed maximum temperature
(P53) 0
A76
No application selected
No application is enabled by the user. The user must
enable at least one application and select it. (P01 to
P05)
0
A81
Motor speed temporarily too
high
The motor has been running too fast and has
stopped. This can be caused by fast pressure fall on
the condenser side or if the main voltage has high
fluctuations 1
A82
Motor speed temporarily too
low
The motor has been running too slowly and has
stopped. This can be caused by fast pressure increase on the condenser side or if the mains voltage
has high fluctuations
1
A90
Check clock settings
The clock needs to be adjusted
0
A91
Configuration mismatch on
DI’s
The DI input is configured for the same function
twice.
0
The temperature of the inverter has been exceeding
the maximum limit and the motor has stopped.
If the temperature falls under the limit the motor will
be automatically restarted.
1
The mains supply voltages have been below the
minimum limit or above the maximum limit.
1
A fault has been detected on the mains supply.
1
A96
Overload of Display outlet
The digital input or display supply voltage has been
short circuited
1
A97
Controller internal temp. too
high
The temperature of the inverter is exceeding the
maximum limit. The electronics are too hot
1
A98
Inverter temp. too high
The temperature of the inverter is exceeding the
maximum limit. The electronics are too hot
A92
Compressor stop due to too
high Controller temperature
Condenser
Temperature
A93
Mains supply voltage out of
range
A95
Mains supply frequency out
of range
38
Max temperature
0
1
2
3
4
5
50 Hz fault
60 Hertz fault
High frequency
Low frequency
Floating frequency
No frequency
1
4.18
Alarm Handler
(continued)
4.18.2.2 Other alarms
T4C event listing
Text
T4C event listing
Value 1
T4C event listing
Value 2 format
Manual text
Alarm
Group
E25 S3 Sensor error
The S3 sensor has a fault
2
E26 S4 Sensor error
The S4 sensor has a fault
2
E27 S5 Sensor error
The S5 sensor has a fault
2
E28 S6 Sensor error
The S6 sensor has a fault
2
E29 S3b Sensor error
The S3b sensor has a fault
2
E80 Motor error
The motor system has detected a fault 4
E90 Electronic failure
The electronic has an internal fault.
3
For diagnosis of the sensor errors please refer to the section “Service mode”
4.18.3 Alarm acknowledgement
There are 3 different ways to acknowledge alarms:
⋅⋅ By pushing the reset button on the local display CRA 172, remotely from a front end system or auto
acknowledge by the SLV.
⋅⋅ As default, the SLV is not set to auto acknowledge.
⋅⋅ By setting the parameter “Auto acknowledge” (o84) different to zero the function is enabled.
4.18.4 Restrictions
None
4.18.5 Dependencies
None
39
4.19
Event logging system
4.19.1 Purpose
In order to analyse information during the electronic and systems lifetime, the SLV has a logging system,
which tracks events such as alarms, change of settings or local events initiated by the user.
4.19.2 Functional description
The event logger will show all events in a chronological order, starting with the most recent event on top.
The event logger can hold up to 200 events, before the logger is full. In such a case, the oldest event at the
bottom will be deleted and substituted with the latest on top. In the “Time” column the time of occurrence
is listed. The 2nd column “User” is showing the initiator for the event. The following initiators can create
an event:
⋅⋅ System: For example Temperature Alarms, controller in service mode, Logger alarms, Max defrost time
exceeded
⋅⋅ Tool4Cool: For example change of settings.
⋅⋅ MMI: For example change of settings, acknowledge of alarms, controller in Stop mode, application
change over, defrost start
⋅⋅ Danfoss front end system: For example application change over, defrost start, alarm acknowledge etc.
⋅⋅ 3rd party front end: For example application change over, defrost start, alarm acknowledge etc.
4.19.2.1 List of possible Events
The following events are useful to track changes and operations during the life of the control unit
T4C event listing
Text
T4C event listing
Value 1
Description
Event database cleared
The event database was cleared Parameter changed
– [Parameter name]
A parameter has been changed.
(The parameter name is in the brackets)
User connected
Mains voltage detected
New value System,
Tool4Cool,
Secop Front end,
3rd Party front end
Supply chain FFT
Supply chain ICI
Supply chain RA
OEM production
MMI
115V
230V
Temperature log cleared
Automatic baudrate
change detected
When a new user uses the system a logging
of the event will be done in order to track
who has made changes.
This event is normal after power up of the
system
The temperature log has been cleared
9600 baud
19200 baud
The baud rate has automatically changed
the baud rate
System boot
The system started
Acknowledge of alarms
The alarm has been acknowledged by the
user
Factory settings stored
The factory settings have been stored in the
database
Factory settings restored
The factory settings in the database have
been restored
A220 Case cleaning completed
This alarm shows that the case cleaning has
been completed
A226 Controller in Service mode
This alarm shows that the controller was set
in service mode
4.19.3 Restrictions
None
4.19.4 Dependencies
None
40
T4C event
listing
Value 2
format
4.20
Service Mode
4.20.1 Purpose
Accessing the service mode makes it possible to manually set the outputs and read the status of the
inputs. This improves the service ability of the whole cabinet.
4.20.2 Functional description
To protect the SLV against unauthorised setting modifications, the SLV is protected with access codes
for the different user levels. To access the Service level, the appropriate access code for the service level
“Access code service” (o07) must be entered first.
In the service level it is possible to read different measurements, as well as force the relay outputs ON or
OFF and force the compressor to run at different speeds.
Readings:
In the service level, the following readings are available:
L50
PCB temperature
Readout of the controller temperature on the circuit board
L51
Inverter temperature
Readout of the controller temperature on the inverter module
L52
Mains voltage supply
Readout of mains supply voltage
L53
Mains frequency
Readout of mains supply frequency
L60
Compressor manual control
Shows that the compressor is in manual mode
L61
Compressor actual state
Indication of whether the compressor is running or not
L62
Set point of the actual compressor speed, in % of the variable speed
Compressor manual speed percentage band during manual control.
when running
0% means compressor runs at minimum speed and 100% means
that the compressor runs at max speed during service mode.
L63
Compressor actual speed percentage
when running
Readout of the actual compressor speed, in % of the variable speed
band during manual control.
0% means compressor runs at minimum speed and 100% means
that the compressor runs at max speed during service mode.
Furthermore, all temperature measurements can be read out. To check the correct reading, compared to
the actual sensor temperature the below 2 tables can be used.
41
4.20
Service Mode
(continued)
NTC temperature table for S3, S3b, S4 and S5
T (°C)
B25/100 = 3980 K, R25 = 5000 Ω, TR = 0°C
Rnom( Ω)
Rnom( Ω)
Rnom( Ω)
Pt 1000 temperature table for S6
Temperature
Ohm
-40
169160
159350
178970
-40
842,7
-35
121800
115390
128200
-35
862,5
-30
88766
84552
92979
-30
882,2
-25
65333
62555
68111
-25
901,9
-20
48614
46778
50450
-20
921,6
-15
36503
35291
37715
-15
941,2
-10
27680
26883
28478
-10
960,8
-5
21166
20646
21686
-5
980,4
0
16330
16003
16657
0
1000,0
1019,5
5
12696
12386
13006
5
10
9951
9670
10232
10
1039,0
15
7855
7604
8105
15
1058,5
20
6246
6025
6467
20
1077,9
25
5000
4806
5194
25
1097,3
30
4029
3859
4198
30
1116,7
35
3266
3118
3414
35
1136,1
40
2665
2535
2794
40
1155,4
1174,7
45
2186
2073
2298
45
50
1803
1705
1901
50
1194,0
55
1495
1419
1581
55
1213,2
60
1247
1172
1321
60
1232,4
65
1044
1110
65
1251,6
979.0
70
878.9
821.7
936.1
70
1270,7
75
743.1
692.9
793.4
75
1289,9
80
631.0
586.9
675.2
Access levels:
Once the service level code has been entered, it’s possible to modify the access codes for the different
access levels:
o05
Access code end user
Access code for the end user level on the display
o06
Access code installer
Access code for the installer level on the display
o07
Access code service
Access code for the service level on the display
o08
Access code OEM lab
Access code for the OEM level on the display
Activation of outputs:
Before it is possible to activate the relays ON/OFF, the service mode must be activated via the parameter
“Service mode” (p83). There are 4 different service modes available:
0:Normal, control mode
1: Service mode
2: Customer lab mode, only to be used in the OEM lab for running special approval test, only accessible
with OEM key.
When the SLV controller is set in service mode, all relays are switched off and the compressor speed is
set to zero. When the controller is set back into normal control all relays are set back into same state as
before entering the service mode and the compressor resumes with the same capacity.
The 5 relays R1 to R5 can be set ON and OFF with the parameters “Relay X Manual control” (P84 to P88)
When the controller is taken out of the service mode and put into the normal control mode, the normal
cabinet control will be resumed, regardless of the actual states of the relay in the service mode.
4.20.3 Restrictions
None
4.20.4 Dependencies None
42
4.21
Local Display
indications and menu
structure
4.21.1 Purpose
The function of the display is to act as the user interface between the user and the cooling application.
This includes readouts of temperature, application change over, setting of parameters, starting of a
defrosting and reset of alarms.
Besides the 3 numeric digits the display also has 4 LED’s for Alarm, Defrosting, Service and Cooling.
4.21.2 Functional description
The different parameters of the SLV controller can be accessed via the local display or via the Modbus. In
this section, only the local display interface will be described.
The different parameters of the SLV controller are split into 3 different levels on the display interface. Each
level can be protected with an individual access code, which can be defined by the customer. If a level is
protected with an access code, the user will be asked to enter in the access code for the actual level.
For details concerning the access codes, please refer to section 1.23, Service Mode.
o05
Access code end user
Access code for the end user level on the display
o06
Access code installer
Access code for the installer level on the display
o07
Access code service
Access code for the service level on the display
o08
Access code OEM lab
Access code for the OEM level on the display
In the parameter overview the accessibility indicated in the different levels is shown with an “R” or a “W”,
which represents read or write.
Menu structure for the display
The manoeuvring through the local display menu structure is based on different activations of the buttons
on the right side of the front. There are 3 different ways of activating the buttons:
⋅⋅ Single short activation
⋅⋅ Single long activation
⋅⋅ Triple short activation
Level
Daily
Event
Action
Upper button short
Acknowledge active alarm/receipt alarm/see alarm code
Change to inspection of alarms
Upper button long
Change to parameter selection.
Middle button short
Application change over (if more than 1 application is enabled, this will toggle
between the enabled applications)
Middle button triple
Change to edit set point for actual selected application
Lower button short
Selection of special function according to below scheme.
Lower button long
Start/Stop defrost depending on d61 and d62, please refer to
section 4.10.2.4 Defrost control function
Lower button tripple
Stopped / operating, depending on “Selection of stopped mode” (P32)
It is possible for the customer, to define a function on the lower right button, during daily operation:
43
4.21
Local Display
indications and menu
structure
(continued)
Definition of functionality on lower button
(o93)
1 = Activation of Light ON /OFF
Activation of the lower right button switches the light ON or OFF. The
light can also be controlled via the internal control timer or remotely via
the Modbus. It is always the last command which determines the status
of the light.
2 = Activation of Night Mode
Activation of the lower right button switches the night mode ON or OFF.
3 = Read out of Defrost stop temperature
Activation of the lower right button reads out the temperature of the
Defrost stop sensor.
4 = Read out of S6 temperature
Activation of the lower right button reads out the temperature of the
S6 sensor
5 = Read out of S5 temperature
Activation of the lower right button reads out the temperature of the
S5 sensor
6 = Read out of S3b temperature
Activation of the lower right button reads out the temperature of the
S3b sensor
7 = Read out of Actual Tref
Activation of the lower right button reads out the temperature reference
for the controller.
Level
Inspection of alarms
Event
Action
Upper button short
Previous alarm in alarm listing
Lower button short
Next alarm in alarm listing
Inspection of alarms will timeout after 4 seconds and the menu system reverts back to the daily level.
Level
Parameter selection
Event
Action
Upper button short
Select next parameter
Upper button long
Select next parameter continuously
Lower button short
Select previous parameter
Lower button long
Select previous parameter continuously
Middle button short
Change to edit parameter
During parameter selection, the upper and lower buttons scroll through the parameters, which are sorted
in alphanumeric order.
Parameter selection will timeout after 4 seconds and the menu system reverts back to the daily level.
If the parameters are protected with access codes, the parameters o05 to o08 are set to a value different
from 0. In such cases, the access code must be entered first.
Level
Edit set point
Event
Action
Upper button short
Increment set point value
Upper button long
Fast increment set point value
Lower button short
Decrease set point value
Lower button long
Fast decrease set point value
Middle button short
End editing set point
The edit set point level will timeout after 4 seconds, without any activity on any button, and the menu
system reverts back to the daily level. If a value was altered it will not be stored unless the middle button is
activated.
Alarms on the display
The alarms, which can be generated in the SLV controller, are divided into different groups, depending on
the reason for the alarm. These alarms can be sent out on the Modbus, via the local alarm relay or the
local display. With the parameter “alarm on the display” (o98), the following 3 options are possible:
0 =No alarm indication on the display at all.
1 =Only User Application Faults (System related). These alarms are caused by the end user and can also
be corrected, without assistance of a service engineer. Typical reasons could be overloading of the
cabinet, loading of the cabinet with hot goods, dirt, open doors etc.
2 =All alarms will be shown on the local display.
44
4.21
Local Display
indications and menu
structure
(continued)
Readout on the Display
CRA 172
It is possible to select
between a number of
different readouts on
the display CRA 172.
In most cases, the customer will use the actual cabinet temperature Tact but it is possible to select
between the following number of parameters, “Display temperature” (o99):
0 =TS3/TS4, weighting based upon the parameter “S3/S4 weighting” (017)
1 =T Temperature logger, temperature used for the internal temperature logger.
2 =Tact
3 =Talarm, temperature used for the alarm thermostat
4 =S3
5 =S3b
6 =S4
7 =S5
8 =S6
With the parameter “display temperature step resolution” (o15), it is possible to change the resolution of
the display readout as follows:
1 =XX,1° - > resolution of 0.1
2 =XX,5° - > resolution of 0.5
3 =XX,0° - > resolution of 1.0
With the parameter “S3/S4 temperature offset” (r04) it is possible to adjust the readout on the display,
while the parameter “Minimum limitation of the lowest temperature readout of the display” (r06) can be
used to limit the lowest possible shown readout.
With the parameter “Temperature unit (°C/°F)” (r05), it is possible to select between °C or °F for the
display read out. Please keep in mind that all settings are in °C only!
4.21.3 Restrictions
None
4.21.4 Dependencies
None
45
4.22
Configuration of
relays
4.22.1 Purpose
The configuration of the relay outputs is pre defined from the factory. They can be redefined via settings
in the controller. Relay R1 to R4 are pre wired internally in the controller, so that no additional, external
junction box is needed.
The max total load of R1 to R4 is 2 Amps, which must be shared for these 4 relays. Please see the
technical data for the controller.
The relay R5 is galvanic isolated from the rest of the electronics and can be used in a separate alarm
circuit or as a changeover relay in certain applications.
4.22.2 Functional description
All 5 relay outputs are mechanical coded, to prevent wiring errors in the production and especially in the
field in cases of service.
With the parameters “Relay x configuration” (L01 to L05), each of the 5 relays can be defined as follows:
"Relay x configuration”
(L01 to L05)
Description
0: Always OFF
No control functions attached to the relay.
1: Always ON
The relay will be activated, as soon as the SLV is connected to the mains supply.
2: ON during operation
The relay will be activated, as soon as the controller is energized and has left the stopped
mode.
3: ON during stopped
The relay will be activated, as long as the controller is energized and in the stopped mode.
4: Follows Compressor
The relay will be ON, as long as the compressor is running
5: Condenser fan
The relay is controlled by the condenser control function
6: Evaporator fan
The relay is controlled by the evaporator control function
7: Defrost
The relay is attached to the defrost control algorithm. The relay will be ON, when defrosting
heat is requested. This can be an electrical heater or a hot gas valve.
8: Drain heater
The relay is controlling the drain heater, which can be energized prior to, during and after a
defrosting.
9: Do not use
The controller isn’t supporting this function yet, which is prepared for a future function.
10: Do not use
The controller isn’t supporting this function yet, which is prepared for a future function.
11: Blind relay
It’s possible to connect a night blind or curtain to the relay output, which will be controlled
by the night blind function.
12: Light relay
It’s possible to connect a cabinet light to the relay output, which will be controlled by the
light function.
13: Do not use
The controller isn’t supporting this function yet, it is prepared for a future function.
14: Do not use
The controller isn’t supporting this function yet, it is prepared for a future function.
15: Alarm relay
The relay is used for local alarm indication. The relay will be activated as soon as the controller is energized and no alarms are active. If a galvanic separated alarm is demanded,
the relay R5 must be used.
16: Temperature logger The relay will be activated, when the temperature limits for the internal temperature logger
alarm relay
have been exceeded and the delay timer has elapsed.
46
17: Do not use
The controller isn’t supporting this function yet, it is prepared for a future function.
18: Control timer
The relay will follow the status of the control timer. The relay will be active, when the control
timer is active.
4.22
Configuration of
relays
(continued)
4.22.3 Restrictions
None
4.22.4 Dependencies
The control of the relay outputs will be overruled, when the controller is put into service mode.
All relays will be de energised during the start up of the controller.
47
4.23
Configuration of
Low voltage I/O
4.23.1 Purpose
The SLV controller contains one digital input DI1 that can be configured for different functions, which
includes overriding the normal control of the SLV, activated by the end user.
4.23.2 Functional description
The DI1 input holds many functions. The parameter “I/O function” (o02) specifies the usage of the DI
inputs. Depending on the DI type/function configured, the DI may operate either as a contact or as a push
button.
The status of the digital input is defined as follows:
⋅⋅ The contact is closed; the DI input is defined to be 1/ON
⋅⋅ The contact is open; the DI input is defined to be 0/OFF
Important remark: The Digital input is not galvanic separated and the input is connected directly to the
mains supply! For that reason, only double isolated switches must be used, as well as the cables must
fulfil the the double insulation requirements
If the DI1 is configured for alarm monitoring, an alarm will be sent out after the delay timer “Alarm delay
for DI1” (A27) has elapsed.
DI1 config.
Function
Description
0
Do not use
No DI1 function enabled
Not in use
1
DI-status / Bus (status only)
Contact, ON=closed
2
Door function
The door will be considered as being closed, as long as the DI1 is OFF
3
Alarm
If the DI1 is ON, an alarm will be sent out after elapse of delay timer
4
Defrost start
The defrosting will be started when the DI1 changes from OFF to ON
5
Main switch on
The controller will go into Stopped mode when the DI1 is OFF
6
Night operation
The controller will go into Night setback mode when the DI1 is ON
(closed)
7
Application change over
The pre defined application will be selected, when the DI is ON
8
Light switch
The Light will be turned ON when the DI is closed
9
Separate alarm
An alarm will be generated if the DI1 is open
10
Case cleaning
The Case cleaning sequence will be started or stepped further when
the DI1 goes from OFF to ON.
11
Do not use
No DI1 function enabled
Not in use
12
Blind cover button
The curtain or night blind will be toggled up or down, every time the
DI1 goes from OFF to ON
13
Do not use
No DI1 function enabled
Not in use
14
Do not use
No DI1 function enabled
Not in use
15
Set point Tref
Not in use
16
Set point CapRef
External compressor capacity given by a 500 kΩ logarithmic potentiometer connected to DI1.
17
Alarm LED
The DI will energise an operating LED simultaneously with the Alarm
LED on the display CRA 172.
18
Operating LED
The DI will energise an operating LED as long as the controller is not
in Stopped mode.
19
Capacity in
Not in use. The lead-lag compressor capacitiy control is not released
by Secop yet. For details please contact Secop.
20
Capacity out
Not in use. The lead/lag compressor capacitiy control is not released
by Secop yet. For details please contact Secop.
21
Do not use
No DI1 function enabled
Not in use
22
Do not use
No DI1 function enabled
Not in use
23
Do not use
No DI1 function enabled
Not in use
4.23.3 Restrictions
The DI1 input has a one second minimum response time before make/break is detected, i.e. a condition
must be present for at least one second before detection.
4.23.4 Dependencies
None
48
4.24
Storing and restoring
to factory settings
2.24.1 Purpose
The SLV controller contains a “Store to factory” and “Restore to factory” function. With this function it is
very convenient for the OEM to program the SLV with his own factory settings. Furthermore, it helps the
service engineer to restore a controller of cooling application in case of “lost overview” during modification
or optimization of setting on site.
2.24.2 Functional description
Storing settings as factory settings “Store to factory setting”(P31) is only possible with an OEM log in, the
restoring function “Restore to factory settings” (P30) is also enabled for the service engineer.
2.24.3 Restrictions
When activating the “Restore to factory” function, all actual settings in the SLV controller will be over
written immediately.
2.24.4 Dependencies
None
49
5.
Parameters
Code T4C
Parameter
group
A03
Temperature
alarms
T4C
Drop down text
T4C
Description of the parameter
High Temperature
alarm delay, during
normal control
Delay timer for high temperature alarms,
during normal control
Configuration
A04
- Door alarm
Delay for door alarm Delay for door alarm, if set to zero the alarm
is turned off. If DI is defined as door contact,
the delay is measured from the moment the
switch is open.
A12 High Temperature
alarm delay, after
power up, defrosting,
case cleaning etc.
Delay timer for high temperature alarms,
after initial start up or defrosting
A13
Temperature
alarms
High alarm limit
Setting for high temperature alarm
A14
Temperature
alarms
Low alarm limit
Setting for low temperature alarm
Alarm Delay for DI
Alarm Delay for DI
Min value = 0
Max value = 240 minutes
For the temperature alarm, a mix of the S3 &
S4 measurement can be used. With a setting
of 100%, only the S4 sensor will be used.
With a setting of 0% only the S3 sensor will
be used. For settings inbetween, a mix will
be used.
Defrost stop
temperature
Min value = 0 and
Max value = 25
An ongoing defrosting will stop as soon as a
defrost stop temperature has been reached.
If this limit has not been reached within the
max defrosting time, the ongoing defrosting
will stop anyway and a “max defrosting Time
exceeded” alarm will be sent out.
In case of a sensor error for the defrost stop
temperature, the defrosting will instead be
terminated on time.
Interval between
defrost start
Min value = 0 and
Max value = 168 hours
Interval between defrost, when multible
defrost per day has been chosen. (d90 = 3)
Max. defrost time
An ongoing defrosting will stop as soon as a
defrost stop temperature has been reached.
Min value = 0 and
If this limit has not been reached within the
Max value = 240 minutes max defrosting time, the ongoing defrosting
will stop anyway and a “Max defrosting Time
exceeded” alarm will be sent out.
Drip off time
Min value = 0 and
Max value = 60 minutes
Configuration
A27 - Low voltage
I/O
A36
Temperature
alarms
d02 Defrost setup
d03
Defrost
Schedule
d04 Defrost setup
d06 Defrost setup
50
T4C
Parameter text
Weighting for alarm
thermostat S4
Delay of compressor and evaporator fan start
after defrosting, to drain remaining drips out
of the evaporator. If set to zero, this function
is obsolete.
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
1
240
min
90
90
30
W
W
W
W
W
x
0
240
min
60
60
60
W
W
W
W
x
1
240
min
240
240
90
W
W
W
W
W
x
-50
50
°C
-14
15
8
W
W
W
W
W
x
-50
50
°C
-30
-10
-30
W
W
W
W
W
x
0
240
min
30
30
30
W
W
W
W
x
0
100
%
100
100
100
W
W
W
W
W
x
0
25
°C
3
5
6
W
W
W
W
W
x
1
168
hrs
4
4
4
W
W
W
W
x
o/skip
240
min
120
45
45
W
W
W
W
W
x
0/skip
60
min
0
0
0
W
W
W
W
51
5. Parameters
(continued)
Code T4C
Parameter
group
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
d07 Defrost setup
Additional delay for
evaporator fan start
after drip off
Min value = 0 and Max
value = 60 minutes
Additional delay for evaporator fan start after
drip off, starting after“Drip off time (d06)” has
elapsed. The delay timer will be cancelled,
if the evaporator temperature is below the
“Evaporator fan start temperature (d08)”.
d08 Defrost control
Evaporator fan start
temperature
Min value = -50 and
Max value = 0
The evaporator fan will not be started, before
the 2 delay timers d06 and d07 have elapsed.
Evaporator fan
d09 Defrost control running during
defrost
Enabled
Disabled
Selection of whether the evaporator fan
should be running during defrosting. For
electrical and hot gas defrosting, the
evaporator is normally stopped, while the fan
normally runs during natural defrosting.
d10 Defrost control Defrost stop sensor
Stop on time
S5
S4
S3
Selection of defrost stop sensor. When
no sensor is detected, the defrosting is
terminated on time. If a sensor is selected
and detected as defective, an sensor error
alarm is sent out and the defrosting is
terminated on time.
d20 Defrost control
Drain post heating
time
Min value = 0 and
Additional ON time for the drain heater, after
Max value = 240 minutes the defrosting is terminated.
d39 Defrost control
Compressor capacity Min value = 0 and
during Drain Preheat Max value = 100 %
d40 Defrost control
Drain pre heating
time
d41 Defrost control
During the defrosting cycle and during
Maximum pull down Min value = 0 and
the aftercoming pull down of the cabinet
time. after defrosting Max value = 240 minutes temperature, the local display will read out
the “dEF” code.
Drain preheating time for drain, prior to a
Min value = 0 and
defrosting, to make sure that the drain is free.
Max value = 240 minutes
If set to zero, this function is obsolete.
Compressor capacity
d42 Defrost control during hot gas
Min value = 0 and
defrosting
Max value = 100 %
Compressor capacity during hot gas
defrosting. For electrical or natural
defrosting, this setting must be zero
d43 Defrost control
Compressor capacity Min value = 0 and
during drip off time
Max value = 100 %
Capacity during drip off time
d60 Defrost setup
Allow remote start of Disabled
defrost
Enabled
Allow remote start of defrost via Modbus.
d61 Defrost setup
Allow local disply to
start defrost
Manual start of defrost via local display
Defrost
d62
Schedule
Min interval between Min value = 0 and
manual defrost.
Max value = 168 hours
Min interval between manual defrost, to
avoid too many defrosting cycles, initiated by
an inexperienced daily user. Can be reset by
switching OFF and ON the controller. If set to
zero, there is no limitation.
Defrost
d71
Schedule
1st daily start or
Sunday hour
(-1 = not active)
Min value = -1 and
Max value = 23 hours
If 1 defrost per day is selected (d90 = 1), this
parameter gives the starting hour for Sunday.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start hour for the 1st defrost.
Defrost
Schedule
2nd daily start or
Monday hour
(-1 = not active)
Min value = -1 and
Max value = 23 hours
If 1 defrost per day is selected (d90 = 1),
this parameter gives the starting hour for
Monday.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start hour for the 2nd defrost.
d72
52
For electrical and natural defrosting, this
parameter should be set to 0. Once it has
been decided to start a defrost, it makes
no sense to spend compressor energy on
keeping the evaporator cold.
For hot gas defrosting it must be considered
to set the capacity between 50 and 100%, not
to loose the high condensing pressure.
Disabled
Enabled
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
0
60
min
0
0
0
W
W
W
W
x
-50
0
°C
-5
-5
-5
W
W
W
W
x
0/no
1/yes
-
0
0
1
W
W
W
W
x
0
3
-
1
1
0
W
W
W
W
x
0
240
min
0
0
30
W
W
W
W
x
0
100
%
0
0
0
W
W
W
x
0/skip
240
min
3
3
0
W
W
W
W
x
0
240
min
90
90
0
W
W
W
W
x
0
100
%
90
90
0
W
W
W
W
x
0
100
%
0
0
0
W
W
W
x
0
1
-
1
1
0
W
W
W
W
W
x
0
1
-
1
1
0
W
W
W
W
x
0
168
hrs
21
21
0
W
W
W
W
x
-1
23
hrs
-1
1
.1
W
W
W
W
W
W
x
-1
23
hrs
1
-1
-1
W
W
W
W
W
W
53
5. Parameters
(continued)
Code T4C
Parameter
group
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
Defrost
d73
Schedule
3rd daily start or
Tuesday hour
(-1 = not active)
Min value =-1 and
Max value = 23 hours
If 1 defrost per day is selected (d90 = 1), this
parameter gives the starting hour for Tuesday.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start hour for the 3rd defrost.
Defrost
Schedule
4th daily start or
Wednesday hour
(-1 = not active)
Min value = -1 and
Max value = 23 hours
If 1 defrost per day is selected (d90 = 1),
this parameter gives the starting hour for
Wednesday.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start hour for the 4th defrost.
Defrost
Schedule
5th daily start or
Thursday hour
(-1 = not active)
Min value = -1 and
Max value = 23 hours
If 1 defrost per day is selected (d90 = 1),
this parameter gives the starting hour for
Thursday.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start hour for the 5th defrost.
Defrost
Schedule
6th daily start or
Friday hour
(-1 = not active)
Min value = -1 and
Max value = 23 hours
If 1 defrost per day is selected (d90 = 1), this
parameter gives the starting hour for Friday.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start hour for the 6th defrost.
Defrost
Schedule
7th daily start or
Saturday hour
(-1 = not active)
Min value = -1 and
Max value = 23 hours
If 1 defrost per day is selected (d90 = 1),
this parameter gives the starting hour for
Saturday.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start hour for the 7th defrost.
Defrost
d78
Schedule
8th daily start hour
(-1 = not active)
Min value = -1 and
Max value = 23 hours
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start hour for the 8th defrost.
Defrost
d81
Schedule
1st daily start minute Min value = -1 and
(-1 = not active)
Max value = 59 minutes
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start minute for the 1st defrost.
Defrost
Schedule
2nd daily start
minute
(-1 = not active)
Min value = -1 and
Max value = 59 minutes
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start minute for the 2nd defrost.
Defrost
Schedule
3rd daily start
minute
(-1 = not active)
Min value = -1 and
Max value = 59 minutes
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start minute for the 3rd defrost.
Defrost
Schedule
4th daily start
minute
(-1 = not active)
Min value = -1 and
Max value = 59 Minutes
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start minute for the 4th defrost.
Defrost
d85
Schedule
5th daily start
minute
(-1 = not active)
Min value = -1 and
Max value = 59 minutes
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start minute for the 5th defrost.
Defrost
d86
Schedule
6th daily start
minute
(-1 = not active)
Min value = -1 and
Max value = 59 minutes
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start minute for the 6th defrost.
d74
d75
d76
d77
d82
d83
d84
54
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
-1
23
hrs
-1
-1
-1
W
W
W
W
W
W
x
-1
23
hrs
-1
-1
-1
W
W
W
W
W
W
x
-1
23
hrs
1
-1
-1
W
W
W
W
W
W
x
-1
23
hrs
-1
-1
-1
W
W
W
W
W
W
x
-1
23
hrs
-1
-1
-1
W
W
W
W
W
W
x
-1
23
hrs
-1
-1
-1
W
W
W
W
x
0
59
min
0
0
0
W
W
W
W
x
0
59
min
0
0
0
W
W
W
W
x
0
59
min
0
0
0
W
W
W
W
x
0
59
min
0
0
0
W
W
W
W
x
0
59
min
0
0
0
W
W
W
W
x
0
59
min
0
0
0
W
W
W
W
55
5. Parameters
(continued)
Code T4C
Parameter
group
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
Defrost
d87
Schedule
7th daily start
minute
(-1 = not active)
Min value = -1 and
Max value = 59 minutes
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start minute for the 7th defrost.
Defrost
d88
Schedule
8th daily start
minute (-1 = not
active)
Min value = -1 and
Max value = 59 minutes
If 1 defrost per day is selected (d90 = 1), this
parameter has no effect.
If multiple defrosts per day have been
selected (d90 = 2), this parameter gives the
start minute for the 8th defrost.
Number of
defrostings
Never
One pr. Day
Multi pr. day fixed hour
Multiple pr. day timer
based
Defrost on Demand
d90
Defrost
Schedule
Evaporator fan Evaporator Fan
F01
control
mode
F03
F04
Evaporator fan Evaporator Fan stop
control
on door open
Evaporator fan Evaporator Fan stop
control
temperature (Tdefr)
Evaporator fan Evaporator Fan
F05
control
Pulsing
56
Selection of number of automatic defrosts per
day or week.
0 =Never
1 =One per day, based on the real time clock
2 =Multi defrost pr. day at fixed hour, based on the real time clock
3 =Multiple per day, timer based with fixed interval, set via d03.
Off
Enabled
Enabled on Tdefr
Selection of evaporator fan control mode:
0 =No evaporator fan control
1 =Enabled, for details see parameter
F03 to F07
2 =Enabled and fan stop check on Tdefr (F04)
No
Yes, expect defrosting
If the DI1 is set up as a door switch, this
parameter specifies whether to stop the
evaporator fan during door opening or not.
0 = No, evaporator fan continues running.
1 = Yes, evaporator stop at door open
Min value = -50 and
Max value = 50
To avoid heating of the cabinet, in case the
cooling stops, the evaporator temperature is
monitored. If the evaporator fan mode (F01) is
set to 2, this gives the maximum temperature
for the evaporator, measured with Tdef. . If
exceeding this value the fan must stop. The
Fan must start again when the temperature at
Tdefr falls below F04 – 2 K.
No pulse operation
At compressor cut out
Compressor cut out at
night
During night
In certain cooling applications, it might be
beneficial, to pulse the evaporator fan during
predifined conditions:
0 =No pulse operation
1 =At compressor cut out only
2 =Only at compressor stop during night operation
3 =During night
F06
Evaporator Fan
Evaporator fan
Min value = 1 and
period time for pulse
control
Max value = 30 Minutes
mode
If pulsing mode is active, this setting gives the
pulsing period time.
F07
Evaporator Fan OnEvaporator fan
time in % of period
control
time
Min value = 0 and
Max value = 100 %
If pulsing mode is active, this parameter gives
the ON - time in % compared to the period
time.
F11
Condenser fan Condenser Fan
control
mode
Off
Run with compressor
Hysteretic controlled
by S3b
Always Run unless
stopped
Running mode for condenser fan, if present.
F12
Condenser fan Condenser Fan start Min value = -50 and
control
temperature (S3b)
Max value = 50
Cut in value for condenser fan during
hysteretic control. Based on temperature
measured with S3b
F13
Condenser fan Condenser Fan stop
control
temperature (S3b)
Min value = -50 and
Max value = 50
Cut out value for condenser fan during
hysteretic control. Based on temperature
measured with S3b
F14
Condenser Fan
Condenser fan
Alarm temperature
control
(S3b)
Min value = -50 and
Max value = 50
High temperature alarm limit for condenser
fan control. Based on temperature measured
with S3b
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
0
59
min
0
0
0
W
W
W
W
x
0
59
min
0
0
0
W
W
W
W
x
0
4
-
1
1
0
W
W
W
W
W
W
x
0
2
-
0
0
1
W
W
W
W
x
0/no
1/yes
-
1
1
1
W
W
W
W
x
-50
50
°C
10
10
10
W
W
W
W
x
0
3
-
0
0
0
W
W
W
W
x
1
30
min
5
5
5
W
W
W
W
x
0
100
%
100
100
100
W
W
W
W
x
0
3
-
1
1
3
W
W
W
x
-50
50
°C
50
50
50
W
W
W
x
-50
50
°C
50
50
50
W
W
W
x
0
50
°C
0
0
0
W
W
W
57
5. Parameters
(continued)
Code T4C
Parameter
group
T4C
Parameter text
Condenser fan Condenser Fan
F15
control
Pulsing
T4C
Drop down text
T4C
Description of the parameter
No pulse operation
During night
If active, the condenser fan will be pulsed
during the night mode.
0 = No pulse operation
1 = During night
Condenser Fan
F16 Condenser fan
Min value = 1 and
period time for pulse
control
Max value = 30 minutes
mode
F17
Condenser Fan OnCondenser fan
time in % of period
control
time
Min value = 0 and
Max value = 100 %
If condenser fan pulsing is chosen to be active
during the night mode, this parameter gives
the ON time during this period.
g02
Compressor
control
Compressor Restart
time
Minimum time between two starts.
g03
Compressor
control
Compressor
Minimum Stop time
Minimum compressor stop time, betwen stop
and new start
g04
Compressor
control
Compressor
Minimum Run time
Minimum run time, once the compressor
has started, Regardless of actual requested
compressor capacity
g05
Compressor
control
Compressor Period
time
If the requested compressor capacity goes
below 50%, the compressor starts and stops
in a PWM pattern, where the duty cycle
changes from 0 too 100. With this parameter,
the period time is set.
g16
Compressor
control
Compressor status
Running
Read out if compressor is running or not.
Compressor
g17
control
Compressor speed
percentage when
running
Read out of the actual compressor speed
in % of the variable speed band. 0% means
minimum speed and 100% means maximum
speed.
Configuration
h01 -Temperature
logger
Log interval
Min value = 15 and
Max value = 240
Log interval for the temperature logger, The
smaller the logging interval is selected, the
sooner the logger will be full and over write
previous logs.
Configuration
High threshold for
h02 - Temperature
logging
logger
58
If condenser fan pulsing is chosen to be active
during the night mode, this parameter gives
the length of the pulsing interval
Min value = -50 and
Max value = 50
“High Threshold” ≥ “Low Threshold”:
Temperatures outside or on these limits will
be logged.
“Low Threshold” > “High Threshold”:
Temperatures inside or on these limits will be
logged.
“High Threshold” ≥ “Low Threshold”:
Temperatures outside or on these limits will
be logged.
Configuration
Low threshold for
h03 - Temperature
logging
logger
Min value = -50 and
Max value = 50
h04 1=Clear (Auto reset)
Clearing of the temperature logger
Configuration Selection of sensor
h11 - Temperature for the logger
logger
function
None
S6
TS3/S4
Talarm
Tact
S5
S3B
The SLV has an internal temperature
logger, which can log one of the following
parameters:
0 =No logging function defined
1 =S6 temperature, with a Pt1000 sensor
2 =TS3/S4 temperature,
3 =Talarm temperature,
4 =Tact temperature,
5 =S5 temperature,
6 =S3B temperature,
Configuration
Alarm limit for the
h12 - Temperature
logger function
logger
Min value = -50 and
Max value = 50
High alarm limit for the temperature logger
Configuration
Time delay for the
h13 - Temperature
alarm
logger
Min value = 1 and
Max value = 60 minutes
Time delay for high temperature alarm on the
Temperature logger
Clear Datalog
“Low Threshold” > “High Threshold”:
Temperatures inside or on these limits will be
logged.
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
0
1
-
0
0
0
W
W
W
x
1
30
min
5
5
5
W
W
W
x
0
100
%
100
100
100
W
W
W
x
0
10
min
2
2
2
W
W
W
x
0
240
sec
90
90
90
W
W
W
x
0
240
sec
30
30
30
W
W
W
x
5
30
min
15
15
15
W
W
W
0
1
-
R
R
R
R
R
R
0
(2000
RPM)
100
(4000
RPM)
%
R
R
R
R
R
R
x
15
240
Min
30
30
30
W
W
W
W
W
W
W
x
-50
50
°C
-50
-50
0
W
W
W
x
-50
50
°C
50
50
0
W
W
W
0
1
-
W
W
W
x
0
6
-
4
4
0
W
W
W
W
W
x
-50
50
°C
-14
15
8
W
W
W
W
W
W
x
1
60
min
60
60
30
W
W
W
W
W
W
59
5. Parameters
(continued)
60
Code T4C
Parameter
group
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
Configuration
L01 - Relay
configuration
Configuration of Relay 1:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON when stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
Relay 1 configuration 8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
Configuration of Relay 1:
0: Always OFF
1: Aways ON
2:ON during operation
3ON when stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
Configuration
L02 - Relay
configuration
Configuration of Relay 1:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON when stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
Relay 2 configuration 8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
Configuration of Relay 2:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON when stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
Configuration
L03 - Relay
configuration
Configuration of Relay 1:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON when stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
Relay 3 configuration 8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
Configuration of Relay 3:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON when stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
Configuration
L04 - Relay
configuration
Configuration of Relay 1:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON when stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
Relay 4 configuration 8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
Configuration of Relay 4:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON when stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
T4C
Help
Text
Multi
Apps
x
x
x
x
Min
Max
Unit
Default
App. 1
0
18
(19: not
used.
20:
relay
1 test)
-
0
18
(19: not
used.
21:
relay
2 test)
-
Always
off0
0
18
(19: not
used.
22:
relay
3 test)
-
Defrost
relay 7
0
18
(19: not
used.
23:
relay
4 test)
-
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
5
Always
off0
6
Defrost
relay 7
8
Light
Light
Relay 12 Relay 12
7
Follow
Follow
comcompressor 4 pressor 4
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
W
W
W
W
W
W
W
W
W
W
W
W
61
5. Parameters
(continued)
Code T4C
Parameter
group
T4C
Drop down text
T4C
Description of the parameter
Configuration
L05 - Relay
configuration
Configuration of Relay 1:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON during stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
Relay 5 configuration 8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
Configuration of Relay 5:
0: Always OFF
1: Aways ON
2:ON during operation
3:ON during stopped
4: Follows Compressor
5: Condenser fan
6:Evaporator fan
7: Defrost
8: Drain heater
11:Blind relay
12:Light relay
13:Do not use
14:Do not use
15:Alarm relay
16:Temperature logger alarm relay
17:Do not use
18:Control timer
L50 Service Mode
PCB temperature
Controller temperature on the circuit board
L51 Service Mode
Inverter temperature Controller temperature on the inverter
module
L52 Service Mode
Mains voltage supply Readout of mains supply voltage
L53 Service Mode
Mains frequency
Readout of mains supply frequency
L60 Service Mode
Compressor manual on
control
off
Compressor in manual mode
L61 Service Mode
Compressor actual
state
Indication of wether the compressor is
running or not
L62 Service Mode
Compressor manual
speed percentage
when running
Setpoint of the actual compressor speed, in
% of the variable speed band during manual
control.
0% means compressor runs at minimum
speed and 100% means that the compressor
runs at max speed during service mode.
L63 Service Mode
Compressor actual
speed percentage
when running
Readout of the actual compressor speed, in
% of the variable speed band during manual
control.
0% means compressor runs at minimum
speed and 100% means that the compressor
runs at max speed during service mode.
Actual motor speed
Readout of actual compressor speed in RPM
Emergency cooling
Capacity during S3 /
S4 error
Min value = 0 and Max
value = 100
%
In case of a sensor error, the compressor
capacity will be reset to this value
L99
Enhanced
Overview Enhanced
Overview
Configuration
n21 - Safety
function
n22
Compressor
control
Compressor
Capacity Switching
on door open (n23)
on
off
If the DI1 input is defined as a door switch,
the compressor will be completely stopped.
n23
Compressor
control
Compressor
Capacity at door
open
Min value = 0 and Max
value =100
If the DI1 input is defined as a door switch,
the compressor capacity will be reset to this
value.
Capacity Override
mode
0:No override
1:Override, followed by resuming previous capacity.
2:Override, followed by Pull dow or Pull up
Readout of the input for capacity controller:
0:No override
1:Override, followed by resuming previous capacity.
2:Override, followed by Pull down or Pull up
Compressor
control n28
Advanced
settings
62
T4C
Parameter text
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
0
18
(19: not
used.
24:
relay
5 test)
-
Always
off0
Always
off0
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
Alarm
Relay
15
T4C
LL
T4C
DSL
T4C
DDL
W
W
W
x
0
100
(61691) (15329)
°C
(Bit)
R
R
R
R
0
150
(1989) (52469)
°C
(Bit)
R
R
R
R
0
307
V
R
R
R
R
40
(valid
limit)
70
(valid
limit)
Hz
R
R
R
R
0
1
-
R
R
R
R
R
R
0
1
-
R
R
R
R
0
(2000
RPM)
100,00
(4000
RPM)
%
R
R
W
W
W
W
0
(2000
RPM)
100,00
(4000
RPM)
%
R
R
R
R
0
6000
RPM
R
R
R
R
x
0
100
%
60
30
50
W
W
W
W
x
0/no
1/yes
-
1
1
1
W
W
W
x
0
100
%
50
50
50
W
W
W
W
0
2
-
R
R
R
R
R
63
5. Parameters
(continued)
Code T4C
Parameter
group
n29
n30
Compressor
control Advanced
settings
Compressor
control
Compressor
control n35
Advanced
settings
Compressor
control n36
Advanced
settings
Compressor
control n37
Advanced
settings
n38
64
Compressor
control Advanced
settings
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
Capacity Override
value
Read out of requested compressor capacity
during override
Smart setting for PI
control
PID polynomial R1
PID polynomial R2
PID polynomial S0
PID polynomial S1
0:User defined
1:Very slow control
2:Slow control
3:Medium control (Default)
4:Fast control
5:Very fast control
The settings for the PI controller can be
defined by the user, in close cooperation with
Secop. As a starting point it is suggested
to start with “Medium Control” If faster
or slower capacity adaptation is needed,
for instance in small cabinets or control
according to air temperature, the speed can
be increased or vice versa.
0:User defined
1:Very slow control
2:Slow control
3:Medium control (Default)
4:Fast control
5:Very fast control
Min value = -50 and
Max value = 50
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
compared to the reference temperature Tref.
The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
Min value = -50 and
Max value = 50
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
compared to the reference temperature Tref.
The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
Min value = -50 and
Max value = 50
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
compared to the reference temperature Tref.
The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
Min value = -50 and
Max value = 50
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
compared to the reference temperature Tref.
The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
0
100
%
R
R
R
R
R
R
x
0
10
no test
3
3
3
W
W
W
(no
copy)
W
(no
copy)
W
(no
copy)
W
(no
copy)
x
-50.00
50,0
-
W
W
W
x
-50.00
50,0
-
W
W
W
x
-50.00
50,0
-
W
W
W
x
-50.00
50,0
-
W
W
W
65
5. Parameters
(continued)
Code T4C
Parameter
group
n39 Compressor
control n40
Advanced
settings
Compressor
control n41
Advanced
settings
n42
n43
66
Compressor
control Advanced
settings
Compressor
control Advanced
settings
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
Min value = -50 and
Max value = 50
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
compared to the reference temperature Tref.
The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
Min value = -50 and
Max value = 50
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
compared to the reference temperature Tref.
The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
Min value = -50 and
Max value = 50
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
compared to the reference temperature Tref.
The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
PID polynomial T2
Min value = -50 and Max
value = 50
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
compared to the reference temperature Tref.
The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
h sampling time
The SLV controller is using a PID controller
for the calculation of the appropriate
compressor capacity, based upon the
deviation of the actual cabinet temperature
Min value = 10 and
compared to the reference temperature Tref.
Max value = 600 Seconds The bigger the deviation, then the faster the
compressor speed increases or decreases.
The adaptation of the 8 polynomial values
and the sampling time should only be done in
close cooperation with Secop.
PID polynomial S2
PID polynomial T0
PID polynomial T1
Compressor
control n46
Advanced
settings
Tact below Tref to
start Pull Up limit
Compressor
control n47
Advanced
settings
Tact above Tref to
start Pull Down
Limit
Min value = -10;
Max value = 0 K
At sudden load fluctuations, the cabinet
temperature falls below this limit. In such
cases a forced pull up is iniated once the
timer n50 has elapsed, in order to get the
cabinet temperature inside the range as fast
as possible.
Min value = 0 and
Max value = 10 K
At sudden load fluctuations, the cabinet
temperature reaches above this limit. In such
cases a forced pull down is iniated once the
timer n50 has elapsed, in order to get the
cabinet temperature inside the range as fast
as possible.
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
-50.00
50,0
-
W
W
W
x
-50.00
50,0
-
W
W
W
x
-50.00
50,0
-
W
W
W
x
-50.00
50,0
-
W
W
W
x
10
600
sec
30
30
30
W
W
W
W
x
-10
0
K
-3
-3
-3
W
W
W
W
x
0
10
K
3
3
3
W
W
W
W
67
5. Parameters
(continued)
Code T4C
Parameter
group
Compressor
control n48
Advanced
settings
Compressor
control n49
Advanced
settings
T4C
Drop down text
T4C
Description of the parameter
Min vallue= -10 and
Max value = 10 K
An ongoing pull down will stop when the
cabinet temperature reaches this value. This
“under shoot” in temperature helps the PI
controller to hit the right compressor capacity
after a pull down. The result is a more stable
temperature control.
Tact above Tref to
end Pull Up
Min vallue= -10 and
Max value = 10 K
An ongoing pull up will stop when the
cabinet temperature reaches this value. This
“over shoot” in temperature helps the PI
controller to hit the right compressor capacity
after a pull up. The result is a more stable
temperature control.
Tact below Tref to
end Pull Down
n50
Compressor
control Advanced
settings
Temperature out of
range timeout
Min value = 0 and
Time to elapse, before a forced pull up or pull
Max value = 1800 minutes down is initated.
n51
Compressor
control Advanced
settings
Optimized pull down
time
When the SLV controller decides to initiate a
Min value = 0 and
new pull down, the compressor capacity will
Max value = 1800 minutes be set to “The optimised pull down capacity
(n52)” as long as this timer is active.
Compressor
control n52
Advanced
settings
Optimized pull down
capacity
Min value = 20 and
Max value = 100 %
n53
Compressor
control Advanced
settings
Compressor capacity during the “Optimised
pull down time (51)”
Compressor capacity Min value = 0 and
after pulldown day
Max value = 100 %
At initial start up or start up after power down
during the day time, the SLV controller will
use this “Best guess” as a starting point for
the PI controller after the pull down.
In all other cases the SLV controller will
remember the actual running compressor
capacity and revert back to this after the pull
down.
At initial start up or start up after power down
during the night time, the SLV controller will
use this “Best guess” as a starting point for
the PI controller after the pull down.
In all other cases the SLV controller will
remember the actual running compressor
capacity and revert back to this after the pull
down.
n54
Compressor
control Advanced
settings
Compressor capacity Min value = 0 and
after pulldown night Max value =100 %
n55
Compressor
control Advanced
settings
Requested capacity
Min value = 0 and
Max value = 100 %
Readout of the actual requested compressor
capacity
Controller state
Readout of the current controller state:
0 = Off
1 = Pull down
2 = Pull up
3 = In range
4 = Out of range Up
5 = Out of range Down
6 = Override
n80 Under voltage
Cut out
n81 Under voltage
Cut in
n82 Over voltage alarm
n56
68
T4C
Parameter text
Compressor
control Advanced
settings
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
-10
10
K
0
0
0
W
W
W
W
x
-10
10
K
0
0
0
W
W
W
W
x
0.0
30.0
min
4
4
4.0
W
W
W
W
x
0.0
30.0
min
10
10
10.0
W
W
W
W
x
20
100
%
60
60
60
W
W
W
W
x
0
100
%
60
60
60
W
W
W
W
x
0
100
%
55
55
55
W
W
W
W
0
100
%
R
R
R
R
R
0
6
-
R
R
R
R
R
R
fix
36301
fix
36301
AD
value
(V AC)
R
R
R
W
fix
38436
fix
38436
AD
value
(V AC)
R
R
R
W
fix
56373
fix
56373
AD
value
(V AC)
R
R
R
W
69
5. Parameters
(continued)
Code T4C
Parameter
group
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
I/O function
None
Do not use
Door function
Alarm
Defrost start
Main switch
Night operation
Application changeover
Light switch
Separate alarm open
Case cleaning
Do not use
Blind cover button
Do not use
Do not use
Setpoint Tref.
Setpoint CapRef
Alarm LED
Operating LED
Capacity in
Capacity out
Do not use
Do not use
Do not use
Modbus address
Setting for the Modbus address. If this setting
is modified remotely, the controller will be
lost on the modbus, until the new address is
recognised from the front end. If the address
is set outside the accessible address range,
the controller will remain invisible.
Configuration
o04 - Application
setup
Modbus baud rate
1 = 9600
2= 19200
Setting for the Modbus baud rate if this
setting is modified remotely, the controller
will be lost on the modbus, until the new baud
rate has been changed in the front end.
o05 Service Mode
Access code
enduser
Min value = -999 and
Max value = 999
Acces code for the end user level on the
display
o06 Service Mode
Access code
installer
Min value = -999 and
Max value = 999
Acces code for the installer level on the
display
o07 Service Mode
Access code
service
Min value = -999 and
Max value = 999
Acces code for the service level on the display
o08 Service Mode
Access code
OEM lab
Min value = -999 and
Max value = 999
Acces code for the OEM level on the display
Display temperature
step resolution
0,1
0,5
1,0
The temperature read out of the display is
shown with one digit after the comma. Here
you select the step resolution.
1 = XX,1° - > resolution of 0.1
2 = XX,5° - > resolution of 0.5
3 = XX,0° - > resolution of 1.0
Max hold time after
coordinated defrost
If Max hold time after coordinated defrost is
set active and the ADAP COOL system has set
a hold request through the Modbus register
Min value = 0 and
2022 the pull down must be delayed until the
Max value = 360 minutes signal is received from the master to resume
cooling the o16 time expires.
If the o16 time expires an alarm A5 must be
signalled.
Configuration
o02 - Low voltage
I/O
Configuration
o03 - Application
setup
Configuration
o15 - User
interface
o16 Defrost control
Configuration
o17 - User
interface
70
S3/S4 weighting
(100%=S4, 0%=S3)
Min value = 0 and
Max value = 100 %
For the temperature read out on the display
a mix of the S3 & S4 measurements can be
used. With a setting of 100%, only the S4
sensor will be used. With a setting of 0% only
the S3 sensor will be used. For settings in
between, a mix will be used.
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
x
0
23
-
0
0
0
1
247
-
1
1
1
W
W
1
2
-
2
2
2
W
-999
999
-
0 - off
0 - off
0
-999
999
-
11
11
0
-999
999
-
22
22
-999
999
-
33
33
2 = XX,5° 2 = XX,5°
->
->
resolut- resolution of 0.5 ion of 0.5
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
0
W
W
W
W
0
W
W
W
W
2
W
W
W
W
x
1
3
°K
x
0/skip
240
min
20
20
20
W
W
W
W
S4%
(100%
= S4,
0% =
S3)
x
0
100
%
100
100
100
W
W
W
W
71
5. Parameters
(continued)
Code T4C
Parameter
group
o38
Configuration
- light control
T4C
Parameter text
T4C
Drop down text
o38a:
Configuration light
by night condition
Enabled
Disabled
o38b:
Configuration light
by door switch
o38c:
Control light by o39
Disabled
o39 control
o39 network timeout
Illegal
Enabling of controls that can turn off the light.
As default the light will always be on.
o39
Configuration
- light control
Remote Activation of on
light relay
off
o40
Configuration
- light control
Light turn off delay
after door close.
Min value = 0 and
Delay of Light Off, after closing the door
Max value = 240 minutes
o41
Configuration
- light control
Inverted Light
function
Enabled
Disabled
Configuration
o46 - Case
cleaning
o91
Inverted light function, so that the relay is on
during the day time.
Readout of the case cleaning status
0: Not started
1: De icing
2: Waiting for cleaning
Deicing method
Selection of de icing method during a melting
cycle. 0: Compressor stop
1: Execute defrost
Blind function
None
Night
Selection of how to start the blind function
Auto acknowledge
timer (0 disabled)
0 = off, 1-240min
Auto acknowledgement timer for alarms
0: No auto acknowledgement
1 - 240: delay
Configuration- Filter constant for
Calibration
Tact
no filter
0,10 K/sec
0,09 K/sec
0,08 K/sec
0,07 K/sec
0,06 K/sec
0,05 K/sec
0,04 K/sec
0,03 K/sec
0,02 K/sec
0,01 K/sec
In some cases it might be useful to slower
the updating speed of the actual temperature
value:
0: No damping, (fastest updating)
1: 0,10 K/sec
2: 0,09 K/sec
3: 0,08 K/sec
4: 0,07 K/sec
5: 0,06 K/sec
6: 0,05 K/sec
7: 0,04 K/sec
8: 0,03 K/sec
9: 0,02 K/sec
10: 0,01 K/sec (slowest updating)
Temperature
alarms
no filter
0,10 K/sec
0,09 K/sec
0,08 K/sec
0,07 K/sec
0,06 K/sec
0,05 K/sec
0,04 K/sec
0,03 K/sec
0,02 K/sec
0,01 K/sec
In some cases it might be useful to slower
the updating speed of the alarm temperature
value:
0: No damping, (fastest updating)
1: 0,10 K/sec
2: 0,09 K/sec
3: 0,08 K/sec
4: 0,07 K/sec
5: 0,06 K/sec
6: 0,05 K/sec
7: 0,04 K/sec
8: 0,03 K/sec
9: 0,02 K/sec
10: 0,01 K/sec (slowest updating)
Configuration
o62 - Blind
function
o90
Case cleaning status Activation of light via modbus
Compressor off
Execute defrost
Configuration
o47 - Case
cleaning
o84
72
Enable
Disabled
T4C
Description of the parameter
Alarm
handling
Filter constant for
Talarm
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
x
0
15
-
a38a=En
a38b=En
a38c=o39
control
a38a=En
a38b=En
a38c=o39
control
only if
o38 =
2 or 4)
On =
light
0/Off
1/On
-
1
(only
if o38
= 3)
x
0
0
min
x
0
0
0
x
T4C
LL
T4C
DSL
T4C
DDL
a38a=En
a38b=En
a38c=o39
control
W
W
W
1
0
W
W
W
0
0
2
W
W
W
-
0
0
0
W
W
W
2
-
0
0
0
R
R
R
R
0
1
-
0
0
0
W
W
W
W
x
0
1
-
0
0
0
W
W
W
W
W
W
0
240
min
0
0
0
W
W
W
(0 =
Fastest,
10 =
Slowest)
x
0
10
D°K/
sec
1
W
W
W
x
0
10
D°K/
sec
1
W
W
W
1= 0.1K/ 1= 0.1K/
sec
sec
1
1
Display
T4C
Prod. Service
Level
73
5. Parameters
(continued)
Code T4C
Parameter
group
o92
T4C
Drop down text
T4C
Description of the parameter
no filter
0,10 K/sec
0,09 K/sec
0,08 K/sec
0,07 K/sec
0,06 K/sec
0,05 K/sec
0,04 K/sec
0,03 K/sec
0,02 K/sec
0,01 K/sec
In some cases it might be useful to slower
the updating speed of the weighted S3/S4
temperature value:
0: No damping, (fastest updating)
1: 0,10 K/sec
2: 0,09 K/sec
3: 0,08 K/sec
4: 0,07 K/sec
5: 0,06 K/sec
6: 0,05 K/sec
7: 0,04 K/sec
8: 0,03 K/sec
9: 0,02 K/sec
10: 0,01 K/sec (slowest updating)
None
Light switch
Night Mode
Defrost stop temperature
S6 temperature
S5 temperature
Readout of S3b
temperature
Actual Tref
The lower right button of the display contains
a number of predefined functions:
0 = No function
1 = Activation of Light ON /OFF
2 = Activation of Night Mode,
3 = Read out of Defrost stop temperature,
4 = Read out of S6 temperature,
5 = Read out of S5 temperature,
6 = Read out of S3b temperature,
7 = Read out of Actual Tref
Configuration- Filter constant for
Calibration
S5
no filter
0,10 K/sec
0,09 K/sec
0,08 K/sec
0,07 K/sec
0,06 K/sec
0,05 K/sec
0,04 K/sec
0,03 K/sec
0,02 K/sec
0,01 K/sec
In some cases it might be useful to slower the
updating speed of the S5 temperature value:
0: No damping, (fastest updating)
1: 0,10 K/sec
2: 0,09 K/sec
3: 0,08 K/sec
4: 0,07 K/sec
5: 0,06 K/sec
6: 0,05 K/sec
7: 0,04 K/sec
8: 0,03 K/sec
9: 0,02 K/sec
10: 0,01 K/sec (slowest updating)
Configuration- Filter constant for
Calibration
S6
no filter
0,10 K/sec
0,09 K/sec
0,08 K/sec
0,07 K/sec
0,06 K/sec
0,05 K/sec
0,04 K/sec
0,03 K/sec
0,02 K/sec
0,01 K/sec
In some cases it might be useful to slower the
updating speed of the S6 temperature value:
0: No damping, (fastest updating)
1: 0,10 K/sec
2: 0,09 K/sec
3: 0,08 K/sec
4: 0,07 K/sec
5: 0,06 K/sec
6: 0,05 K/sec
7: 0,04 K/sec
8: 0,03 K/sec
9: 0,02 K/sec
10: 0,01 K/sec (slowest updating)
Configuration- Filter constant for
Calibration
S3b
no filter
0,10 K/sec
0,09 K/sec
0,08 K/sec
0,07 K/sec
0,06 K/sec
0,05 K/sec
0,04 K/sec
0,03 K/sec
0,02 K/sec
0,01 K/sec
In some cases it might be useful to slower the
updating speed of the S3b temperature value:
0: No damping, (fastest updating)
1: 0,10 K/sec
2: 0,09 K/sec
3: 0,08 K/sec
4: 0,07 K/sec
5: 0,06 K/sec
6: 0,05 K/sec
7: 0,04 K/sec
8: 0,03 K/sec
9: 0,02 K/sec
10: 0,01 K/sec (slowest updating)
Alarm
handling
None
Application Faults
All
Selection of alarm level on the relay:
0 =No alarm indication at all
1 =Only User Application Faults
(System related)
2 =All
Configuration- Filter constant for
Calibration
TS3/S4
Configuration
o93 - User
interface
o94
o95
o96
o97
74
T4C
Parameter text
Definition of
functionality on
lower button
Alarm on relay
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
x
0
10
D°K/
sec
1= 0.1K/ 1= 0.1K/
sec
sec
1
0
7
-
0
x
0
10
D°K/
sec
1= 0.1K/ 1= 0.1K/
sec
sec
1
x
0
10
D°K/
sec
1= 0.1K/ 1= 0.1K/
sec
sec
1
x
0
10
D°K/
sec
1= 0.1K/ 1= 0.1K/
sec
sec
1
0
2
-
2
1
1
Default
App. 2
1
1
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
75
5. Parameters
(continued)
Code
T4C
Parameter
group
Configuration
o98 - User
interface
T4C
Drop down text
T4C
Description of the parameter
Selection of alarm level on the display:
0 =No alarm indication at all
1 = Only User Application Faults
(System related)
2 =All
Alarm on display
None
Application Faults
All
Configuration
o99 - User
interface
Display temperature
TS3/TS4
T Temperature logger
Tact
Talarm
S3
S3b
S4
S5
S6
Configuration
P01 - Application
setup
Application 1 enable
Enabled
Disabled
Enabling the Application 1
Configuration
P02 - Application
setup
Application 2 enable
Enabled
Disabled
Enabling the Application 2
Configuration
P03 - Application
setup
Application 3 enable
Enabled
Disabled
Enabling the Application 3
Configuration
P04 - Application
setup
Application 4 enable
Enabled
Disabled
Enabling the Application 4
Configuration
P05 - Application
setup
Application 5 enable
Enabled
Disabled
Enabling the Application 5
Configuration
P10 - Application
setup
Application 1
Application 2
Application selection Application 3
Application 4
Application 5
Application selection
Enhanced
Overview Status
P20 &
Configuration
- Application
setup
Actual selected
application
Actual selected application
Night application
mode for
Application 1
None
Application1
Application 2
Application 3
Application 4
Application 5
Night application mode for Application 1
Night application
mode for
Application 2
None
Application1
Application 2
Application 3
Application 4
Application 5
Night application mode for Application 2
Night application
mode for
Application 3
None
Application1
Application 2
Application 3
Application 4
Application 5
Night application mode for Application 3
Night application
mode for
Application 4
None
Application1
Application 2
Application 3
Application 4
Application 5
Night application mode for Application 4
Configuration
P21 - Application
setup
Configuration
P22 - Application
setup
Configuration
P23 - Application
setup
Configuration
P24 - Application
setup
76
T4C
Parameter text
Selection of temperature, to show on the
display:
0 =TS3/TS4
1 =T Temperature logger
2 =Tact
3 =Talarm
4 =S3
5 =S3b
6 =S4
7 =S5
8 =S6
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
T4C
LL
T4C
DSL
T4C
DDL
0
2
-
1
1
2
W
W
W
W
W
W
W
x
0
8
-
2
W
W
W
W
W
0
1
-
1
1
1
W
W
W
W
W
W
W
0
1
-
1
1
1
W
W
W
W
W
W
W
0
1
-
0
1
1
W
W
W
W
W
W
W
0
1
-
0
1
1
W
W
W
W
W
W
W
0
1
-
0
1
1
W
W
W
W
W
W
W
0
4
-
x
x
x
W
(no
copy)
W
(no
copy)
W
(no
copy)
W
(no
copy)
0
4
-
R
R
R
R
R
R
R
R
R
R
R
0/
None
5
-
0
0
0
W
W
W
W
W
W
W
0/
None
5
-
0
0
0
W
W
W
W
W
W
W
0/
None
5
-
0
0
0
W
W
W
W
W
W
W
0/
None
5
-
0
0
0
W
W
W
W
W
W
W
0 = TS3/ 0 = TS3/
S4
S4
Display
T4C
Prod. Service
Level
77
5. Parameters
(continued)
Code T4C
Parameter
group
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
Night application
mode for
Application 5
None
Application1
Application 2
Application 3
Application 4
Application 5
Night application mode for Application 5
Configuration
P27 - Application
setup
Application for
closed DI
None
Application1
Application 2
Application 3
Application 4
Application 5
Application for closed DI
Configuration
P28 - Application
setup
None
Application1
Application for Active Application 2
control timer
Application 3
Application 4
Application 5
Application selection for Active control timer
P30 Service Mode
Restore to factory
settings
Restore controller settings to factory settings
Configuration
P31 - Application
setup
Store to factory
settings
Store actual controller settings as factory
settings
Configuration
P25 - Application
setup
The SLV controller can be put into stop mode
by mode by one of the following ways:
Configuration
P32 - User
interface
Selection of stopped
mode
None
Display
Remote
Digital Input
Action Timer
Enhanced
P34 Overview Status
Alarm
Read out of active alarms
U84
Relay 1 actual state
U85
Relay 2 actual state
U86
Relay 3 actual state
U87
Relay 4 actual state
U88
Relay 5 actual state
Read out of actual relay state
P39
(U84,
U85, Service Mode
U86,
U87,
U88)
Configuration
P50 - Safety
function
Check temperature
None
Tdefr
Tact
S3b
0: No stopped functionality
1: Via a button on the display
2: Remotely via the Modbus
3: Digital input DI1
4: During active Control timer
When the “Check Temperature” function is
chosen to be active after a defrosting, one of
the following temperatures must be below
the “Maximum check value (P53)” before
the timer P51 has elapsed. Otherwise the
compressor will stop. This function should
only be chosen if the cabinet is performing
hot gas defrosting!
0 = No safety function enabled
1 = Monitoring of the Tdefr temperature
2 = Monitoring of the Tact temperature
3 = Monitoring of the S3b temperature
78
Configuration
P51 - Safety
function
Time after
compressor start to
check
Min value = 0 and
Delay, before the temperature check is made.
Max value = 240 minutes
Configuration
P52 - Safety
function
Interval between
checking’s
Min value = 0 and
Interval between checkings
Max value = 240 minutes
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
0/
None
5
-
0
0
0
W
W
W
W
W
W
W
0/
None
5
-
0
0
0
W
W
W
W
W
W
W
0/
None
5
-
0
0
0
W
W
W
W
0
1/Do
-
W
W
W
W
W
W
0
1/Do
-
W
W
(no
copy)
W
(no
copy)
W
(no
copy)
x
0
5
-
1
1
0
W
W
W
W
W
W
x
0
255
-
R
R
R
R
0
65535
-
R
R
R
R
x
0
3
-
1
1
0
W
W
W
W
x
0/
Always
240
min
15
15
5
W
W
W
W
x
0
240
min
1
1
1
W
W
W
W
79
5. Parameters
(continued)
80
Code T4C
Parameter
group
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
Configuration
P53 - Safety
function
Maximum check
value (P50)
Min value = -50 and
Max value = 50
Maximum allowed temperature for the check
function
P82 P83 Service Mode
Service mode
Normal mode,
Service mode
Customer lab mode
Secop test mode
Supply Chain test mode
Selection of controller mode:
0: Normal mode,
1: Service mode
2: Customer lab mode
3: Secop test mode
4: Supply Chain test mode
P84 Service Mode
Relay 1
Manual Control
on
off
Relay 1 manual ON during service mode
P85 Service Mode
Relay 2
Manual control
on
off
Relay 2 manual ON during service mode
P86 Service Mode
Relay 3
Manual control
on
off
Relay 3 manual ON during service mode
P87 Service Mode
Relay 4
Manual control
on
off
Relay 4 manual ON during service mode
P88 Service Mode
Relay 5
Manual control
on
off
Relay 5 manual ON during service mode
Temperature setpoint
min value = -50 and
Max value = 50
Upper limitation of the temperature setpoint
range. The reference is calculated as Tset
+ delta night. To prevent the end user from
creating settings beyond the intended working
range of the cabinet.
r01
Enhanced
Overview Status
&
Tset
Configuration
Temperatures
setpoint
r02
Configuration
Tset max
Temperatures
setpoint
r03
Configuration
Tset min
Temperatures
setpoint
min value = -50 and
Max value = 50
Lower limitation of temperature setpoint
range. The reference is calculated as Tset
+ delta night. To prevent the end user from
creating settings beyond the intended working
range of the cabinet.
r04
Configuration
- User
interface
S3/S4 temperature
offset
min value = -10 and
Max value = 10 K
Offset adjustment for the display read out
r05
Configuration
- User
interface
Temperature unit
(°C/°F)
°C
°F
Selection of the temperature units for the
display
0: °C
1: °F
r06
Configuration
- User
interface
Minimum limitation
of Display read out
Min value = -50 and
Max value = 20
Limitation of the lowest temperature readout
of the display.
r09
Calibration Temperature
sensors
S4 offset
Offset calibration of the S4 sensor
r10
Calibration Temperature
sensors
S3 offset
Offset calibration of the S3 sensor
r13
Configuration
Night setback
Temperatures
setpoint
Min value = -10 and
Max value = 10 K
Displacement of the Tset during night
condition.
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
-50
50
°C
12
12
12
W
W
W
W
0
65535
0
W
W
W
0
4
-
0
0
0
W
W
W
W
W
W
0
1
Off /
On
0
W
W
W
W
W
W
0
1
Off /
On
0
W
W
W
W
W
W
0
1
Off /
On
0
W
W
W
W
W
W
0
1
Off /
On
0
W
W
W
W
W
W
0
1
Off /
On
0
W
W
W
W
W
W
x
-49
50
°C
-20
5
0
W
W
W
W
x
-49
50
°C
-15
10
50
W
W
W
W
x
-50
49
°C
-27
0
-50
W
W
W
W
x
-10.0
+10.0
°K
-3
-3
0
W
W
W
W
x
°C
°F
°C/°F
0=C
0=C
0=C
W
W
W
W
x
-50
20
°C
-50
0
-50
W
W
W
W
x
-10.0
10.0
°K
0
0
0
W
W
W
x
-10.0
10.0
°K
0
0
0
W
W
W
x
-10
10
°K
0
0
0
W
W
W
W
81
5. Parameters
(continued)
82
Code T4C
Parameter
group
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
r15
Configuration
S3/S4 weighting
for Tact at day
Temperatures
(100%=S4, 0%=S3)
setpoint
Min value = 0 and
Max value = 100 %
For the thermostat temperature
measurement during the day, a mix of the
S3 & S4 measurement can be used. With a
setting of 100%, only the S4 sensor will be
used. With a setting of 0% only the S3 sensor
will be used. For settings in between, a mix
will be used.
r16
Configuration
- Melting
function
Time between melt
periods
Min value = 0 and
Max value = 60 hours
If the compressor has been running
continously longer than the time limit, a
compressor cut out will be initiated.
r17
Configuration
- Melting
function
Duration of melt
period
Min value = 0 and
Max value = 65535
minutes
During this cycle the display will show “deF”
until the cool down period has elapsed.
If the timers for “Drain post heating” and
“Delay for fan” have not elapsed at this time,
they will be forced off.
r18
Configuration
- Melting
function
Duration of cool
down period
Min value = 0 and
Max value = 65535
minutes
During this cycle the display will show “deF”
until the cool down period has elapsed.
If the timers for “Drain post heating” and
“Delay for fan” have not elapsed at this time,
they will be forced off.
r19
Configuration
- Melting
function
Lower temperature
limit to start melt
Min value = -15 and
Max value = 15
There will be no melting initiated, if the
temperature setting for the thermostat is
below this limit.
r20
Configuration
- Melting
function
Higher temperature
limit to start melt
Min value = -15 and
Max value = 15
There will be no melting initated, if the
temperature setting for the thermostat is
above this limit.
r25
Configuration
Tref max
Temperatures
setpoint
min value = -50 and
Max value = 50
Upper limitation of temperature reference
range. The reference is calculated as Tset +
night setback.
r26
Configuration
Tref min
Temperatures
setpoint
min value = -50 and
Max value = 50
Lower limitation of temperature reference
range.The reference is calculated as Tset +
night setback.
r55
Calibration Temperature
sensors
S3b offset
Offset calibration of the S3b sensor
r56
Calibration Temperature
sensors
S6 offset
Offset calibration of the S6 sensor
r57
Calibration Temperature
sensors
S5 offset
Offset calibration of the S5 sensor
r61
Configuration
S3/S4 weighting for Min value = 0 and
Tact at night
Max value = 100
Temperatures
(100% = S4, 0% = S3) %
setpoint
For the thermostat temperature
measurement during the night, a mix of the
S3 & S4 measurement can be used. With a
setting of 100%, only the S4 sensor will be
used. With a setting of 0% only the S3 sensor
will be used. For settings in between, a mix
will be used.
t07
Configuration
- Real time
clock
hour
Min value = 0 and
Max value = 59
Hour setting for the internal clock
t08
Configuration
- Real time
clock
Minutes
Min value = 0 and Max
value = 59
Minute setting for the internal clock
t09
Seconds
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
S4%
(100%
= S4,
0% =
S3)
x
0
100
%
100
100
100
W
W
W
W
x
0/Off
10
hrs
0
0
1
W
W
W
W
x
1
10
min
0
0
5
W
W
W
W
x
0
10
min
0
0
0
W
W
W
W
x
-15
15
°C
-5
-5
-5
W
W
W
x
-15
15
°C
10
10
10
W
W
W
x
-49
50
°C
-15
10
50
W
W
W
W
x
-50
49
°C
-27
0
-50
W
W
W
W
x
-10.0
10.0
°K
0
0
0
W
W
W
x
-10.0
10.0
°K
0
0
0
W
W
W
x
-10.0
10.0
°K
0
0
0
W
W
W
S4%
(100%
= S4,
0% =
S3)
x
0
100
%
100
100
100
W
W
W
W
0
23
hrs
W
W
W
W(no
copy)
W(no
copy)
W(no
copy)
W(no
copy)
0
59
min
W
W
W
W(no
copy)
W(no
copy)
W(no
copy)
W(no
copy)
0
59
min
W(no
copy)
W(no
copy)
W(no
copy)
W(no
copy)
83
5. Parameters
(continued)
Code T4C
Parameter
group
T4C
Drop down text
T4C
Description of the parameter
t45
Configuration
- Real time
clock
Day
Min value = 1 and Max
value = 31
Day setting for the internal clock
t46
Configuration
- Real time
clock
Month
Min value = 1 and Max
value = 12
Month setting for the internal clock
t47
Configuration
- Real time
clock
Year
Min value = 2000 and
Max value = 2099
Year setting for the internal clock
t80
Configuration Control timer Start
- Control timer hour
Min value = 0 an Max
value = 23
hours
Starting time for the control timer. Ieg. Day/
night change over, application selection etc.
t81
Configuration Control timer Start
- Control timer minute
Min value = 0 and Max
value = 59
minutes
Starting time for the control timer. Ieg. Day/
night change over, application selection etc.
t82
Configuration Control timer Stop
- Control timer hour
Min value = 0 and Max
value = 23
hours
Stop time for the control timer
t83
Configuration Control timer Stop
- Control timer minute
Min value = 0 and Max
value = 59
minutes
Stop time for the control timer
Configuration Control timer
- Control timer Function.
Function:
None
Status display
Main switch
Night operation
Light
Application changeover
Relay out
Selection of action for the control timer
The function” Status display” is currently not
supported.
t84
U09 Service Mode
S5 Temperature
Readout of the raw S5 measurement
U12 Service Mode
S3 Temperature
Readout of the raw S3 measurement
U16 Service Mode
S4 Temperature
Readout of the raw S4 measurement
Enhanced
U17 Overview Status
Temperature Actual
Readout of the actual temperature, used as
input to the temperature controller
Enhanced
U28 Overview Status
Tref
Readout of actual temperature reference,
calculated as Tset + Night setback.
U36 Service Mode
S6 Temperature
Readout of the raw S6 measurement
Enhanced
U37 Overview Enhanced
Overview
Enhanced
U56 Overview Enhanced
Overview
84
T4C
Parameter text
Defrost Temperature Read out of defrost temperature
Temperature Display Read out of the temperature shown in the
display
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
T4C
LL
T4C
DSL
T4C
DDL
1
31
day
W
W
W
W(no
copy)
W(no
copy)
W(no
copy)
W(no
copy)
1
12
month
W
W
W
W(no
copy)
W(no
copy)
W(no
copy)
W(no
copy)
9
99
Years
W
W
W
W(no
copy)
W(no
copy)
W(no
copy)
W(no
copy)
0
23
hrs
0
W
W
W
W
W
W
0
59
min
0
W
W
W
W
W
W
0
23
hrs
0
0
0
W
W
W
W
W
W
0
59
min
0
0
0
W
W
W
W
W
W
0
6
-
0
0
0
W
W
W
W
W
W
-55,00
(open
circuit:
-300,00)
+85.00
(short
circuit:
300.00)
°C
R
R
R
R
R
R
-55,00
(open
circuit:
-300,00)
+85.00
(short
circuit:
300.00)
°C
R
R
R
R
R
R
-55,00
(open
circuit:
-300,00)
+85.00
(short
circuit:
300.00)
°C
R
R
R
R
R
R
x
-55,00
(open
circuit:
-300,00)
+85.00
(short
circuit:
300.00)
°C
R
R
R
R
x
-59
60
°C
Ø
Ø
Ø
R
R
R
R
-55,00
(open
circuit:
-300,00)
+85.00
(short
circuit:
300.00)
°C
R
R
R
R
R
R
-55,00
(open
circuit:
-300,00)
+85.00
(short
circuit:
300.00)
°C
R
R
R
R
x
-50,0
(depends
on r06)
(open
circuit:
-300.00)
+85.00
(short
°C / °F
circuit:
300.00)
R
R
R
R
Display
T4C
Prod. Service
Level
85
5. Parameters
(continued)
Code T4C
Parameter
group
Enhanced
Overview Enhanced
U57 Overview
&
Temperature
alarms
T4C
Parameter text
T4C
Drop down text
T4C
Description of the parameter
Alarm Temperature
Read out of the temperature used for the
alarm monitoring
Enhanced
U70 Overview Status
Cooling appliance
status
Readout of the cooling appliance status
0: Power up delay
1: Service mode
2: Stopped
3: Case deicing
4: Case cleaning
5: Loading
6: Defrosting
7: Melting
8: Cooling after melt
9:Normal control
10:Door open
11: Emergency cooling
12:Safety alarm stop
13:Busadr. in display
14:Restoring factory settings
15:Storing factory settings
16:Normal operating mode
U76 Service Mode
S3b Temperature
Readout of the raw S3b measurement
Enhanced
U98 Overview Enhanced
Overview
Temperature TS3/S4 Enhanced
Overview Enhanced
U99 Overview &
T Log
Configuration
- Temperature
logger
86
Read out of the weighted temperature S3/S4
Read out of the temperature used in the
temperature logger
T4C
Help
Text
Multi
Apps
Min
Max
Unit
Default
App. 1
Default
App. 2
Default
App.
3…5
Display
End
user
Level
Display
Inst.
Level
Display
Serv.
Level
Display
T4C
Prod. Service
Level
T4C
LL
T4C
DSL
T4C
DDL
x
-55,00
(open
circuit:
-300,00)
+85.00
(short
circuit:
300.00)
°C
R
R
R
R
x
0
16
-
R
R
R
R
-55,00 -85,00
(open (short
circuit: circuit:
-300.00) -300.00)
°C
R
R
R
R
R
R
-55,00 -85,00
(open (short
circuit: circuit:
-300.00) -300.00)
°C
R
R
R
R
x
-55,00 -85,00
(open (short
circuit: circuit:
-300.00) -300.00)
°C
R
R
R
R
87
6.
Modbus
The Modbus used in the SLV is based on a RS-485 physical layer. Timing is controlled by an UART. The
transmission of data happens on a differential pair of wires. D1 is the non inverted representative of the
UART signal; D0 is the inverted signal of the UART.
Be aware: the RS-485 is not comparable with a RS-232. Both lines on a RS-485 are carrying the same
data, however on a RS-232 one line is for transmission and one is for receiving. The logic is based on the
voltage level, D0 > D1 = ‘1‘and D0 < D1 =‘0‘. Both lines are referring against each other, whereas RS-232
signals are always referring to GND.
The communication is controlled by a bus-master. The required supported bus speeds are 9.6 kbit and the
standard bit rate19.2 kbit; other standard bit rates are not supported.
Short description of all bus parts:
Knots
Knots are all devices on a bus which can receive and/or transmit data.
Bus-Master (Head-Unit, Gateway)
The bus-master is an active knot which starts the communication process requesting data from other
passive knots. There is always only one bus master allowed.
Secondarys
Secondarys like the SLVs are passive knots which should only transmit data when a master requests them.
A PNU list containing the data addresses is necessary to setup the bus-master.
Data-Line
The data-line in a RS-485 based Modbus is a differential pair. A differential pair is built by 2 wires; D1
and D0. The logic is based on the voltage level, D0 > D1 = ‘1‘and D0 < D1 =‘0‘. The differential pair should
always be together in a twisted pair.
For a minimum setup a bus-master, a secondary and the data-line between them is necessary. All the
following items are recommended; they will increase the performance and reliability significantly.
Common-Line
The common-line is required to bring all transceivers to one potential level.
BIAS-Resistors (RBIAS) (also called balancing or polarization)
The voltage level on the bus line is not defined when there is no transceiver active, so it is necessary to
pull D1 and D0 to the bus-idle-state (D1=‘1‘, D0=‘0‘).
Termination-Resistor (RT)
Must be installed at each end of the bus. They have to suppress reflections of the data signal at the end of
the data-line.
Shield
The cable which is used should be shielded to protect the data-line against outside disturbances.
Equivalent Circuit diagram of the Modbus
88
6.
Modbus
(continued)
Recommended electrical equipment:
The SLV is designed to use standard network equipment with RJ-45 CAT5 cables and RJ-45 Y-distributors
with 1:1 pin connection. Make sure that the adapter is a shielded type; otherwise the shield will end behind
the first Y-connector. With these parts it is very simple to build up the connections between the SLV and
the bus master. Screw terminals and D-shell 9 are also accepted by the standard and could be used, the
SLV is designed to support RJ-45.
Be aware: Connection of a crossed cable in a 2-wire Modbus system may cause damage.
Installation:
Cable length
With the recommended usage of RJ-45 and CAT-5 cables, a maximum cable length of 600m may be
reached without additional equipment. A cable length of 1000m is possible when choosing other cables,
but this solution is normally much more expensive in material and installation. The possible cable length
depends on the installation quality and the type of termination.
Knot count
The knot count depends on the properties of each connected knot and from the quality of the installation.
At least 32 knots are always guaranteed (without repeater) by the specification, but this requires a proper
installation.
The properties of the knots are defined by their driver capabilities. There are “full”, “1/2”, “1/4” and “1/8”
available on the market. Full transceivers make 32 knots possible. With “1/2” transceivers up to 64 knots
are possible and so on. The weakest transceiver holds the maximum possible knot count. When there
is only one “full” transceiver in a bunch of “1/4” transceivers the bus is limited to max 32 units. With
“1/8” transceivers it is possible to build a network with up to 256 knots, but this requires good network
equipment and a very proper installation. With more than 32 knots a repeater could be necessary. When
more than 31 SLVs are used, a repeater is recommended.
Data-Rate
The SLV is supporting a data rate of 9.6 kbit and 19.2 kbit, 19.2 kbit being the default. Further data-rates
are not supported.
Wiring
The wiring is a one to one connection of the used lines, so all D1-lines are connected to one wire, similarly
D0- lines and all commons (see also “Pin-Assignments”). D1 and D0 must be together in a twisted pair.
This is guaranteed with the recommended equipment. The recommended topology is the “bus”- structure
with passive taps and a derivation cable to the SLV. The standard allows a maximum length for passive
taps of 20m and with multi-port taps of 40m, but the derivation cables should be as short as possible to
reduce problems and increase performance.
This solution is the simplest way to install a cheap network with low risk of error. The recommended
equipment is the standard parts for computer networks.
Polarization
The communication with the SLVs requires line polarization, the SLV as a passive device isn‘t prepared to
do this. Both bus lines must be pulled to a stable state which represent its logical idle state D1 = ‘1‘(type
5V) and D0= ‘0‘(COM/PE). The specification requires a value of 450Ω to 650Ω for each. These balancing
resistors must only be installed once on the bus. Often the master will have these resistors built in;
otherwise it should be close to the master.
Termination
The specification requires a resistor of 150Ω (0.5W) at either end or a 120Ω (0.25W) resistor with a 1nF
(25V) capacitor in series between D1 and D0. The bus termination is a very important point when the
knot count is high and/or the cable is very long. The termination must be placed on both ends of the
communication line.
It is possible that other Modbus equipment has built in termination, these terminators must be disabled
(these additional terminators will increase the busload and limit the possible length of the bus and knot
count). Only the terminators at the ends of the Modbus are allowed. The general rule is to reduce the
resistance or to decrease the current. A reduction of the current by using a RC-terminator instead of
a simple resistor is one of the safest ways. Be aware, it‘s possible that the terminations inside the bus
master only have a resistor. In these cases it is recommended to disable the internal termination and add
a RC-terminator external. This solution has the benefit of the lowest power consumption in bus idle state.
A bus configuration with a normal resistor termination should only be used if there are only a few knots
and a relative short bus.
89
6.
Modbus
(continued)
Common-Line
The common-line is required to bring together all transceivers which are connected to the bus. This line
should have only one direct connection to PE, which should be close to the bus master. In some cases the
master has a common port which has a direct PE connection. If this internal PE connection is optional
a direct connection to a PE-rail would be the better choice. Further PE connections (like contact to the
chase of the fridge) will establish loops which could have influence on the communication quality. Non
isolated bus-knots are in general not allowed.
Shield
The used cables must be shielded. The requirements are the same as for the common. The shield must
be connected to PE at only one point. Best-case would be the same point as the common (when common
is direct connected to PE), but the common and the shield should have no further connection to each
other. A connection to PE via a pigtail will decrease the performance; a metal cable clamp on a PE-rail is
the preferable solution. All cables and connectors should be shielded. The shield of the female connector
must be connected to the other female connectors in the Y-adaptors or in the D-shells.
Pin assignments
If an RJ-45 or a 9-pin D-shell connector is used for a standard Modbus device, the pin outs hereafter must
be respected for every implemented circuit.
2W-Modbus RJ45 and 9-pin D-shell Pinouts
Pin on
RJ45
Pin on
D9-shell
Level of
requirement
IDv
Circuit
ITr
Circuit
EIA/TIA485 name
3
3
optional
PMC
–
–
4
5
required
Df
D1
B/B’
Transceiver terminal 1, V1 Voltage
(V1 > V0 for binary 1 (OFF) state)
5
9
required
D0
D0
A/A’
Transceiver terminal 0, V0 Voltage
(V0 > V1 for binary 0 (ON) state)
7
2
recommended
VP
–
–
Positive 5…24 V D.C. Power Supply
8
1
required
C/C’
Signal and Power Supply Common
Common Common
Description for IDv
Port Mode Control
Pin assignment for RJ-45 and D-Sub
RJ-45 Jack for single pair communication
Device side – female connector
D-Sub connector
The following systems can be connected to the Modbus:
⋅⋅ ADAP-KOOL® – Danfoss supermarket monitoring system
⋅⋅
Master functions:
- Night offset
- Blind
- Clock synchronization
- Alarm limit offset
- Dew point control
⋅⋅ TOOL4COOL® – Secop tool for adjusting and servicing of variable speed compressor products
The possibility of errors in the installation is very limited when using standard computer network
equipment for the Modbus. A safely running bus is ensured with BIAS-resistors (inside the bus-masters)
and the correct termination. Bigger networks require a proper installation of common lines and shielded
cables.
For more information please refer to "Technical Resources" on www.modbus.org
90
7.
Technical Data
7.1
SLV15CNK.2
Compressor R290
General
Code number (without electronic unit)
Electronic unit
Approvals
Compressors on pallet
Application
Application
Frequency
Evaporating temperature
Voltage range
Max. condensing temperature continuous
(short)
Max. winding temperature continuous (short)
Cooling requirements
Frequency
Application
32°C
38°C
43°C
Remarks on application:
104H8541
105N46xx series controller
EN 60335-2-34, CCC
80
LBP
Hz
°C
V
50
-40 to -10
180 - 254
60
-40 to -10
180 - 254
°C
55 (65)
55 (65)
°C
125 (135)
125 (135)
Hz
LBP
F2
F2
F2
50
MBP
–
–
–
HBP
–
–
–
LBP
F2
F2
F2
60
MBP
–
–
–
HBP
–
–
–
F2 = Fan cooling 3 m/s necessary
LST only, airflow on compressor and electronic unit: 3m/s
Features
Speed range
Thermostat
rpm
Protections
Motor
Motor type
LRA (rated after 4 sec. UL984),
Maximum current
Resistance, all 3 windings (25°C)
Design
Displacement
Oil quantity (type)
Maximum refrigerant charge
Free gas volume in compressor
Weight - Compressor/Electronic unit
A
A
Ω
cm3
cm3
g
cm3
kg
2000 - 4000
- intregrated
- electronic
- current
- speed
- temperature
permanent magnet
electronic cut off
4.6
7.7
15.28
600 (polyolester)
150
1510
12.0/1.4
91
7.1
SLV15CNK.2
Compressor R290
(continued)
EN 12900 Household (CECOMAF)*
220 V, 50 Hz, fan cooling F2
2,000 rpm
Evap. temp. in °C
-45
Capacity in W
-40
-35
-30
-25 -23.3 -20
-15
-10 -6.7
175
236
311
402
437
510
638
786
229
266
303
315
338
372
402
Power cons. in W
192
Current cons. in A
1.01 1.19 1.37 1.54 1.60 1.70 1.86 2.01
COP in W/W
0.91 1.03 1.17 1.33 1.39 1.51 1.72 1.96
-45
-40
-35
-30
-25 -23.3 -20
-15
-10 -6.7
Capacity in W
218
297
393
509
553
645
805
990
Power cons. in W
242
284
327
371
385
414
455
493
Current cons. in A
1.18 1.39 1.60 1.80 1.87 2.01 2.22 2.42
COP in W/W
0.90 1.05 1.20 1.37 1.43 1.56 1.77 2.01
-45
Capacity in W
-40
-35
-30
-25 -23.3 -20
-15
258
353
467
602
652
759
941 1151
-10 -6.7
331
388
441
458
489
533
Power cons. in W
271
Current cons. in A
1.34 1.57 1.80 2.03 2.11 2.26 2.50 2.73
COP in W/W
0.95 1.07 1.21 1.37 1.43 1.55 1.77 2.02
-45
Capacity in W
10
15
20
-5
0
5
7.2
10
15
20
-5
0
5
7.2
10
15
20
0
5
7.2
10
15
20
571
-40
-35
-30
-25 -23.3 -20
325
460
615
792
858
996 1228 1494
-15
436
512
583
607
650
Power cons. in W
355
1.68 2.02 2.36 2.68 2.78 2.99 3.28 3.56
COP in W/W
0.92 1.06 1.20 1.36 1.42 1.53 1.72 1.94
Accessories for SLV15CNK.2
Code number
103N2008
713
-10 -6.7
Current cons. in A
Cover
-5
771
Test conditions
Mounting accessories
Bolt joint for one
compressor
Bolt joint in quantities
Code number
Ø: 16 mm
118-1917
Ø: 16 mm
118-1918
Snap-on in quantities
Ø: 16 mm
118-1919
EN 12900/CECOMAF*
Condensing temperature
45°C
Ambient temperature
32°C
Suction gas temperature
92
7.2
EN 12900 Household (CECOMAF)*
220 V, 50 Hz, fan cooling F2
4,000 rpm
Evap. temp. in °C
5
EN 12900 Household (CECOMAF)*
220 V, 50 Hz, fan cooling F2
3,000 rpm
Evap. temp. in °C
0
EN 12900 Household (CECOMAF)*
220 V, 50 Hz, fan cooling F2
2,500 rpm
Evap. temp. in °C
-5
Liquid temperature
32°C
no subcooling
7.2
SLV12CLK.2
Compressor
R404A/R507
General
Code number (without electronic unit)
Electronic unit
Approvals
Compressors on pallet
Application
Application
Frequency
Evaporating temperature
Voltage range
Max. condensing temperature continuous
(short)
Max. winding temperature continuous (short)
Cooling requirements
Frequency
Application
32°C
38°C
43°C
Remarks on application:
104L2603
105N46xx series controller
EN 60335-2-34, CCC
80
LBP
Hz
°C
V
50
-40 to -10
180 - 254
60
-40 to -10
180 - 254
°C
50 (60)
50 (60)
°C
125 (135)
125 (135)
Hz
LBP
F2
F2
F2
50
MBP
–
–
–
HBP
–
–
–
LBP
F2
F2
F2
60
MBP
–
–
–
HBP
–
–
–
F2 = Fan cooling 3 m/s necessary
LST only, airflow on compressor and electronic unit: 3m/s
Features
Speed range
Thermostat
rpm
Protections
Motor
Motor type
LRA (rated after 4 sec. UL984),
Maximum current
Resistance, all 3 windings (25°C)
Design
Displacement
Oil quantity (type)
Maximum refrigerant charge
Free gas volume in compressor
Weight - Compressor/Electronic unit
A
A
Ω
cm3
cm3
g
cm3
kg
2000 - 4000
- intregrated
- electronic
- current
- speed
- temperature
permanent magnet
electronic cut off
4.6
7.7
12.87
600 (polyolester)
1300
1510
12.0/1.4
93
7.2
SLV12CLK.2
Compressor
R404A/R507
(continued)
EN 12900 Household (CECOMAF)*
220 V, 50 Hz, fan cooling F2
2,000 rpm
Evap. temp. in °C
-45
Capacity in W
-40
-35
-30
-25
-23.3
-20
-15
-10
134
196
269
355
387
455
572
705
Power cons. in W
182
227
268
308
321
345
379
410
Current cons. in A
0.97
1.16
1.36
1.55
1.62
1.74
1.94
2.13
COP in W/W
0.74
0.86
1.00
1.15
1.21
1.32
1.51
1.72
-45
-40
-35
-30
-25
-23.3
-20
-15
Capacity in W
160
243
342
459
502
592
742
910
212
270
325
377
394
426
472
515
Current cons. in A
1.06
1.32
1.58
1.82
1.91
2.07
2.30
2.53
COP in W/W
0.75
0.90
1.05
1.22
1.27
1.39
1.57
1.77
-45
Capacity in W
-40
-35
-30
-25
-23.3
-20
-15
-10
181
283
406
550
604
714
895
1093
Power cons. in W
237
308
375
439
460
499
557
612
Current cons. in A
1.13
1.45
1.76
2.06
2.16
2.35
2.62
2.88
COP in W/W
0.76
0.92
1.08
1.25
1.31
1.43
1.61
1.79
-6.7
-5
0
-6.7
-5
0
-6.7
-5
0
EN 12900 Household (CECOMAF)*
220 V, 50 Hz, fan cooling F2
4,000 rpm
Evap. temp. in °C
0
EN 12900 Household (CECOMAF)*
220 V, 50 Hz, fan cooling F2
3,000 rpm
-45
Capacity in W
-40
-35
-30
-25
-23.3
-20
-15
-10
200
370
542
720
782
909
1114
1339
Power cons. in W
270
404
508
588
611
649
695
731
Current cons. in A
0.91
1.68
2.30
2.77
2.90
3.10
3.28
3.31
COP in W/W
0.74
0.92
1.07
1.22
1.28
1.40
1.60
1.83
Accessories for SLV12CLK.2
Cover
Code number
103N2008
Test conditions
Mounting accessories
Bolt joint for one
compressor
Bolt joint in quantities
Code number
Ø: 16 mm
118-1917
Ø: 16 mm
118-1918
Snap-on in quantities
Ø: 16 mm
118-1919
EN 12900/CECOMAF*
Condensing temperature
45°C
Ambient temperature
32°C
Suction gas temperature
94
-10
Power cons. in W
Evap. temp. in °C
-5
EN 12900 Household (CECOMAF)*
220 V, 50 Hz, fan cooling F2
2,500 rpm
Evap. temp. in °C
-6.7
Liquid temperature
32°C
no subcooling
7.3
SLV 105N46xx Series
Controller
Input Power
Name
Pin
Earth
1
Phase
2
Neutral
3
Name
Type
Specification
protective earth
voltage
current
6.3 A (10 A Fuse)
Relays
Name
Pin
Name
4
Neutral
5
Normal open
RL 1
RL 2
RL 5
Neutral
Normal open
8
Neutral
9
Normal open
10
Normal open
12
Normal closed
RL 3
RL 4
6
7
12
Neutral
13
Normal closed
14
Normal open
15
Common
Pin
Name
4
D1
5
D0
8
GND (insulated)
Pin
Name
19
GND
21
S3
22
GND
Type
Neutral pass through, live
switched, normally open
Neutral pass through, live
switched, normally open
Neutral pass through, live
switched, normally open
Neutral pass through, live
switched, normally open and
normally closed
Specification
Voltage
230 V AC
current 2 A rms
cos phi 0.65
number of switchings
100000
(EN60730-1)
special feature for R3: zero crossing switch
special feature for R5: zero crossing switch
gold plated for small signal switching
min contact load 1 mA
max contact load
20 mA
Attention: if used for more than 20 mA once, it
cannot be used for low voltage again
Galvanic isolated, base pin and
max. total current for RL1 to RL 4
normally/closed connection
max. current for RL5
2 A rms
2 A rms
Modbus
Name
MODBUS
Type
MODBUS-RTU, RS-485
Specification
COM-Port Settings:
19.2 kbit
8 bit data length
Even parity, single stop bit
Sensor inputs
Name
S3
S4
S5
S3b
S6
24
S4
25
GND
27
S5
28
GND
30
S3b
28
GND
29
S6
Type
Specification
-55 to 85° C
Analogue input for connection Measurement range
Max. cable length
3m
to NTC 5K sensor
Suitable for EPCOS M2020
Analogue input for connection Not insulated
to NTC 5K sensor
Analogue input for connection
to NTC 5K sensor
Analogue input for connection
to NTC 5K sensor
Analogue input for connection HACCP
to PT 1000 sensor
Suitable for PT 1000, double insulated
Miscellaneous
Name
Pin
Not used
20
Name
Type
Specification
No connection
Not used
23
No connection
Not used
26
No connection
95
7.3
SLV 105N46xx Series
Controller
(continued)
Motor connection
Name
Pin
Name
COMP
(cable)
MC
Name
Pin
Name
31
GND
32
Supply for
external device
33
DI
Pin
Name
34
GND
35
Supply
36
Data signal
Type
Specification
Voltage
switched 350 V DC
3 phase trapezoidal and
Current limit
4.5 A
sensor less BLDC motor drive Frequency norm
10 KHz / < 15 KHz
DI
DI
Display
Name
Display
Type
Specification
Low voltage digital I/O
Analogue input
+ supply voltage (32/33)
Voltage
Max. current
Short circuit protected
Max. current sourcing
Type
12 V DC
50 mA
20 mA
Specification
Display connection
Low voltage digital I/O
Analogue input
+ supply voltage (35/36)
Voltage Max. current
Short circuit protected
Max. current sourcing
12 V DC
50 mA
20 mA
General Specifications
Name
Operating conditions
-10 °C to 50 °C
humidity < 90 % RH non condensing
Storage conditions
-20 °C to 70 °C
humidity < 90 % rH non condensing
Supply voltage
230 V (+15 % / - 20 %)
Frequency
50/60 Hz
Input power rating
96
Specification
WEEE
RoHS
IMDS
CE
LVD - Low Voltage Directive 2006/95/EC
EMC - Electromagnetic Compatibility Directive 2004/108/EC
1000 W at 230 V (+15 % / - 20 %)
Idle power
1W
Airflow
Min 3 ms
Secop
20.10
7.4
Dimensions
Dimensions
Height
Suction connector
Process connector
Discharge connector
Oil cooler connector
Connector tolerance
mm
location/I.D. mm | angle
material | seal
location/I.D. mm | angle
material | seal
location/I.D. mm | angle
material | seal
location/I.D. mm | angle
material | seal
I.D. mm
A
B
B1
B2
C
D
E
F
199
193
173
90
10.2 | 37°
Cu-plated steel | Al cap
6.2 | 37°
Cu-plated steel | Al cap
6.2 | 37°
Cu-plated steel | Al cap
–
–
±0.09
97
8.
Ordering
Software
Gateway
Display / Cables / Sensors / Connetors / Potentiometer Control
Controller
Item
98
Code no.
Description
SLV controller 105N46xx series
105N4600
For refrigeration device with Modbus only
Display CRA 172
105N9512
3 ½ LED based local display
3 push buttons
width: 74 mm, height: 34 mm, depth: 22 mm
Display cable, short
105N9509
length: 600 mm
3 wires isolated for display connection
Display cable, long
105N9511
length: 2000 mm
3 wires isolated for display connection
Temperature sensor S3
105N9626
length: 3000 mm
EPCOS M2020
Temperature sensor S4
105N9629
length: 2000 mm
EPCOS M2020
Temperature sensor S5
105N9633
length: 2000 mm
EPCOS M2020
Counter connector for Digital Input
105N9513
10 pcs. / bundle
Counter connector for Mains
105N9563
10 pcs. / bundle
Counter connector for RL1
105N9565
10 pcs. / bundle
Counter connector for RL2
105N9567
10 pcs. / bundle
Counter connector for RL3
105N9569
10 pcs. / bundle
Counter connector for RL4
105N9571
10 pcs. / bundle
Counter connector for RL5
105N9573
10 pcs. / bundle
Counter connector for
DI, Mains, RL1-RL5
105N9575
7 pcs. / bundle (1 piece of each type)
Potentiometer control
on request
small assembly with potentiometer for setpoint control,
1 Operating/Fault LED
Secop Bluetooth gateway
105N9502
with USB power supply and DSUB-9 / RJ45 adaptor
RJ45 Ethernet patch cable
Tool4Cool LabEdition
not available connection between SLV controller and Bluetooth
from Secop gateway with DSUB-9 / RJ45 adaptor
free of
charge
www.secop.com/tool4cool.html
99
www.secop.com
SLV with intelligent 220 V 50/60 Hz controller
SLV compressors are the natural choice when you need a versatile package for a wide range of applications.
The built-in data logging function which monitors system performance and the intelligent controller for ultimate control and alarm management, are just a few of the enhancements that place SLV compressors above
other optimised compressors.
OUR JOURNEY
SO FAR
1956
Founded and start up
production of Pancake
compressor.
1970
Introduction of SC
compressors. The
birth of a standard
setting platform in
the light commercial
market.
1990
1999
2008
Introduction NL
compressors.
Start of production with
natural refrigerant R290 (Propane)
Production facility in
Wuqing, China founded.
1960
1972
1993
2002
2010
Introduction TL
compressors.
Introduction FR
compressors.
Start of production with
natural refrigerant R600a (Isobutane)
Production facility
Zlate Moravce,
Slovakia
founded.
Introduction SLV-CNK.2
and SLV-CLK.2 variable
speed compressors.
Production facility in Crnomelj, Slovenia
founded.
Secop GmbH · Mads-Clausen-Str. 7 · 24939 Flensburg · Germany · Tel: +49 461 4941 0 · Fax: +49 461 4941 44715 · www.secop.com
Secop can accept no responsibility for possible errors in catalogues, brochures and other printed material. Secop reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the
respective companies. Secop and the Secop logotype are trademarks of Secop GmbH. All rights reserved
Produced by Secop | February 2013
DES.S.300.A2.02

Понравилась статья? Поделить с друзьями:
  • Seconds salon super mild hair mask инструкция по применению
  • Seccom technologies model 081 инструкция
  • Sebum strike serum инструкция по применению
  • Sebium gel moussant инструкция по применению bioderma
  • Sebastian cellophanes инструкция по применению