RDG1…

Room thermostats with display, for fan coil units

RDG100, RDG100T, RDG110, RDG140, RDG160

Basic Documentation

Edition: 1.0

CE1P3181en

28 May 2009

Tel: 01823 665660

Heronhill — for all your Siemens requirements

RDG100T

www.heronhill.co.uk

Building Technologies

Fax: 01823 665807

loading

Related Manuals for Siemens RDG100

Summary of Contents for Siemens RDG100

  • Page 1
    Heronhill — for all your Siemens requirements RDG1… RDG100T Room thermostats with display, for fan coil units RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation Edition: 1.0 CE1P3181en Building Technologies 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…
  • Page 2: Table Of Contents

    4.15 Control parameters ……………..45 4.15.1 Service level ………………..46 4.15.2 Expert level, diagnostics and test …………47 2 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Contents 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…

  • Page 3
    Connection diagrams …………….54 Mechanical design …………….56 General ………………..56 Dimensions …………………56 Technical data ………………57 Index …………………… 1 1 7 H 3/60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Contents 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…
  • Page 4: About This Document

    Before you start 1.3.1 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.2 Quality assurance The document was prepared with great care.

  • Page 5: Document Use / Request To The Reader

    Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.

  • Page 6: Summary

    Heronhill — for all your Siemens requirements Summary Brief description • 2-pipe fan coil units, 2-pipe with electrical heater, Applications 2-pipe with radiator / floor heating • 4-pipe fan coil units, 4-pipe with electrical heater • 2-stage heating or cooling application •…

  • Page 7: Types And Features

    Infrared remote control must be ordered as a separate item ECM fan output DC 0…10 V ON/OFF, PWM or 3-position (triac outputs) Relay output (SPDT) 7 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Summary 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 8: Equipment Combinations

    Heronhill — for all your Siemens requirements Equipment combinations Data Description Product no. Sheet Infrared remote control IRA211 3059 Cable temperature sensor QAH11.1 1840 Room temperature sensor QAA32 1747 Condensation detector / extension QXA2000 / 1542 module AQX2000 2-position actuators…

  • Page 9: Accessories

    • 1-stage compressor for heating or cooling and radiator / floor heating • 1-stage compressor for heating and cooling with reversing valve • 2-stage compressor for heating or cooling 9 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 10: Functions

    • 2-position control on RDG100, RDG100T, RDG110 • PI / P control with 3-position control output on RDG100, RDG100T, • PI / P control with PWM output on RDG100, RDG100T • PI / P control with DC 0…10 V control output on RDG140, RDG160 The switching differential or proportional band is 2 K for heating mode and 1 K for cooling mode (adjustable via parameters P30 and P31).

  • Page 11: Operating Modes

    The behavior of the operating mode button can be selected via parameter P02: Without time With time program Remark program (RDG100T only) Factory setting 11 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…

  • Page 12: Room Temperature Setpoints

    Heronhill — for all your Siemens requirements Room temperature setpoints Comfort mode The setpoint in Comfort mode can be adjusted via the rotary knob. Setpoint limitation For energy saving purposes, the setpoint setting range can be limited to minimum (P09) and maximum (P10).

  • Page 13: Setpoints And Sequences

    = setpoint cooling in Energy Saving or Protection mode CoolEco/Prot YR = radiator sequence YE = electrical heater sequence 13 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 14: Pipe Applications

    Heronhill — for all your Siemens requirements 4.4.2 4-pipe applications On 4-pipe applications, the Comfort setpoint (w) is in the middle of the dead zone, between the heating and cooling sequence. The dead zone can be adjusted via parameter P33.

  • Page 15: Applications Overview

    (B1) • 2-stage compressor DC 0…10 V RDG140 (B1) DC 0 … 10 V RDG160 15 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…

  • Page 16: Additional Features

    Heronhill — for all your Siemens requirements Heat pump application covered by RDG110 (SPDT = relay with NO and NC contact) With ECM fan control DC 0…10 V Heating or heating/cooling valve actuator M1 1-speed or 3-speed fan Cooling valve actuator…

  • Page 17
    If parameter P48 or P49 is set to above 1 minute, the minimum on/off time for the control output is maintained as set, even if the setpoint or changeover mode is readjusted. This function is only available for on/off control with RDG100, RDG100T and RDG110. All heating sequences can also be used for floor heating.
  • Page 18
    Heronhill — for all your Siemens requirements The table below shows the relation between parameter, temperature source and temperature display: External temp. Source for display of room Output control according Floor temp. limit Parameter P51 sensor available temperature function Built-in sensor…
  • Page 19
    Comf Absence Prot Auto Prot Not available Extension Comf Auto Absence Auto Prot Not available 19 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…
  • Page 20: Control Sequences

    Heronhill — for all your Siemens requirements Control sequences 4.7.1 Sequences overview (setting via parameter P01) The sequence can be set via parameter P01. The thermostats can be used in systems featuring: • Heating only (P01=0) • Cooling only (P01=1) •…

  • Page 21: Control Outputs Overview (Setting Via Dip Switches 4 / 5 And Parameters P46 / P47)

    Available with type * (only possible for 1 actuator) With RDG100 and RDG100T, the function of the control outputs (2-position or 3- position) is set via DIP switches 4 and 5 . With RDG140 and RDG160, DIP switches 4 and 5 can be used to invert the DC 0…10 V signal to 10…0 V.

  • Page 22: Pipe Fan Coil Unit

    Heronhill — for all your Siemens requirements 4.7.3 2-pipe fan coil unit On 2-pipe applications, the thermostat controls a valve in heating / cooling mode with changeover (automatic or manual), heating only, or cooling only. Cooling only is factory set (P01=1).

  • Page 23: Pipe Fan Coil Unit With Electrical Heater

    SDC Switching differential “Cooling” (P31) ½ SDH ½ SDH Dead zone (P33) Setpoint differential (P34) 23 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…

  • Page 24
    Heronhill — for all your Siemens requirements Modulating control 3-position, PWM or DC 0…10 V Control sequence The diagram below shows the control sequence for modulating control. modulating output Heating mode Cooling mode (automatic changeover = heating or heating only) (man.
  • Page 25: Pipe Fan Coil Unit With Radiator Or Floor Heating

    SDC Switching differential “Cooling” (P31) Control command “Valve” or “Compressor” Dead zone (P33) Control command “Radiator” Setpoint differential (P34) 25 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 26
    Heronhill — for all your Siemens requirements Modulating control: 3-position, PWM or DC 0…10 V The diagram below shows the control sequence for modulating PI control. Heating mode Cooling mode (automatic changeover = heating or heating only) (man. / auto. changeover = cooling or cooling only)
  • Page 27: Pipe Fan Coil Unit

    • The thermostat assumes winter operation when B2 > P37 (factory setting 28 °C) • The thermostat assumes summer operation when B2 < P36 (factory setting 16 °C) 27 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions…

  • Page 28
    Heronhill — for all your Siemens requirements ON/OFF control The diagram below shows the control sequence for 2-position control. Heating mode with manual selection Cooling mode with manual selection (P01=2) (P01=2) T[°C] T[°C] ½ SDC ½ SDC ½ SDH ½ SDH Heating and cooling mode (P01=04) T[°C] Room temperature…
  • Page 29: Pipe Fan Coil Unit With Electrical Heater

    ½ SDH ½ SDH SDC Switching differential “Cooling” (P31) Dead zone (P33) Setpoint differential (P34) 29 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…

  • Page 30
    Heronhill — for all your Siemens requirements Modulating control: 3-position or PWM The diagram below shows the control sequence of modulating PI control. Heating mode with manual selection (P01=2) Cooling mode with manual selection P01=2) Y [%] Y [%] Y2 (YE) T[°C]…
  • Page 31: Stage Heating Or Cooling

    SDH Switching differential “Heating” (P30) SDC Switching differential “Cooling” (P31) Dead zone (P33) Setpoint differential (P34) TR [°C] 31 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 32
    Heronhill — for all your Siemens requirements Modulating control: 3-position, PWM or DC 0…10 V The diagram below shows the control sequence of modulating PI control. Heating mode (P01=0) Cooling mode P01=1) 100% 100% YHC1 YHC2 YHC2 YHC1 TR [°C] TR [°C]…
  • Page 33: Chilled / Heated Ceiling And Radiator Applications

    (automatic or manual). Cooling only is factory-set (P01=1). • Set basic application «4-pipe» (see section 4.7.6) • Connect compressor and reversing valve as follows: 33 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 34
    Heronhill — for all your Siemens requirements Hardware This application is available with RDG110 only. ON/OFF control The diagrams below show the control sequences for 2-position control. Heating mode with manual selection Cooling mode with manual selection (P01 = 2)
  • Page 35: Control Outputs

    Caution A safety thermostat (to prevent overtemperatures) must be provided externally. 3-position This function is available with RDG100 and RDG100T only. control signal Heating: Output Y1 provides the OPEN command, and Y2 the CLOSE command to the 3-position actuator. Cooling: Idem with Y3 and Y4.

  • Page 36
    3. After the actuator reaches the position calculated by the thermostat, a waiting time of 30 seconds is applied to stabilize the outputs. This function is available with RDG100 and RDG100T only. PWM control The demand calculated by PI control from the current room temperature and set- point is provided via Y1 and Y3 to the valve actuator as a PWM signal (pulse width modulation) for thermal actuators.
  • Page 37: Fan Control

    Switching range for fan “Heating” Switching range for fan “Cooling” T[°C] SDH/SDC >4.5 Look-up table with /XpC on/off control 37 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…

  • Page 38
    Heronhill — for all your Siemens requirements 1-speed / 3-speed fan The fan speed thermostat can control a 1-speed or 3-speed fan (selected via control parameter P53). A 1-speed fan is connected to terminal Q1, a 3-speed fan to terminals Q1, Q2 and Q3.
  • Page 39
    To let the heating / cooling coil reach its temperature, the fan start can be delayed (2-position control only) by a time period set via parameter P67. 39 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…
  • Page 40: Multifunctional Input, Digital Input

    Heronhill — for all your Siemens requirements 4.10 Multifunctional input, digital input The thermostat has 2 multifunctional inputs X1 and X2 and a digital input D1. A sensor type NTC like the QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals.

  • Page 41: Auto Timer (Rdg100T Only)

    However the auto timer will continue to run with the time before the power loss occurred. Enter the setting mode to adjust the time of day if needed. 41 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions…

  • Page 42
    Heronhill — for all your Siemens requirements Setting the timers The RDG100T provides 8 programmable timers A1 … A8. Each timer has a Comfort mode start and end time that can be applied to one or several weekdays. To set an auto timer, proceed as follows: Press the program mode button twice to select “Auto timer setting”…
  • Page 43: Handling Faults

    • Select fan mode “Automatic” or “Manual” A buzzer in the thermostat indicates remote control command reception. Infrared remote control can be disabled via parameter P70. 43 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 44: Dip Switches

    Heronhill — for all your Siemens requirements 4.14 DIP switches Use the DIP switches at the rear of the thermostat to commission the thermostat’s basic application prior to snapping it to the base. – The application is set via DIP switches 1…3 –…

  • Page 45: Control Parameters

    The factory setting for the control parameters can be reloaded via parameter P71, by changing the value to “ON”. Confirm by pressing the right button. The display shows “8888” during reloading. 45 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 46: Service Level

    Heronhill — for all your Siemens requirements 4.15.1 Service level Name Factory setting Range Service level Control sequence When 2-pipe / 0 = Heating only 2-stage: 1 = Cooling only 1 = Cooling only 2 = H/C changeover manual When 4-pipe:…

  • Page 47: Expert Level, Diagnostics And Test

    Parameter not available Note P46, P47: Setting to 2-position or 3-position is made with DIP switches 4 and 5. 47 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Functions 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 48
    Heronhill — for all your Siemens requirements Fan operation 0 = Disabled 1 = Enabled 2 = Heating only 3 = Cooling only Fan speed 3-speed 1 = 1-speed 2 = 3-speed Fan overrun time 60 sec 0 … 360 sec (only when electr.
  • Page 49: Handling

    • Size correctly the cables to the thermostat, fan and valve actuators for AC 230 V mains voltage • Use only valve actuators rated for AC 230 V on RDG100… / RDG110 • The power supply line must have an external fuse or circuit breaker with a rated current of no more than 10 A •…

  • Page 50: Operation

    Heronhill — for all your Siemens requirements Operation See also Operating Instructions B3181 enclosed with the thermostat. Layout RDG100 RDG100T RDG110 RDG140 RDG160 1 Operating mode button / Esc 2 Button to enter the time and to set the timers…

  • Page 51
    Confirmation of parameters Indicates that room temperature is displayed 51 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Handling 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…
  • Page 52: Disposal

    Heronhill — for all your Siemens requirements Disposal The device is classified as waste electronic equipment in terms of the European Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted muni- cipal waste. The relevant national legal rules must be adhered to.

  • Page 53: Engineering

    Y12, Y22 Control output “Valve” AC 230 V (NC, for normally open valves) Y10, Y20 Control output for DC 0…10 V actuator 53 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Engineering 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…

  • Page 54: Connection Diagrams

    Heronhill — for all your Siemens requirements Connection diagrams Note For details concerning connection of peripheral devices and setting of the DIP switches, please refer to the Mounting Instructions: – M3181.1 (RDG100, RDG100T) – M3181.2 (RDG110) – M3181.3 (RDG140, RDG160) RDG100……

  • Page 55
    1st or 2nd stage DC 0…10 V outputs Electrical heater DC 0…10 V controlled converter / current valve 55 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Engineering 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…
  • Page 56: Mechanical Design

    Heronhill — for all your Siemens requirements Mechanical design General The room thermostat consists of 2 sections: • Plastic housing which accommodates the electronics, the operating elements and the temperature sensor • Mounting plate with the screw terminals The housing engages in the mounting plate and is secured with 2 screws on the left side.

  • Page 57: Technical Data

    Ext. temperature sensor (P38=1) Input X2 Changeover sensor (P40=2) Operating mode switchover Input D1 (P42=3) 57 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Technical data 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807…

  • Page 58
    Heronhill — for all your Siemens requirements Built-in room temperature sensor Measuring range 0…49 °C Accuracy at 25 °C < ± 0.5 K Temperature calibration range ± 3.0 K Settings and display resolution Setpoints 0.5 °C Current temperature value displayed 0.5 °C…
  • Page 59
    Operating mode button ……….11 ECM fan…………. 7, 38 Operating mode input……….11 Electrical heater…………. 23 Operating mode switchover ……..40 59 / 60 Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en Building Technologies Index 28 May 2009 Tel: 01823 665660 www.heronhill.co.uk…
  • Page 60
    Heronhill — for all your Siemens requirements Operating voltage ………… 7 Setpoint Comfort mode ……… 13 Overlapping of timer sequences……43 Setpoint Energy Saving mode……. 13 Setpoint limitation ……….12 Setpoint Protection mode ……..13 Parameter setting ……….45 Setpoints and sequences ……..13 Power failure…………

инструкцияSiemens RDG100

s

RDG100, RDG110, RDG110U RDG100T, RDG160T, RDG160TU

Room thermostats with LCD for wall mounting

RDG100

RDG100T

RDG110, RDG110U

RDG160T, RDG160TU

Basic documentation

Edition 6.0

CE1P3181en

2019-07-05

Smart Infrastructure

Посмотреть инструкция для Siemens RDG100 бесплатно. Руководство относится к категории термостаты, 10 человек(а) дали ему среднюю оценку 8.6. Руководство доступно на следующих языках: английский. У вас есть вопрос о Siemens RDG100 или вам нужна помощь? Задайте свой вопрос здесь

  • 1 About this document
  • 2 Summary
  • 3 Use
  • 4 Functions
  • 5 Handling
  • 6 Engineering
  • 7 Mechanical design
  • 8 Technical data

Нужна помощь?

У вас есть вопрос о Siemens а ответа нет в руководстве? Задайте свой вопрос здесь Дай исчерпывающее описание проблемы и четко задайте свой вопрос. Чем детальнее описание проблемы или вопроса, тем легче будет другим пользователям Siemens предоставить вам исчерпывающий ответ.

Количество вопросов: 0

Логотип Siemens
Главная
Siemens
RDG100
термостат
английский
Руководство пользователя (PDF)

Не можете найти ответ на свой вопрос в руководстве? Вы можете найти ответ на свой вопрос ниже, в разделе часто задаваемых вопросов о Siemens RDG100.

Где лучше всего разместить термостат?

Что такое зона нечувствительности термостата?

Какая идеальная комнатная температура?

Инструкция Siemens RDG100 доступно в русский?

Не нашли свой вопрос? Задайте свой вопрос здесь

Нет результатов

Siemens iQ500 RDH100
Siemens iQ500 RDH100

инструкция2 страниц(ы)

Siemens RDS110
Siemens RDS110

инструкция76 страниц(ы)

Siemens RAA11
Siemens RAA11

инструкция4 страниц(ы)

Danfoss TP7000 Range
Danfoss TP7000 Range

инструкция100 страниц(ы)

Drayton Digistat+1
Drayton Digistat+1

инструкция2 страниц(ы)

Drayton Digistat+2RF
Drayton Digistat+2RF

инструкция2 страниц(ы)

Grässlin Chronostat 1000
Grässlin Chronostat 1000

инструкция5 страниц(ы)

Grässlin Famoso 600
Grässlin Famoso 600

инструкция16 страниц(ы)

Grässlin Thermio 402
Grässlin Thermio 402

инструкция10 страниц(ы)

Grässlin Thermio E
Grässlin Thermio E

инструкция2 страниц(ы)

Посмотреть все Siemens руководства Посмотреть все Siemens термостат руководства

Описание

Краткое описание

  • Режимы работы: Комфорт, Экономия и Защита
  • Управляющие выходы: 2-точечные, 3-точечные или ШИМ
  • Автоматическое или ручное управление скоростью вентилятора
  • 3 мультифункциональных входа для ключ-карты, внешней комнатной температуры / температуры обратного воздуха (QAH11.1, QAA32), переключения нагрев / охлаждения, оконного контакта вкл/выкл, монитора точки росы, включения электронагревателя, аварийного контакта
  • Автоматическое или ручное переключение нагрев / охлаждение
  • Настраиваемые параметры управления и запуска
  • Минимальное и максимальное ограничение уставки
  • Подсветка дисплея

Приложения:

  • 2-трубная система
  • 2-трубная система с электронагревателем
  • 2-трубная система и радиатор / теплый пол
  • 4-трубная система
  • 4-трубная система с электронагревателем
  • 2-ступенчатый нагрев или охлаждение
Рабочее напряжение AC 230 В
Потребляемая мощность 8 ВА / 1 Вт, 1 Вт
Диапазон задания уставки 5…40 °C
Дифференциал переключения Нагрев: 0,5…6 K Охлаждение: 0,5…6 K
Колич. аналоговых входов 2
Колич. дискретных входов 1
Релейные выходы Вентилятор: 1- или 3-скоростной
Колич. дискретных выходов 3
Дискретный выход, ток коммутируемой цепи AC 230 В
Дискретный выход, ток коммутируемой цепи 5 (4) A
Тиристорный выход Клапан, эл. нагреватель , 2-позиционный, ШИМ, 3-точечный
Колич. тиристорных выходов 3
Тиристорный выход, переключающее напряжени AC 230 В
Тиристорный выход, ток переключения Макс. 1 A
Способ монтажа Монтаж на стену винтами
Класс защиты IP30
Размеры (Ш х В х Г) 93 x 128 x 30.8 мм

Логистическая информация

Длина упаковки, см 10,6
Ширина упаковки, см 14,7
Высота упаковки, см 5,8
Вес, кг 0,37

Информация по гарантии:

Гарантийный срок со стороны производителя составляет: 1 год

ГК «У2» является ведущим поставщиком оборудования  Департамента «Автоматизация и безопасность зданий» компании Siemens.

Наша главная задача  — предложение широкого ассортимента товаров и услуг на постоянно высоком качестве обслуживания.

Среди наших преимуществ можно отметить большой, постоянно поддерживаемый склад оборудования; лучшие ценовые условия и сроки поставки; детальный анализ проектов с выдачей корректной спецификации автоматики Siemens для заказа; индивидуальный подход и профессиональный менеджмент. Наши сотрудники всегда окажут профессиональное содействие в подборе оборудования по предоставленным характеристикам, детально изучат проект и выдадут конечные «рабочие» заказные спецификации с аргументами по рекомендациям.

Обращайтесь за RDG100 к нашим менеджерам любым удобным для вас способом. Мы гарантируем вам лучшее ценовое предложение на рынке!

ГК «У2» всегда держит на складах в больших объемах контроллерное оборудование Сименс, в частности Siemens Desigo , помимо этого у нас есть множество периферийного оборудования, такого как датчики, клапаны, приводы Siemens.

Характеристики

Варианты внешних датчиков для мультифункциональных входов
Ключ-карта, внешней комнатной температуры / температуры обратного воздуха (QAH11.1, QAA32), переключения нагрев / охлаждения, оконного контакта вкл/выкл, монитора точки росы, включения электронагревателя, аварийного контакта
Возможность подключения внешнего датчика температуры
Есть
Встроенные режимы работы
Комфорт<br>Энергосбережение<br>Защита от замерзания
Дискретный выход, напряжение
AC 230 В
Дискретный выход, ток коммутируемой цепи
5 (4) A
Класс защиты
IP30
Количество аналоговых входов
2
Количество дискретных входов
1
Количество дискретных выходов
3
Количество мультифункциональных входов
3
Наличие расписания
Нет
Ограничение подогрева пола
есть
Переключение режимов отопление/охлаждение
Автоматическое<br>Ручное
Подсветка экрана
Есть
Потребляемая мощность
8 ВА / 1 Вт;1 Вт
Рабочее напряжение
AC 230 В
Релейные выходы
Вентилятор: 1- или 3-скоростной
Ручное переключение скоростей вентилятора
Да
Способ монтажа
Монтаж на стену винтами
Срок гарантии, лет
1
Страна происхождения
Китай
Тип вентилятора фенкойла/конвектора
1 скорость<br>3 скорости
Тип термостата
Электронный
Тип фенкойла
2-х трубный<br>4-х трубный
Тиристорный выход
Клапан<br>эл. нагреватель<br>2-позиционный<br>ШИМ<br>3-точечный
Тиристорный выход, переключающее напряжение
AC 230 В
Тиристорный выход, ток переключения
Макс. 1 A
Управление приводом клапана
2-х точечное (вкл/выкл)<br>3-х точечное<br>ШИМ
Управление скоростью вентилятора фенкойла/конвектора
Автоматическое<br>Ручное
Цвет
Белый
Чем управляет термостат
Радиатор водяного отопления<br>Теплый водяной пол<br>Фенкойл 2-х трубный<br>Фенкойл 4-х трубный<br>Тепловой насос
Экран
LCD

Устройство:
Siemens RDG100


Размер: 3,79 MB
Добавлено: 2013-08-07 19:14:52

Количество страниц: 2
Печатать инструкцию

Скачать

Как пользоваться?

Наша цель — обеспечить Вам самый быстрый доступ к руководству по эксплуатации устройства Siemens RDG100. Пользуясь просмотром онлайн Вы можете быстро просмотреть содержание и перейти на страницу, на которой найдете решение своей проблемы с Siemens RDG100.

Для Вашего удобства

Если просмотр руководства Siemens RDG100 непосредственно на этой странице для Вас неудобен, Вы можете воспользоваться двумя возможными решениями:

  • Полноэкранный просмотр -, Чтобы удобно просматривать инструкцию (без скачивания на компьютер) Вы можете использовать режим полноэкранного просмотра. Чтобы запустить просмотр инструкции Siemens RDG100 на полном экране, используйте кнопку Полный экран.
  • Скачивание на компьютер — Вы можете также скачать инструкцию Siemens RDG100 на свой компьютер и сохранить ее в своем архиве. Если ты все же не хотите занимать место на своем устройстве, Вы всегда можете скачать ее из ManualsBase.

Siemens RDG100 Руководство по эксплуатации

Печатная версия

Многие предпочитают читать документы не на экране, а в печатной версии. Опция распечатки инструкции также предусмотрена и Вы можете воспользоваться ею нажав на ссылку, находящуюся выше — Печатать инструкцию. Вам не обязательно печатать всю инструкцию Siemens RDG100 а только некоторые страницы. Берегите бумагу.

Резюме

Ниже Вы найдете заявки которые находятся на очередных страницах инструкции для Siemens RDG100. Если Вы хотите быстро просмотреть содержимое страниц, которые находятся на очередных страницах инструкции, Вы воспользоваться ими.

Понравилась статья? Поделить с друзьями:
  • Siemens pm240 2 инструкция на русском
  • Siemens optipoint key module инструкция
  • Siemens optipoint 500 entry инструкция
  • Siemens openstage 15 hfa инструкция на русском
  • Siemens ncdr 1100 инструкция на русском