Page 3
___________________ SITRANS P DS III with HART Introduction ___________________ Safety instructions ___________________ Description SITRANS ___________________ Installing/mounting Pressure transmitter ___________________ SITRANS P DS III with HART Connecting ___________________ Operation Operating Instructions ___________________ Operating functions through HART ___________________ Functional safety ___________________ Commissioning… -
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. -
Page 5: Table Of Contents
Measuring cell for absolute pressure, front-flush membrane …………32 Remote seal ……………………..33 SIMATIC PDM ……………………..34 Installing/mounting ……………………..35 Basic safety instructions ………………….35 4.1.1 Installation location requirements ………………..39 4.1.2 Proper mounting……………………… 39 SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 6
6.5.5.3 Blind setting of full scale value ………………..90 6.5.5.4 Blind adjusting of the start of scale value ………………90 6.5.5.5 Blind adjustment of the full scale value ………………91 SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 7
Trimming the sensor ……………………130 7.17 Current sensor trim ……………………130 7.18 Factory calibration ……………………132 7.19 Static configuration data ………………….132 7.20 Flow rate measurement (only differential pressure) …………..134 SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 8
Display in case of a fault ………………….170 10.2.4 Changing the measuring cell and application electronics …………170 10.3 Cleaning ………………………. 171 10.3.1 Servicing the remote seal measuring system …………….172 10.4 Return procedure ……………………173 SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 9
SITRANS P, DS III for gauge pressure and absolute pressure from the gauge pressure series ……………………….203 12.2 SITRANS P DS III for differential pressure, flow rate and absolute pressure from the differential pressure series ………………….205 12.3 SITRANS P DS III for level ………………….208 12.4… -
Page 10
Table of contents SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 11: Introduction
The programming manual is an integral part of the CD, which is either supplied or can be ordered. The programming manual is also available on the Siemens homepage. On the CD, you will also find the catalog extract with the ordering data, the Software Device Install for SIMATIC PDM for additional installation, and the required software.
-
Page 12: History
Absolute pressure from the differential pressure series 7MF4433 Differential pressure and flow rate, PN 32/160 (MAWP 464/2320 psi) 7MF4533 Differential pressure and flow rate, PN 420 (MAWP 6092 psi) 7MF4633 Level SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 13: Checking The Consignment
● Devices/replacement parts should be returned in their original packaging. ● If the original packaging is no longer available, ensure that all shipments are properly packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages.
-
Page 14: Notes On Warranty
The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
-
Page 15: Safety Instructions
● National Electrical Code (NEC — NFPA 70) (USA) ● Canadian Electrical Code (CEC) (Canada) Further provisions for hazardous area applications are for example: ● IEC 60079-14 (international) ● EN 60079-14 (EC) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 16: Conformity With European Directives
Due to the large number of possible applications, each detail of the described device versions for each possible scenario during commissioning, operation, maintenance or operation in systems cannot be considered in the instructions. If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note…
-
Page 17: Use In Hazardous Areas
• Connect the device with type of protection «Intrinsic safety» solely to an intrinsically safe circuit. • Observe the specifications for the electrical data on the certificate and in Chapter «Technical data (Page 175)». SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 18
• Devices and tools used must be free of static charge. • Hold modules only by their edges. • Do not touch connector pins or conductor tracks on a module with the ESD notice. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 19: Description
● PC with HART modem, on which appropriate software is installed, e.g. SIMATIC PDM (load 230 … 500 Ω) ● Control system which can communicate via the HART protocol, e.g. SIMATIC PCS7 Figure 3-1 Possible system configurations SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 20: Application Range
● Gauge pressure, suitable for small positive or negative pressure value ● in combination with a restrictor device: flow rate q ~ The smallest measuring span is 1 mbar (0.0145 psi), the largest 30 bar (435 psi). SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 21
100 bar a (1450 psi a). The smallest measuring span of the «gauge pressure» series is 8.3 mbar a (0.12 psi a), and the largest is 30 bar a (435 psi a). SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 22: Structure
● The protective conductor terminal/equipotential bonding terminal is located at the back of the enclosure. ⑩ ● The electrical terminal compartment for the auxiliary power and shield is accessible ⑨ when you remove the back cover SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 23: Nameplate Layout
The nameplate bearing the Order No. and other important information, such as design details and technical data, is on the side of the enclosure. ① ② Order number (machine-readable product Serial number code) Figure 3-3 Example of a nameplate SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 24: Measuring Point Label Layout
Example of a nameplate Measuring point label layout Figure 3-5 Example of measuring point label Functional principle 3.6.1 Overview of mode of operation This chapter describes how the transmitter works. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 25: Operation Of The Electronics
● This signal is amplified by the measuring amplifier and digitized in an analog-to-digital ③ converter ④ ● The digital signal is analyzed in a microcontroller and corrected with regard to linearity and thermal characteristics. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 26: Measuring Cell Operation
In the following sections, the process variable to be measured is called general inlet pressure. Overview The following modes of operation are described: ● Gauge pressure ● Absolute pressure ● Differential pressure and flow rate ● Level SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 27: Measuring Cell For Gauge Pressure
Transmitters with measuring span ≤ 63 bar measure the inlet pressure against atmosphere, those with measuring spans ≥ 160 bar against vacuum. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 28: Measuring Cell For Differential Pressure And Flow Rate
(bridge circuit) of the differential pressure sensor. ● The change in the resistance causes a bridge output voltage proportional to the differential pressure. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 29: Measuring Cell For Level
The displacement changes the resistance of the four doped piezoresistors in the bridge circuit. ● The change in the resistance causes a bridge output voltage proportional to the differential pressure. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 30: Measuring Cell For Absolute Pressure From The Differential Pressure Series
(bridge circuit) of the absolute pressure sensor. ● The change in the resistance causes a bridge output voltage proportional to the absolute pressure. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 31: Measuring Cell For Absolute Pressure From The Gauge Pressure Series
, displacing its measuring diaphragm. The displacement changes the resistance of the four piezoresistors (bridge circuit) of the absolute pressure sensor. The change in the resistance causes a bridge output voltage proportional to the inlet pressure. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 32: Measuring Cell For Gauge Pressure, Front-Flush Membrane
Measuring cell Filling liquid ② ⑤ Process connection Absolute pressure sensor ③ Seal diaphragm Inlet pressure Figure 3-13 Function chart of the measuring cell for absolute pressure, flush mounted diaphragm SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 33: Remote Seal
● The loss of transmission fluid results in inaccuracies in the measurement and failure of the measuring system. ● In order to avoid leaks and measuring errors, please observe the installation and maintenance instructions in addition to the safety notes. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 34: Simatic Pdm
SIMATIC PDM allows the process device data to be: ● displayed ● set ● modified ● saved ● diagnosed ● checked for plausibility ● managed ● simulated SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 35: Installing/Mounting
Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
-
Page 36
• In the case of a conduit system, mount a spark barrier at a defined distance from the device input. Observe national regulations and the requirements stated in the relevant approvals. See also Technical data (Page 175) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 37
Loss of explosion protection Danger of explosion in hazardous areas if the device is open or not properly closed. • Close the device as described in Chapter «Connecting the device (Page 62)». SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 38
Damage to device by severe external stresses and loads (e.g. thermal expansion or pipe tension). Process media can be released. • Prevent severe external stresses and loads from acting on the device. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 39: Installation Location Requirements
• Make sure that process connectors are clean, and suitable gaskets and glands are used. • Mount the device using suitable tools. Refer to the information in Chapter «Technical data (Page 175)», for example installation torques requirements. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 40: Disassembly
• If the device contains dangerous media, it must be emptied prior to disassembly. Make sure that no environmentally hazardous media are released. • Secure the remaining connections so that no damage can result if the process is started unintentionally. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 41: Installation (Except Level)
Install the transmitter below the pressure tapping point. Lay the pressure tubing with a constant gradient to the pressure tapping point so that any gas pockets can escape in the main line. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 42: Installation (Except Level)
● On a wall or a mounting frame using two screws ● On a vertical or horizontal mounting tube (Ø 50 to 60 mm) using a tube bracket Fasten the transmitter mounting bracket using the two screws provided. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 43
Fastening the transmitter on the mounting bracket Figure 4-2 An example of fastening the transmitter on the mounting bracket in the case of differential pressure and horizontal differential pressure lines SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 44: Level» Installation
Instructions for level installation Requirements Note Compare the desired operating data with the data on the nameplate. Please also refer to the information on the remote seal if this is fitted. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 45: Installation For Level
Ensure that the seal is centrically positioned and that it does not restrict the movement of the flange’s seal diaphragm in any way as otherwise the tightness of the process connection is not guaranteed. 2. Screw on the transmitter’s flange. 3. Observe the installation position. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 46: Connection Of The Negative Pressure Line
Measurement assembly on an open container Lower filling level Δp Start of scale value Upper filling level Δp Full-scale value Pressure ρ Density of the measured medium in the container Acceleration due to gravity SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 47
(mostly with the condensate of the measured medium) and install a condensate pot. You can cut off the device using the dual pneumatic block 7MF9001-2. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 48
The process connection on the negative side is a female thread -18 NPT or an oval flange. Lay the line for the negative pressure using a seamless steel tube 12 mm x 1.5 mm. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 49: Remote Seal» Installation
The pressure rating specified on the remote seal applies to reference conditions according to IEC 60770. • For the maximum permissible pressure at higher temperatures, please refer to the standard specified on the remote seal. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 50: Installation Of The Remote Seal With The Capillary Line
– If halocarbon oil is used as the filling liquid, this maximum height difference is only = 4 m, see installation types A and B. 1max. If negative overpressure is observed during measurements, reduce the permissible height difference accordingly. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 51
Distance between the container flange and the pressure transmitter For absolute pressure measurements (vacuum), install the measuring device at least at the height of the remote seal or below it (see installation types C). SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 52
Full scale pressure ρ Density of the filling oil in the capillary line of the remote seal Acceleration due to gravity Distance between the container flange and the pressure transmitter SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 53
Full-scale value Start of scale pressure start Full scale pressure ρ Density of the filling oil in the capillary line of the remote seal Acceleration due to gravity Gland distance SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 54
Density of the process medium in the container ρ Density of the filling oil in the capillary line of the remote seal Acceleration due to gravity Lower filling level Upper filling level Gland distance SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 55
= ρ * g * H — ρ * g * H Full-scale value: = ρ * g * H — ρ * g * H Below the lower measuring point SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 56: Turing The Measuring Cell Against Housing
③ electronic housing. An orientation mark is provided at the throat of the measuring cell. This mark must remain in the marked section when turning. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 57
(Allen screw 2.5 mm). 2. Turn the electronic housing against the measuring cell. Follow the marked turning range ① while doing so. 3. Tighten the retaining screw (torque: 3.4 to 3.6 Nm). SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 58: Rotating The Display
You can turn it by ±90° or ±180°. 3. Screw the covers back on as far as they will go. 4. Secure the covers with the cover catch. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 59: Connecting
• Connect the device in accordance with the specified power supply and signal circuits. The relevant specifications can be found in the certificates, in Chapter «Technical data (Page 175)» or on the nameplate. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 60
• Circuits of limited energy may also be connected in the energized state in hazardous areas. • Exceptions for type of protection «Non-sparking nA» (Zone 2) are regulated in the relevant certificate SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 61
For metal housings there is an increased electromagnetic compatibility compared to high- frequency radiation. This protection can be increased by grounding the housing, see Chapter «Connecting the device (Page 62)». SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 62: Connecting The Device
• Refer to HART communication information in Chapter «Technical data (Page 175)». Connecting the device Opening the device 1. Unscrew the cover of the electrical cable compartment. An identification text «FIELD TERMINAL» is provided at the side of the housing. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 63
Safety catch ③ ⑦ Cable entry for auxiliary power/analog Protective conductor connection/ output equipotential bonding terminal ④ ⑧ Connecting terminals Process connection ⑨ Ground terminal Figure 5-1 Electrical connection, power supply SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 64: Connecting The Han Plug
Structure (Page 22) Connecting the Han plug WARNING The connector may only be used for Ex ia devices and non-Ex devices; otherwise the safety required for the approval is not guaranteed. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 65
3. Crimp the contact parts on the cable ends. 4. Assemble the coupling socket. Output current Auxiliary power Connector pin assignment with Han 7D or Han 8D plug See also Technical data (Page 175) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 66: Connecting The M12 Connector
Figure 5-3 Preparing the connecting cable ① ③ Reference edge for stripping Insulating sleeve over the shield ② ④ Reference edge for the dimension Shrink sleeve specifications for cable assembly SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 67
Layout for M12 jack ① ① M12 x 1 thread Positioning slot ② Positioning catch Not connected Not connected Shield Shield Middle jack contact not connected See also Technical data (Page 175) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 68
Connecting 5.4 Connecting the M12 connector SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 69: Operation
Blind adjustment of the full scale value Zero point calibration (position correction) Current transmitter Fault current Keyboard lock and write protection Yes, release except for write protection Unit type, unit SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 70: Basic Safety Instructions
The operating instructions in the «Local operation without display» section apply if the device has been delivered with a blind cover. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 71: Display
Violation of upper limit displays are also referred to as status since they have meanings dependent on the settings. ⑧ If the communication display blinks, this indicates an active communication. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 72: Units Display
The status of one of the device variables is • «UNCERTAIN». «SIMULATION» Is always displayed when the simulation of a pressure value or temperature value is active. See also Measured value status (Page 116) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 73: Error Display
Event counter for limit values exceeded – Calibration time expired – Current saturation reached the status of one of the device variables is «BAD». • «SENSOR BREAK» Appears when there is a sensor break. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 74: Mode Display
Adjusting damping if the upper damping value is if the value falls below the exceeded lower damping value only for the pressure device version only for the pressure device version SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 75: Overflow Range
Violations of the measured value limits are output on the display by or . Note The setting of the overflow range and the fault current range can be freely selected via HART communication. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 76: Local Operation
Display Increment key ② ⑤ Connecting plug for the display Decrement key ③ ⑥ Mode key Key symbols shown in the key cover Figure 6-5 Position of keys and display SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 77
Measured value in pressure unit Current Current Current switch on constant output current in mA transmitter higher lower «3.6»; «4», «12», «20» or «22.8» Switch off using the [M] key. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 78
Y22, unit as from the specified) table of the physical unit Not relevant for gauge and absolute pressure) See also Overview of operation (Page 69) Operating functions through HART communication (Page 105) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 79: Operation Using Buttons
Modes 2 and 3 are used for this. Rising and falling characteristic curves can be realized with appropriate use of the buttons. If the transmitter is not in «Pressure» measuring mode, this mode is skipped in local operation. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 80
Current calculation formula for setting Example of setting with reference pressure A Initial situation B Setting start of scale value C Setting full scale value Explanations for the example of setting with reference pressure SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 81
To calculate the output currents when setting the start of scale value or the full scale value, the reference pressure must be selected such that a value between 4 and 20 mA results for the current. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 82
The «Current calculation formula for adjusting» can be used to calculate the current to be adjusted for the desired full scale value I (16 mA at 14 bar) with the existing reference pressure. It can be adjusted with the [↑] or [↓] buttons I SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 83: Setting/Adjusting The Start Of Scale Value
To set the output current of the start of scale value to 4 mA, proceed as follows: 1. Create the reference pressure. 2. Set mode 2. 3. Set the start of scale value to 4 mA. 4. Save with the [M] button. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 84: Setting/Adjusting The Full Scale Value
Set or adjust the full scale value of the pressure transmitter in mode 3. You can also adjust the start of scale value or the full scale value separately as well as adjust both these values one after the other. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 85
You have a device with a cover that does not have an inspection window and you do not wish to set the full scale value, but adjust it continuously. You will need an ammeter for this purpose. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 86: Setting/Adjusting Electrical Damping
Condition for «adjusting» The default setting of steps is an interval of 0.1 seconds. If you press the [↑] or [↓] button for a longer time, the step is increased. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 87: Blind Start Of Scale Value/Full Scale Value
(measuring span ratio = r, turn down). The correlation between the measured pressure and the output current generated is linear. The square root extracting characteristic curve for differential pressure transmitters is an exception. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 88
With a marked elevation of the zero point, the full scale value must therefore previously be reduced such that it still lies within the permitted range after elevation of the zero point. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 89: Blind Setting Of Start Of Scale Value
You have not created any reference pressure and have selected a pressure unit. Procedure To the set the start of scale value blindly, proceed as follows: 1. Set mode 5. 2. Press the [↑] and [↓] buttons simultaneously for 2 seconds. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 90: Blind Setting Of Full Scale Value
You can toggle between rising and falling characteristic curves. Condition You are familiar with the correct operation of the transmitter and the associated safety notes. You have not created any reference pressure and have selected a pressure unit. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 91: Blind Adjustment Of The Full Scale Value
The device type determines the way in which you proceed. SIMATIC PDM or the HART communicator will display the total of all zero point corrections. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 92: Current Transmitter
The following output current can be adjusted irrespective of the input pressure: ● 3.6 mA ● 4.0 mA ● 12.0 mA ● 20.0 mA ● 22.8 mA You can use HART communication to adjust intermediate values. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 93: Output Current In Case Of Fault
3. Save using the [M] key. Note If a current saturation interrupt is active, the setting of the output current may deviate from your setting in the case of a fault. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 94: Locking Buttons And Functions
The device can be operated by means of HART communication. Keys on the transmitter are partially locked. Exception: Setting start of scale value • Releasing key lock • The device can be operated by means of HART communication. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 95
In the measured value display function, check whether the desired setting is displayed. Procedure To disable the buttons, proceed as follows: 1. Set mode 10. 2. Select the desired lock mode. 3. Confirm the lock mode with the [M] button. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 96: Releasing Key Lock Or Function Lock
Variable application point The output current for the «srlin» and «sroff» functions can be displayed linearly or set to zero below the application point of the square root extracting characteristic curve. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 97
The root extraction function «srli2» is set in «flow rate» measuring mode. You therefore set the «characteristic curve» parameter in SIMATIC PDM to «linear». SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 98
Characteristic curves and application point of square root extracting characteristic curves SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 99: Measured Value Display
SIMATIC PDM. You will finds details of the relation between primary variable (PV) assignment and the DV in the following section: Measuring mode «Pressure» (Page 108) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 100: Unit
3. Save with the [M] button. See also Measured value display (Page 127) 6.5.13 Unit Introduction In mode 14, select the physical unit in which the measured value display of the device should be shown. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 101
FTH2O g/cm2 Gcm2 mm mercury column mmHG Kg/cm2 KGcm2 Inch mercury column in_HG Torr TORR mm water column (4°C / 39 °F) m4H2O Inch water column (4°C / 39°F) i4H2O SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 102
Long ton / d lT/d T / d Table 6- 11 Units available for temperature Temperature unit Display Temperature unit Display ° Celsius ° / C Kelvin ° Fahrenheit ° / F Rankine SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 103
British barrel liquid / minute bbl/m Gallon / second Gal/S British barrel liquid / hour bbl/h Gallons/minute Gal/m British barrel liquid / day bbl/d See also Selection of the physical unit (Page 128) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 104
Operation 6.5 Local operation SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 105: Operating Functions Through Hart
«Pressure», «Level», «Flow rate» and a user programmable «Characteristic curve». One or more device variables are permanently allocated to each measuring mode in order to execute corresponding measuring tasks. See also Overview of operation (Page 69) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 106: Process Tag Data
One or more device variables are permanently allocated to each measuring mode. The following device variables are always active and are therefore always displayed: ● Pressure ● Sensor temperature ● Electronics temperature ● Pressure (untrimmed) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 107: Measuring Mode Selector
The dynamic variables «Primary», «Secondary», «Tertiary» and «Quarternary» (PV, SV, TV, QV) can be interconnected with any active device variables. Various different measuring mode examples are conceivable with a 4 bar pressure transmitter. See also Measured value status (Page 116) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 108: Measuring Mode «Pressure
SIMATIC PDM or the HART communicator. Device variable Start of scale value Full scale value Primary variable Quarternary variable Secondary variable Tertiary variable Figure 7-1 Measuring mode «Pressure» SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 109: Customized Characteristic Curve
With regard to the device variable status, rising characteristic curves are however preferred. Otherwise the meanings of HIGH LIMIT and LOW LIMIT are swapped. See also Measured value status (Page 116) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 110: Measuring Mode «Level
0 bar process pressure, 10 m is displayed in DV4 and 20 m is displayed at 2 bar. The values for the start of scale value and the full scale value, which are effective for the analog output, are configured in the «analog output» block. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 111
Activate the «Level» measuring mode for this purpose. For all settings, the measuring limits may be exceeded by +/-20%. Values which lie above or below that will be rejected by the device. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 112: Measuring Mode «Flow Rate
In the calculation example, the input value for the «root extraction function» is approx. 25 % for a prevailing process pressure of 0.5 bar. The output value is approximately 50%. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 113
In SIMATIC PDM or the HART communicator, the «Flow rate» block is configured in an online dialog box in an extremely compact manner. In this online dialog box, you can compile all values in a menu and transfer them to the device collectively. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 114: Measuring Mode «User
All alphabetic a…z, A…Z and numeric 0…9 inputs are allowed for the customized unit. The following characters are also allowed: ° » $ / < > * , _ + — = @ SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 115
0.5 bar, there is a value of 25% on the characteristic curve. DV [x] Device variable x Start of scale value Pressure Full scale value Figure 7-7 Functions of the «User» block SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 116: Measured Value Status
● LOW LIMIT A higher-level diagnosis program can display and analyze these states. GOOD status During smooth, uninterrupted operation, the measured value status of all active device variables is GOOD. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 117
The reasons for changes in the status of a device variable are summarized in the table. If there were several reasons for a change in status, MANUAL always has the highest priority. BAD has the second highest and UNCERTAIN the third highest priority. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 118
When DV2 more than 20% Analog-to- Analog-to- temperature digital converter DV2 is outside the sensor digital digital simulated limits converter in converter in over/underrang overrange underrange e, fault in linearization SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 119
If you use falling characteristic curves in the blocks, the meanings of HIGH LIMIT and LOW LIMIT are swapped around. If you mix falling and rising characteristic curves, the meanings will be swapped each time a falling characteristic curve is run. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 120: Analog Output
In this case, a current of 4 mA is output for a measured height of 12 m, and a current of 20 mA for 18 m. Device variable Start of scale value Primary variable Full scale value Secondary variable Tertiary variable Quarternary variable Figure 7-9 «Analog output» scaling SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 121: Scaling The Display Value
This display option has the highest priority amongst all options. A switch over to %, mA or any other unit is not possible in this status. You need to deactivate the LCD scaling again for this purpose. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 122: Setting Zero Point And Limit Point
Communicator. You can use this function to realize rising or falling characteristic curves. The pressure unit can be set separately for the display and for HART communication. See also Difference between setting and adjusting (Page 79) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 123: Blind Setting Of Zero Point And Limit Point
With an upstream pressure of 100 mbar, the effective measuring range of a 1-bar transmitter is reduced to a point between 0 and 0.9 bar. See also Trimming the sensor (Page 130) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 124: Electrical Damping
SIMATIC PDM or the HART Communicator. Reference NAMUR recommendation NE43 dated 03.02.2003 «Standardization of the signal level for the breakdown information of digital transmitters» SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 125: Setting The Current Limits
Recommended setting range for lower fault current range and lower control range limit ⑦ Recommended setting range for upper fault current range and upper control range limit Figure 7-12 Current limits SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 126: Key Lock And Write Protection
The device can be operated by means of HART communication. Write protection You can now only release the lock using HART communication. See also Locking buttons and functions (Page 94) Releasing key lock or function lock (Page 96) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 127: Measured Value Display
GAUGE (G) or ABS (A). The add-on has no effect on the real measured value. To do so, select the option Gauge or Absolute under the «Pressure display type» menu item. There are two options for the display: SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 128: Selection Of The Physical Unit
The unit can be set separately for the display and for HART communication. You can also choose to link the setting of the two units. See also Unit (Page 100) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 129: Bar Graph
100 mbar is available. You can carry out zero point correction by performing a lower sensor trim at 100 mbar. Note The accuracy of the test device should be at least three times as high as that of the transmitter. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 130: Trimming The Sensor
The current that is output by the transmitter can be trimmed independently of the pressure measuring circuit. This function is designed for compensating inaccuracies in the processing chain following the transmitter. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 131
If a multimeter is used, it must always be sufficiently accurate. Original characteristic Characteristic curve after current transmitter trim 4 mA Characteristic curve after current transmitter trim 20 mA Figure 7-15 Current transmitter trim SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 132: Factory Calibration
These values are not contained in the «Factory calibration» function; in other words, changes in the device are permanently saved. List of variable material parameters: ● Flange type ● Flange material ● Remote seal type SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 133
● Material of vent valve ● Vent valve position ● Remote seal type ● Remote seal ● Diaphragm material ● Remote seal filling medium You can use up to 16 characters for each entry. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 134: Flow Rate Measurement (Only Differential Pressure)
HART communication allows you to activate and evaluate a wide range of diagnostic functions from a central control room or onsite: ● Calibration/service timer ● Min/max indicator ● Limit monitoring modules SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 135: Operating Hours Counter
On expiry of a second time span set by parameter as a time difference, a diagnostic alarm is reported and a fault current is output. The calibration intervals for the electronics are calculated using the following formula: SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 136
The timer immediately starts running again from zero and will report again when the warning/alarm limit is next reached. The next calibration interval is therefore immediately active. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 137: Min/Max Indicator
Consequently, the values are available even after the device is restarted. The min/max indicators are also updated during a simulation. Pressure Time Figure 7-16 Basic representation of min/max indicators SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 138: Limit Modules
Example 3 shows the direction of fault current with the «Saturated current value» setting. Example 4 shows the direction of fault current with the «Active upper interrupt value» setting. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 139
«Active upper interrupt value» setting. The upper fault current is outputted although the direction of current saturation is downward. Figure 7-17 Four examples of saturation monitoring See also Fault current (Page 124) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 140: Simulation
You can simulate the pressure and both temperature values. It should be noted here that changing the temperatures by simulation will have no effect on the measured pressure value. Figure 7-18 Block diagram of simulation SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 141: Simulation As Fixed Value
Upper limit value Upper limit value in the unit of the device variable. Lower limit value Lower limit value in the unit of the device variable. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 142
Limit monitoring, warning/interrupt: lower limit Select whether a warning or a warning plus an interrupt should be triggered when the event counter lower limit is violated. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 143
Figure 7-20 Limit monitor and event counter Messages from the limit monitor and from the event counter can be acknowledged separately. Resetting the event counter starts a new monitoring interval. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 144
Operating functions through HART 7.23 Limit monitor SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 145: Functional Safety
Note Use of remote seals If remote seals are used, the application-specific measurement error is the product of the transmitter and remote seal measurement errors. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 146
Only one SITRANS P DS III device is required for single-channel operation for SIL 2. Safety-instrumented system in multi-channel operation (SIL 3) Figure 8-2… -
Page 147: Safety Integrity Level (Sil)
P DS III devices. As soon as the measured values differ by e.g. 2% or more, the system must be brought into the safe state and the fault must be located. Two SITRANS P DS III devices are required for multi-channel operation for SIL 3. Operation with one DS III is not permitted.
-
Page 148
● The configuration level of the firmware is blocked against unauthorized operation. ● The function requires SIL of less than 4. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 149: Settings
Requirement: See Releasing key lock or function lock (Page 96). We recommend that: SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 150: Safety Characteristics
Functional safety 8.4 Safety characteristics ● Check both SITRANS P DS III devices as follows for a safety-instrumented system in multi-channel operation (SIL 3). ● You check the status for warnings and alarms. ● You check the measured value limits.
-
Page 151: Maintenance/Checking
(order option C20) or 72 hours (order option C23). Special points to note for multi-channel operation (SIL 3) ● Two SITRANS P DS III devices are required for multi-channel operation in accordance with SIL 3. ● The automation system must monitor the measured values of both devices. The system must be put into safe mode as soon as the measured values differ too greatly.
-
Page 152: Add-On Parts
1. Check the connection between the transmitter and remote seal and between the remote seal and the plant for leaks. 2. Observe the safety information and specifications in chapter Installing/mounting (Page 35). SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 153: Commissioning
• Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in accordance with the directives. Exception: Devices having the type of protection «Intrinsic safety Ex i» may also be opened in energized state in hazardous areas. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 154: Introduction To Commissioning
The operating data must correspond to the values specified on the nameplate. If you switch on the auxiliary power, the transmitter will operate. The following commissioning cases are typical examples. Configurations different from those listed here may be meaningful depending on the system configuration. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 155: Gauge Pressure, Absolute Pressure From The Differential Pressure Series And Absolute Pressure From The Gauge Pressure Series
Shut-off module Shut-off valve ③ Shut-off valve to process ⑦ Shut-off valve (optional) ④ Shut-off valve for test connection or for ⑧ Condensate vessel (optional) bleed screw ⑨ Drain valve SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 156
④ 5. Close the shut-off valve for the test connection ⑥ 6. Open the shut-off valve at the pressure tapping point. ③ 7. Open the shut-off valve for the process SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 157: Commissioning With Steam Or Liquid
④ 5. Close the shut-off valve for the test connection ⑥ 6. Open the shut-off valve at the pressure tapping point. ③ 7. Open the shut-off valve for the process SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 158: Differential Pressure And Flow Rate
Measure • Make sure the locking screw and/or the vent valve are screwed in and tightened. • Ensure that the valves are operated correctly and properly. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 159: Commissioning In Gaseous Environments
Differential pressure valves Condensate vessels (optional) ⑤ ⑨ Differential pressure lines Differential pressure transducer Transmitter above the differential Transmitter below the pressure transducer differential pressure transducer Condition All shut-off valves are closed. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 160: Commissioning For Liquids
④ ⑨ Differential pressure valves Differential pressure transducer ⑤ ⑩ Differential pressure lines Vent valves ⑥ Shut-off valves Transmitter below the differential pressure Transmitter above the transducer differential pressure transducer SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 161
12.Check and if required adjust the zero point (4 mA) if the start of scale value is 0 bar. ② 13.Close the stabilizing valve ③ ④ 14.Open the differential pressure valves ( ) completely. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 162: Commissioning With Vapor
② ① stabilizing valve is then opened, the transmitter can be damaged by the flow of vapor. • Follow the specified procedure for commissioning. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 163
12.Close the stabilizing valve ③ ④ 13.Fully open the differential pressure valves ⑦ 14.You can briefly open the drain valves to clean the line. ⑦ 15.Close the drain valve before vapor escapes. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 164
Commissioning 9.4 Differential pressure and flow rate SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 165: Service And Maintenance
WARNING Impermissible repair of explosion protected devices Danger of explosion in areas subject to explosion hazard. • Repair must be carried out by Siemens authorized personnel only. WARNING Impermissible accessories and spare parts Danger of explosion in areas subject to explosion hazard.
-
Page 166
• As long as the device is under pressure, do not loosen process connections and do not remove any parts that are pressurized. • Before opening or removing the device ensure that process media cannot be released. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 167
• Disconnect the device before you open the enclosure or remove enclosure parts. • Observe the special precautionary measures if maintenance is required while the device is live. Have maintenance work carried out by qualified personnel. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 168: Maintenance And Repair Work
• Define a maintenance interval for regular tests in line with device use and empirical values. • The maintenance interval will vary from site to site depending on corrosion resistance. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 169: Checking The Gaskets
Siemens. 1. Clean the enclosure and seals. 2. Check the enclosure and seals for cracks and damage. 3. Grease the seals if necessary. — or — 4. Replace the seals. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 170: Display In Case Of A Fault
PC with HART modem and HART software or PC with HART modem and PDM software). Factory settings will be used if application-specific data are not backed up before the measuring cell is changed. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 171: Cleaning
WARNING Electrostatic charge Danger of explosion in hazardous areas if electrostatic charges develop e.g. when cleaning plastic enclosures with a dry cloth. • Prevent electrostatic charging in hazardous areas. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 172: Servicing The Remote Seal Measuring System
NOTICE Improper cleaning of diaphragm Device damage. The diaphragm can be damaged. • Do not use sharp or hard objects to clean the diaphragm. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 173: Return Procedure
Any devices/replacement parts returned without a decontamination declaration will be cleaned at your expense before further processing. The forms can be found on the Internet as well as in the documentation which comes with the device. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 174: Disposal
Note Special disposal required The device includes components that require special disposal. • Dispose of the device properly and environmentally through a local waste disposal contractor. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 175: Technical Data
● Measuring accuracy (Page 184) ● Operating conditions (Page 191) ● Construction (Page 194) ● Display, keyboard and auxiliary power (Page 199) ● Certificates and approvals (Page 200) ● HART communication (Page 202) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 176: Input Point
(1450 psi g) for oxygen measurement) 100 bar g (1450 psi g) for oxygen ambient temperature/process temperature measurement) ambient temperature/process 60°C temperature 60°C Start of scale value Between the measuring limits (fully adjustable) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 177
5 bar a 10 bar a 30 bar a 5000 mbar a (145 psi a) (435 psi a) (72.5 psi a) (145 psi a) (435 psi a) (2.32 … 72.5 psi a) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 178
100% of max. measuring range 1 bar g (14.5 psi g) only in PMC-Style Standard, not in Minibolt For PMC-Style Minibolt, the span should not be less than 500 mbar SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 179
(1450 psi g) for oxygen measurement) 100 bar g (1450 psi g) for oxygen ambient temperature/process temperature measurement) ambient temperature/process 60°C temperature 60°C Start of scale value Between the measuring limits (fully adjustable) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 180
(1450 psi g) for oxygen measurement) 100 bar g (1540 psi g) for oxygen ambient temperature/process temperature measurement) ambient temperature/process 60°C temperature 60°C Start of scale value Between the measuring limits (fully adjustable) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 181
-100% of max. measuring range Measuring cell with • (-33 % for 30 bar (435 psi) measuring cell) or 30 mbar a (0.44 psi a) silicone oil filling Measuring cell with • inert liquid SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 182
-100% of the max. measuring range or 30 mbar a (0.44 psi a) depending on the mounting Measuring cell with • flange inert liquid Upper measuring limit 100% of maximum span 100% of max. measuring range Start of scale value between the measuring limits continuously adjustable SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 183: Output
Linearly increasing or linearly decreasing • Linear increase or decrease or square root extracting increasing (only for • DS III differential pressure and flow rate) Bus physics – IEC 61158-2 Polarity-independent – SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 184: Measuring Accuracy
Effect of auxiliary power supply In percent per change in voltage – 0.005 % per 1 V Measuring value resolution – 3 • 10 of the rated measuring range SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 185
Correction via zero offset Effect of auxiliary power supply In percent per change in voltage – 0.005 % per 1 V Measuring value resolution – 3 • 10 of the rated measuring range SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 186
In percent per change in voltage – 0.005 % per 1 V Measured value resolution – 3 • 10 of the rated measuring range *) not for 4 bar PMC Minibolt SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 187
Correction via zero offset Effect of auxiliary power supply In percent per change in voltage – 0.005 % per 1 V Measured-value resolution – 3 • 10 of the rated measuring range SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 188
As percentage (double values for measuring cell 20 mbar g (0.29 psi g)) ≤ (0.08 • r + 0.1) % ≤ 0.3% At -10 … +60°C (14 … 140°F) • SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 189
– 10 < r ≤ 30 • ≤ (0.0075 • r + 0.075) % – 30 < r ≤ 100 • Settling time T without electrical Approx. 0.2 s damping SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 190
Effect of auxiliary power supply In percent per change in voltage 0.005 % per 1 V Measured-value resolution – 3 • 10 of the rated measuring range SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 191: Operating Conditions
Measuring cell with inert liquid • -10 … +85 °C (14 … 185 °F) Measuring cell with Neobee • (FDA-compliant) -30 … +85 °C (-22 … +185 °F) Display • SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 192
-50 … +85 °C (-58 … +185 °F) Storage temperature • Climate class Condensation Permitted IP65, IP68 Degree of protection in • accordance with EN 60529 NEMA 4X Degree of protection in • accordance with NEMA 250 SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 193
30 bar (435 psi) Measuring cell with inert liquid -20 … +100 °C (-4 … +212 °F) -20 … +85 °C (-4 … +185 °F) Measuring cell • 30 bar (435 psi) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 194: Construction
Approx. 1.5 kg (3.3 lb) for aluminum enclosure Material Wetted parts materials • Process connection Stainless steel, mat. no. 1.4404/316L or Hastelloy C4, mat. no. 2.4610 Oval flange Stainless steel, mat. no. 1.4404/316L SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 195
Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision • casting, mat. no. 1.4408 Standard: Polyester-based paint • Option: 2 coats: Coat 1: epoxy-based; coat 2: polyurethane Stainless steel nameplate • SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 196
Option: 2 coats: Coat 1: epoxy-based; coat 2: polyurethane Stainless steel nameplate • Mounting bracket Steel or stainless steel Measuring cell filling Silicone oil • Inert liquid • Process connection SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 197
Stainless steel Mounting bracket Steel or stainless steel Measuring cell filling Silicone oil • Neobee M20 • Inert liquid • (max. 120 bar g (2320 psi g) for oxygen measurement) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 198
Sealing material in the pressure caps Viton for standard applications • Copper for underpressure • applications on the mounting flange Minus side Stainless steel, mat. no. 1.4404/316L Seal diaphragm • SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 199: Display, Keyboard And Auxiliary Power
Display, keyboard and auxiliary power Display and user interface Keys 3 for on-site programming directly at the device Display With or without integrated display (optional) • Cover with inspection window (optional) • SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 200: Certificates And Approvals
-40 … +85 °C (-40 … +185 °F) temperature class T4 -40 … +70 °C (-40 … +158 °F) temperature class T5 -40 … +60 °C (-40 … +140 °F) temperature class T6 SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 201
=17.5 V, I = 570 mA = 45 V Linear barrier = 32 V, I = 132 mA, P = 1 W Effective inner capacitance = 6 nF = 1.1 nF SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 202: Hart Communication
IBM-compatible, user memory > 32 MB, hard disk > 70 MB, depending on the type of modem: RS 232 interface or USB connection, VGA graphic Software for computer SIMATIC PDM SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 203: Dimension Drawings
Connection side ⑦ Mounting bracket (optional) ⑧ Process connection: -14 NPT, • Connection pin G A or • Oval flange • ⑨ Electronics side, display (longer for cover with inspection window) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 204
For Pg 13.5 with adapter, approx 45 mm (1.77 inches) Minimum distance for rotating Figure 12-1 Pressure transmitter SITRANS P DS III for absolute pressure, from the gauge pressure series, dimensions in mm (inches) SITRANS P DS III with HART… -
Page 205: Sitrans P Ds Iii For Differential Pressure, Flow Rate And Absolute Pressure From The Differential Pressure Series
Dimension drawings 12.2 SITRANS P DS III for differential pressure, flow rate and absolute pressure from the differential pressure series 12.2 SITRANS P DS III for differential pressure, flow rate and absolute pressure from the differential pressure series ① Key cover ②…
-
Page 206
Dimension drawings 12.2 SITRANS P DS III for differential pressure, flow rate and absolute pressure from the differential pressure series Not for «FM + CSA [is + XP]» type of protection For Pg 13.5 with adapter, approx 45 mm (1.77 inches) 92 mm (3.62 inches) minimum distance for rotating the enclosure with display… -
Page 207
Dimension drawings 12.2 SITRANS P DS III for differential pressure, flow rate and absolute pressure from the differential pressure series ① Key cover ② Blanking plug ③ Cover catch (only for «flameproof enclosure» type of protection) ④ Sealing plug, with valve (optional) ⑤… -
Page 208: Sitrans P Ds Iii For Level
Dimension drawings 12.3 SITRANS P DS III for level 12.3 SITRANS P DS III for level ① Key cover ② Blanking plug ③ Cover catch (only for «flameproof enclosure» type of protection) ④ Process connection: Minus side -18 NPT (EN 61518) ⑤…
-
Page 209: Sitrans P Ds Iii (Flush-Mounted)
92 mm (3.62 inches) minimum distance for rotating the enclosure with display Figure 12-5 SITRANS P DS III (flush mounted) The screen consists of a SITRANS P DS III with an example flange. On this screen, the height is divided into H and H…
-
Page 210: Note 3A And Ehdg
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) In the flange dimensions, only the height H is specified. 12.4.1 Note 3A and EHDG Note Approvals The references to the approvals for «EHEDG» and «3A» refer to the respective process connections and are not device-specific. Please refer to the technical data of the respective transmitter to see whether the desired certificate is available for your device/flange combination.
-
Page 211: F&B And Pharma Flange
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) Flanges as per ASME ASME B 16.5 CLASS ⊘D 110 mm (4.3») Approx. 52 mm (2») 125 mm (4.9») 1½» 130 mm (5.1») 1½» 155 mm (6.1») 150 mm (5.9») 165 mm (6.5») 190 mm (7.5»)
-
Page 212
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) DIN 11864-1 Form A — sterile threaded sockets ⊘D Approvals EHEDG DIN 11864-2 Form A — sterile collar flange ⊘D 94 mm (3.7») Approx. 52 mm (2») 113 mm (4.4») 133 mm (5.2») 159 mm (6.3») -
Page 213
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) Tri-Clamp as per DIN 32676 ⊘D 64 mm (2.5») Approx. 52 mm (2») 91 mm (3.6») Other connections Varivent connector ® ⊘D 40-125 84 mm (3.3») Approx. 52 mm (2») Approvals EHEDG Connection in accordance with DRD ⊘D… -
Page 214
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) BioConnect screwed joint ⊘D 2½» 105 mm (4.1») 3″ 105 mm (4.1») 4″ 145 mm (5.7») Approvals EHEDG BioConnect flange connector ⊘D 110 mm (4.3») Approx. 52 mm (2») 140 mm (5.5») 150 mm (5.9») -
Page 215: Pmc Style
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) Connect S flanged joint ⊘D 125 mm (4.9») Approx. 52 mm (2») 145 mm (5.7») 155 mm (6.1») 180 mm (7.1») 2″ 125 mm (4.9») 2½» 135 mm (5.3») 3″ 145 mm (5.7») 4″…
-
Page 216: Special Connections
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) PMC-Style Minibolt ⊘D – – 26.3 mm (1.0») Approx. 33.1 mm (1.3») 12.4.5 Special connections Tank connection TG52/50 and TG52/150 ⊘D TG52/50 43.5 mm 63 mm (2.5») Approx. 63 mm (2.5») TG52/150 43.5 mm…
-
Page 217
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) SMS threaded sockets ⊘D 2″ 70 x 1/6 mm (2.8″) Approx. 52 mm (2.1») 2½» 85 x 1/6 mm (3.3″) 3″ 98 x 1/6 mm (3.9″) IDF connectors IDF sockets with union nut ⊘D… -
Page 218
Dimension drawings 12.4 SITRANS P DS III (flush-mounted) SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 219: Spare Parts/Accessories
Subject to export regulations AL: N, ECCN, EAR99H Selection and order data Order no. Mounting bracket and fastening parts For SITRANS P DS III, DS III PA and DS III FF For gauge pressure transmitter (7MF403.-..-..C.) For transmitter for absolute pressure (7MF423.-..-..C.) 7MF4997-1AB Made of steel •…
-
Page 220
Selection and order data Order no. Mounting bracket and fastening parts For SITRANS P DS III, DS III PA and DS III FF For gauge pressure transmitter (7MF403.-..-..A., -..B. and -..D.) For transmitter for absolute pressure (7MF423.-..-..A., -..B. and — ..D.) -
Page 221: Order Data For Simatic Pdm
For SITRANS P DS III FF • Network card 7MF4997-1DN For SITRANS P DS III • 7MF4997-1DP For SITRANS P DS III PA and DS III FF • Sealing rings for pressure caps made of 7MF4997-2DA FPM (Viton) • 7MF4997-2DB PTFE (Teflon) •…
-
Page 222
Spare parts/accessories 13.2 Order data for SIMATIC PDM SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 223: Appendix
Electronic • Programmable • Target group: Manufacturers and suppliers of equipment IEC 61511 Functional safety — Safety systems for the process industry Section 1-3 Target group: Planners, constructors and users SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 224: Literature And Catalogs
Products for Totally Integrated Automation Catalog ST 80 SIMATIC Siemens AG E86060-K4680-A101-B4 HMI operation and observation products Catalog IK PI Siemens AG Internet address: Industrial Communication IK PI Catalog (http://www.automation.siemens.com/net/ html_76/support/printkatalog.htm) E86060-K6710-A101-B5 SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 225: Overview Of Hart Operating Structure
Appendix A.4 Overview of HART operating structure Overview of HART operating structure The following overview applies to the HART communicator operating structure. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 226
Appendix A.4 Overview of HART operating structure SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 227
Appendix A.4 Overview of HART operating structure SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 228: Technical Support
● Information about field service, repairs, spare parts and lots more under «Services.» Additional Support Please contact your local Siemens representative and offices if you have any questions about the products described in this manual and do not find the right answers.
-
Page 229: List Of Abbreviations
Number of faults within 10 hours Hardware Fault Tolerance Hardware fault tolerance: Capability of a function unit to continue executing a required function in the presence of faults or deviations. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 230
A safety-instrumented system (SIS) executes the safety functions that are required to achieve or maintain a safe status in a system. It consists of sensors, logic unit/control system and final controlling elements. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 231: Glossary
Failure: A resource is no longer capable of executing a required function. Fault/Error: Undesired state of a resource indicated by its incapability of executing a required function. Fault/Error Failure/Fault/Error → SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 232
Typical applications include transmitters for measuring mechanical and electrical dimensions. MAWP (PS) Maximum Allowable Working Preassure (PS) Non-volatile memory EEPROM → Risk Combination of the probability of damage occurring and the extent of the damage. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 233
The SIL which can be achieved is determined by the following safety-instrumented characteristics: ● Average probability of failure on demand (PFD ● Hardware fault tolerance (HFT) ● Safe failure fraction (SFF) srli2 srlin2 → SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 234
«srli2» is used in sections that refer to the on-site operation of the pressure transmitter. The reason for the abbreviation is that the pressure transmitter display is restricted to five characters. The abbreviation «srlin2» is used for HART operation. SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 235: Index
Fast recording of measured values, 124 Characteristic curve Fast Response Mode, 124 lin, 96 Filling liquid, 27, 29, 30 srlin, Firmware, 12 srlin2, Flange, 29, 45 sroff, 96 Full scale value Characteristics Set, 79 SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
-
Page 236
Primary variable, 99 Mass, 110, 111 MAWP, 229 Full scale value, 108 Qualified personnel, 17 Measured value display, 79, 100 Measured value status, 117 Quarternary variable, Measuring accuracy, 150 Measuring cell SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09… -
Page 237
Set, 79 Stop time, 138 Structure, 22 Support, 228 Secondary variable, Tank connection, 216 Test certificates, 15 Trimming lower trim point, upper trim point, 130 Turning range, 56 Tertiary variable, SITRANS P DS III with HART Operating Instructions, 06/2013, A5E00047092-09…
SITRANS P DS III
SITRANS
Pressure transmitter
SITRANS P DS III
Service Manual
7MF4.33.. 7MF4.34.. 7MF4.35..
06/2014
A5E34219855-01
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
DANGER indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION indicates that minor personal injury can result if proper precautions are not taken.
NOTICE indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
Order number: A5E34219855
Ⓟ 06/2014 Subject to change
Copyright © Siemens AG 2014.
All rights reserved
Table of contents
1
2
3
4
5
1.4
1.5
1.6
1.7
Introduction …………………………………………………………………………………………………………………………… 7
1.1
Purpose of this documentation ………………………………………………………………………………………… 7
1.2
1.3
Product information ………………………………………………………………………………………………………… 7
History ………………………………………………………………………………………………………………………….. 7
Checking the consignment ………………………………………………………………………………………………. 8
Purpose ………………………………………………………………………………………………………………………… 8
Checking the compatibility of the application electronics …………………………………………………….. 9
Transportation and storage ……………………………………………………………………………………………. 11
1.8
Notes on warranty ………………………………………………………………………………………………………… 12
Safety notes ………………………………………………………………………………………………………………………… 15
2.1
2.1.1
2.1.2
Precondition for use ……………………………………………………………………………………………………… 15
Laws and directives ……………………………………………………………………………………………………… 15
Conformity with European directives ………………………………………………………………………………. 15
2.2
2.3
Improper device modifications ……………………………………………………………………………………….. 15
Use in hazardous areas ………………………………………………………………………………………………… 16
Description ………………………………………………………………………………………………………………………….. 19
3.1
Structure ……………………………………………………………………………………………………………………… 19
5.3
5.4
5.5
5.6
5.7
5.7.1
5.7.2
5.7.3
3.2
3.3
Nameplate layout …………………………………………………………………………………………………………. 20
Measuring point label layout ………………………………………………………………………………………….. 21
Connecting …………………………………………………………………………………………………………………………. 23
4.1
Basic safety instructions ……………………………………………………………………………………………….. 23
4.2
Connecting the device ………………………………………………………………………………………………….. 26
Maintenance and servicing …………………………………………………………………………………………………….. 29
5.1
5.2
Basic safety instructions ……………………………………………………………………………………………….. 29
Defining the maintenance interval…………………………………………………………………………………… 32
Checking the gaskets ……………………………………………………………………………………………………. 33
Display in case of a fault ……………………………………………………………………………………………….. 34
Changing the measuring cell and application electronics …………………………………………………… 34
User data following replacement …………………………………………………………………………………….. 35
Replacing parts ……………………………………………………………………………………………………………. 40
Guarantee information ………………………………………………………………………………………………….. 40
Exploded view of the device ………………………………………………………………………………………….. 40
Replacing the connection board …………………………………………………………………………………….. 41
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
5
Table of contents
6
7
A
5.7.4
5.7.5
5.7.6
5.7.7
5.8
5.8.1
Replacing the pushbutton module …………………………………………………………………………………. 43
Replacing the display …………………………………………………………………………………………………… 45
Replacing the application electronics ……………………………………………………………………………… 47
Replacing the measuring cell ………………………………………………………………………………………… 49
Cleaning …………………………………………………………………………………………………………………….. 51
Servicing the remote seal measuring system ………………………………………………………………….. 52
5.9
5.10
Return procedure ………………………………………………………………………………………………………… 53
Disposal……………………………………………………………………………………………………………………… 54
Technical specifications ………………………………………………………………………………………………………… 55
Ordering data for spare parts/accessories ………………………………………………………………………………… 57
Appendix ……………………………………………………………………………………………………………………………. 65
A.1
Certificate …………………………………………………………………………………………………………………… 65
A.2
A.3
Technical support ………………………………………………………………………………………………………… 65
Repair report for installation of spare parts ……………………………………………………………………… 67
Glossary …………………………………………………………………………………………………………………………….. 69
Index …………………………………………………………………………………………………………………………………. 73
6
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Introduction
1.1 Purpose of this documentation
These instructions contain all information that you will require to replace the application electronics, measuring cell, and connection board of the device.
For information about the safe usage of the device, refer to the detailed version of these instructions and corresponding safety instructions on the electronic data medium.
Read these instructions carefully before you start any service and maintenance work. In order to use the device correctly, first make yourself acquainted with its principle of operation.
Readership of these instructions are service and maintenance technicians.
1
1.2 Product information
The programming manual is an integral part of the CD, which is either supplied or can be ordered. The programming manual is also available on the Siemens homepage.
On the CD, you will also find the catalog extract with the ordering data, the Software Device
Install for SIMATIC PDM for additional installation, and the required software.
See also
1.3
Product information on SITRANS P in the Internet ( http://www.siemens.com/sitransp )
Catalog process instrumentation ( http://www.siemens.com/processinstrumentation/catalogs )
History
This history establishes the correlation between the current documentation and the valid firmware of the device.
The documentation of this edition applies to the following firmware:
Edition
06/2014
Firmware identifier nameplate System integration
HART:
FW: 11.03.03, FW: 11.03.04,
FW: 11.03.05, FW: 11.03.06
PA: FW: 301.01.10
FF: FW: 11.01.01
SIMATIC PDM 8.x and previous versions
Installation path for PDM
SITRANS P DSIII.2
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
7
8
Introduction
1.4 Checking the consignment
1.4 Checking the consignment
1. Check the packaging and the spare parts for visible damage caused by inappropriate handling during shipping.
2. Report any claims for damages immediately to the shipping company.
3. Retain the damaged parts for clarification.
4. Check the scope of delivery by comparing your order with the shipping documents for correctness and completeness.
WARNING
Using damaged or incomplete spare parts
Danger of explosion in hazardous areas.
• Do not use damaged or incomplete spare parts.
1.5
Overview
Purpose
Depending on the version, a transmitter measures corrosive, non-corrosive and hazardous gases, vapors and liquids.
You can use the transmitter for the following types of measurement:
● Gauge pressure
● Absolute pressure
● Differential pressure
With appropriate parameter settings and the necessary add-on parts (e.g. flow orifices and remote seals), the pressure transmitter can also be used for the following measurements:
● Level
● Volume
● Mass
● Volume of flow
● Mass flow rate
The output signal is always a load-independent direct current between 4 and 20 mA.
You can install the «intrinsically-safe» or «explosion-proof» version of the transmitter in hazardous areas. The devices have an EC type examination certificate and comply with the appropriate harmonized European CENELEC directives.
Transmitters with remote seals of different shapes can be delivered for special applications.
For example, measuring high-viscosity substances is a special application.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
1.6
Introduction
1.6 Checking the compatibility of the application electronics
Operate the device in accordance with the «Technical specifications» chapter in the operating instructions.
For additional information, refer to the operating instructions for the device.
Checking the compatibility of the application electronics
1. The table shown below indicates whether the new application electronics matches the device.
2. Check the product version on the application electronics sticker.
3. Check the compatibility mark on the nameplate of the device.
Table 1- 1 The following table is valid for: SITRANS P DS III with HART (7MF4.33..)
Product version (ES)
007 to 025
030 to 035
Compatibility mark
K = 01
K = 01
Remark
Replacement not possible
Replacement possible
Table 1- 2 The following table is valid for:
SITRANS P DS III with PA (7MF4.34..) and SITRANS P DS III with FF (7MF4.35..)
Product version (ES)
001 to 015
Compatibility mark
K = 01
Remark
Replacement possible
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
9
Introduction
1.6 Checking the compatibility of the application electronics
Example of application electronics for
SITRANS P DS III with PA and
①
FF
Product version (ES)
Example of application electronics for
SITRANS P DS III with HART
10
①
Compatibility mark
Figure 1-1 Compatibility mark on the nameplate
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Introduction
1.7 Transportation and storage
Figure 1-2 Example of incrementing of product version and compatibility mark and their possible combinations for future developments
See also
Nameplate layout (Page 20)
1.7 Transportation and storage
To guarantee sufficient protection during transport and storage, observe the following:
● Keep the original packaging for subsequent transportation.
● Devices/replacement parts should be returned in their original packaging.
● If the original packaging is no longer available, please ensure that all shipments are sufficiently protected during transport by the replacement packaging. Siemens accepts no liability for additional costs resulting from damage in transit.
CAUTION
Insufficient protection during storage
The packaging only provides limited protection against moisture and infiltration.
•
Provide additional packaging as necessary.
Information on special conditions for storage and transportation of the device and spare parts can be found in the «Technical specifications» chapter in the operating instructions.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
11
Introduction
1.8 Notes on warranty
1.8 Notes on warranty
The contents of this manual shall not become part of or modify any prior or existing agreement, commitment or legal relationship. The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
12
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Introduction
1.8 Notes on warranty
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
13
Safety notes
2
2.1
2.1.1
Precondition for use
2.1.2
Laws and directives
Observe the test certification, provisions and laws applicable in your country during connection, assembly and operation. These include, for example:
● National Electrical Code (NEC — NFPA 70) (USA)
● Canadian Electrical Code (CEC) (Canada)
Further provisions for hazardous area applications are for example:
● IEC 60079-14 (international)
● EN 60079-14 (EC)
Conformity with European directives
The device complies with the European directives even following the use of replacement parts.
2.2 Improper device modifications
WARNING
Improper device modifications
Danger to personnel, system and environment can result from modifications to the device, particularly in hazardous areas.
•
Only carry out modifications that are described in the instructions for the device. Failure to observe this requirement cancels the manufacturer’s warranty and the product approvals.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
15
Safety notes
2.3 Use in hazardous areas
2.3 Use in hazardous areas
Qualified personnel for hazardous area applications
Persons who install, connect, commission, operate, and service the device in a hazardous area must have the following specific qualifications:
● They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures, aggressive, and hazardous media.
● They are authorized, trained, or instructed in carrying out work on electrical circuits for hazardous systems.
● They are trained or instructed in maintenance and use of appropriate safety equipment according to the pertinent safety regulations.
WARNING
Loss of the safety of the device with type of protection «Intrinsic safety Ex i»
If the device has already been operated in non-intrinsically safe circuits or the information on the electrical specifications have been ignored, the safety of the device is no longer ensured for use in hazardous areas. There is a danger of explosion.
•
Connect the device in Intrinsic Safety type of protection solely to an intrinsically safe circuit.
•
Observe the information on the electrical specifications in the certificate and in the
«Technical specifications» chapter in the operating instructions.
WARNING
Use of incorrect device parts in potentially explosive environments
Devices and their associated device parts are either approved for different types of protection or they do not have explosion protection. There is a danger of explosion if device parts (such as covers) are used for devices with explosion protection that are not expressly suited for this type of protection. If you do not adhere to these guidelines, the test certificates and the manufacturer warranty will become null and void.
•
Use only device parts that have been approved for the respective type of protection in the potentially explosive environment. Covers that are not suited for the «explosionproof» type of protection are identified as such by a notice label attached to the inside of the cover with «Not Ex d Not SIL».
• Do not swap device parts unless the manufacturer specifically ensures compatibility of these parts.
16
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Safety notes
2.3 Use in hazardous areas
WARNING
Risk of explosion due to electrostatic charge
To prevent the build-up of an electrostatic charge in a hazardous area, the key cover must be closed during operation and the screws tightened.
The key cover may be opened temporarily at any time for the purposes of operating the pressure transmitter, even during plant operation; the screws should then be tightened again.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
17
Safety notes
2.3 Use in hazardous areas
18
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Description
3.1 Structure
Depending on a customer-specific order, the device comprises different parts.
3
①
②
③
④
Key cover
Cover (front), optionally with inspection window
Display (optional)
Measuring point label
⑤
Retaining screw; twist proofing of the measuring cell in relation to the electronics enclosure
⑥
Process connection
⑦
Nameplate (general information)
Figure 3-1 View of the transmitter: Left: Front right: Rear view
⑧
Cable inlet, optionally with cable gland
⑨
Cover (rear) for electrical terminal compartment
⑩
Electrical terminal compartment
⑪
Protective conductor connector/equipotential bonding terminal
⑫
Nameplate (approval information)
⑬
Blanking plug
● The electronics enclosure is made of die cast aluminum or precision cast stainless steel.
● The housing has a removable circular cover at the front and the back.
● Depending on the device version, the front cover inspection window.
②
may be designed as an inspection window. You can read the measured values straight off the digital display through this
● The cable inlet
⑧
to the electrical terminal compartment is at the side; either the left or right-hand one can be used. The unused opening is closed with a blanking plug
⑬
.
● The protective conductor terminal/equipotential bonding terminal of the enclosure.
⑪
is located at the back
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
19
Description
3.2 Nameplate layout
● The electrical terminal compartment when you remove the back cover
⑩
for the auxiliary power and shield is accessible
⑨
.
● The measuring cell with a process connection
⑥
is located in the lower section of the enclosure. This measuring cell is secured against twisting by a retaining screw
⑤
.
Thanks to the modular design of the transmitter, the measuring cell and application electronics or connection board can be replaced if required.
● On the upper face of the enclosure you can see crosshead screws which secure the key cover
①
, under which there are 3 keys for local operation.
3.2 Nameplate layout
Nameplate with general information
The nameplate bearing the Order No. and other important information, such as design details and technical data, is on the side of the enclosure.
20
①
Order number (machine-readable product code)
Figure 3-2 Example of a nameplate
②
Serial number
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Description
3.3 Measuring point label layout
Nameplate with approval information
On the opposite side is the nameplate with approval information. This nameplate shows e.g. the hardware and firmware versions. You must also observe the information in the relevant certificate for a transmitter version for use in hazardous areas.
3.3
①
Characteristics for hazardous area
②
Category for operating area
③
Type of protection
④
Group (gas, dust)
Figure 3-3 Example of a nameplate
Measuring point label layout
⑤
Maximum surface temperature
(temperature class)
⑥
Device protection level
⑦
Firmware identifier
⑧
Hardware identifier
Figure 3-4 Example of measuring point label
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
21
Description
3.3 Measuring point label layout
22
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Connecting
4
4.1 Basic safety instructions
WARNING
Unsuitable cables and/or cable glands
Danger of explosion in hazardous areas.
•
Only use appropriate cables and cable glands complying with the requirements specified in the «Technical specifications» chapter in the operating instructions.
• Tighten the cable glands in accordance with the torques specified in the «Technical specifications» chapter in the operating instructions.
•
When replacing cable glands, only use ones of the same type.
• After installation check that the cables are seated firmly.
WARNING
Hazardous contact voltage in versions with 4-conductor extension
Danger of electrocution in case of incorrect connection.
• Observe the instructions in the 4-conductor extension operating manual for the electrical connection.
WARNING
Improper power supply
Danger of explosion in hazardous areas as result of incorrect power supply, e.g. using direct current instead of alternating current.
• Connect the device in accordance with the specified power supply and signal circuits.
The relevant specifications can be found in the certificates, in the «Technical specifications» chapter in the operating instructions, or on the nameplate.
WARNING
Unsafe extra-low voltage
Danger of explosion in hazardous areas due to voltage flashover.
• Connect the device to an extra-low voltage with safe isolation (SELV).
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
23
Connecting
4.1 Basic safety instructions
WARNING
Lack of equipotential bonding
Danger of explosion through compensating currents or ignition currents through lack of equipotential bonding.
•
Ensure that the device is potentially equalized.
Exception: It may be permissible to omit connection of the equipotential bonding for devices with type of protection «Intrinsic safety Ex i».
WARNING
Unprotected cable ends
Danger of explosion through unprotected cable ends in hazardous areas.
•
Protect unused cable ends in accordance with IEC/EN 60079-14.
WARNING
Improper laying of shielded cables
Danger of explosion through compensating currents between hazardous area and the nonhazardous area.
•
Only ground shielded cables that run into the hazardous area at one end.
• If grounding is required at both ends, use an equipotential bonding conductor.
WARNING
Connecting device in energized state
Danger of explosion in hazardous areas.
• Connect devices in hazardous areas only in a de-energized state.
Exceptions:
•
Circuits of limited energy may also be connected in the energized state in hazardous areas.
• Exceptions for type of protection «Non-sparking nA» (Zone 2) are regulated in the relevant certificate
24
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Connecting
4.1 Basic safety instructions
WARNING
Incorrect selection of type of protection
Danger of explosion in areas subject to explosion hazard.
This device is approved for several types of protection.
1. Decide in favor of one type of protection.
2. Connect the device in accordance with the selected type of protection.
3. In order to avoid incorrect use at a later point, make the types of protection that are not used permanently unrecognizable on the nameplate.
NOTICE
Ambient temperature too high
Damage to cable sheath.
•
At an ambient temperature ≥ 60 °C (140 °F), use heat-resistant cables suitable for an ambient temperature at least 20 °C (68 °F) higher.
NOTICE
Incorrect measured values with incorrect grounding
The device must not be grounded via the «+» connection. It may otherwise malfunction and be permanently damaged.
•
If necessary, ground the device using the «-» connection.
Note
Electromagnetic compatibility (EMC)
You can use this device in industrial environments, households and small businesses.
For metal housings there is an increased electromagnetic compatibility compared to highfrequency radiation. This protection can be increased by grounding the housing, see Chapter
«Connecting the device (Page 26)».
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
25
Connecting
4.2 Connecting the device
Note
Improvement of interference immunity
•
Lay signal cables separate from cables with voltages > 60 V.
•
Use cables with twisted wires.
•
Keep the device and the cables at a distance from strong electromagnetic fields.
•
Use shielded cables to guarantee the full specification according to HART.
•
Refer to the information on HART communication in the «Technical specifications» chapter in the operating instructions.
4.2 Connecting the device
Opening the device
1. Unscrew the cover of the electrical cable compartment. An identification text «FIELD
TERMINALS» is provided at the side of the housing.
Connecting the device
1. Lead the connecting cable through the cable gland
③
.
2. Connect the device to the plant with the protective conductor connection
⑦
.
3. Connect the wires to the connecting terminals
④
«+» and «-«.
Ensure the correct polarity! If necessary, ground the device using the «-» connection by connecting the «-» connection to the ground terminal
⑨
.
4. If necessary, connect the shield to the screw of the ground terminal connected with the external protective conductor connection.
⑨
. This is electrically
26
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
HART
Connecting
4.2 Connecting the device
PROFIBUS PA / Foundation™ Fieldbus FF
①
Feed separator with integrated load
⑥
Safety catch
②
Auxiliary power
⑦
Protective conductor connection/ equipotential bonding terminal
⑧
Process connection
③
Cable entry for auxiliary power/analog output
④
Connecting terminals
⑤
Test connector for direct current measuring device or connection for external display
⑨
Ground terminal
⑩
PROFIBUS PA / Foundation™ Fieldbus
FF
Electrical connection, power supply
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
27
Connecting
4.2 Connecting the device
Closing the device
1. Screw the covers
④⑦
back on as far as they will go.
2. Secure each cover with the cover catch
③⑥
.
3. Close the key cover
①
.
4. Tighten the screws in the key cover.
5. Check the tightness of the blanking plugs degree of protection.
⑤
and cable gland
②
in accordance with the
①
Key cover
②
Cable gland
③
Safety catch (back)
④
Cover (rear) for electrical terminal compartment
Figure 4-1 View of the transmitter: Left: Back right: Front view
⑤
Blanking plug
⑥
Safety catch (front)
⑦
Cover (front), optionally with inspection window
⑧
Safety catch for stainless steel enclosure
28
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5
5.1 Basic safety instructions
WARNING
Impermissible repair of explosion protected devices
Danger of explosion in areas subject to explosion hazard.
•
Repair must be carried out by Siemens authorized personnel only.
WARNING
Impermissible accessories and spare parts
Danger of explosion in areas subject to explosion hazard.
•
Only use original accessories or original spare parts.
• Observe all relevant installation and safety instructions described in the instructions for the device or enclosed with the accessory or spare part.
WARNING
Use of incorrect device parts in potentially explosive environments
Devices and their associated device parts are either approved for different types of protection or they do not have explosion protection. There is a danger of explosion if device parts (such as covers) are used for devices with explosion protection that are not expressly suited for this type of protection. If you do not adhere to these guidelines, the test certificates and the manufacturer warranty will become null and void.
• Use only device parts that have been approved for the respective type of protection in the potentially explosive environment. Covers that are not suited for the «explosionproof» type of protection are identified as such by a notice label attached to the inside of the cover with «Not Ex d Not SIL».
•
Do not swap device parts unless the manufacturer specifically ensures compatibility of these parts.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
29
Maintenance and servicing
5.1 Basic safety instructions
WARNING
Maintenance during continued operation in a hazardous area
There is a danger of explosion when carrying out repairs and maintenance on the device in a hazardous area.
•
Isolate the device from power.
— or —
•
Ensure that the atmosphere is explosion-free (hot work permit).
WARNING
Commissioning and operation with pending error
If an error message appears, correct operation in the process is no longer guaranteed.
•
Check the gravity of the error.
• Correct the error.
•
If the error still exists:
– Take the device out of operation.
– Prevent renewed commissioning.
WARNING
Hot, toxic or corrosive process media
Danger of injury during maintenance work.
When working on the process connection, hot, toxic or corrosive process media could be released.
•
As long as the device is under pressure, do not loosen process connections and do not remove any parts that are pressurized.
•
Before opening or removing the device ensure that process media cannot be released.
WARNING
Improper connection after maintenance
Danger of explosion in areas subject to explosion hazard.
•
Connect the device correctly after maintenance.
• Close the device after maintenance work.
Refer to Chapter «Connecting the device (Page 26)».
30
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.1 Basic safety instructions
WARNING
Use of a computer in a hazardous area
If the interface to the computer is used in the hazardous area, there is a danger of explosion.
•
Ensure that the atmosphere is explosion-free (hot work permit).
CAUTION
Releasing key lock
Improper modification of parameters could influence process safety.
•
Make sure that only authorized personnel may cancel the key locking of devices for safety-related applications.
CAUTION
Hot surfaces
Danger of burns during maintenance work on parts having surface temperatures exceeding
70 °C (158 °F).
• Take corresponding protective measures, for example by wearing protective gloves.
•
After carrying out maintenance, remount touch protection measures.
WARNING
Hazardous voltage with open device in versions with 4-conductor extension
Danger of electrocution when the enclosure is opened or enclosure parts are removed.
•
Disconnect the device before you open the enclosure or remove enclosure parts.
• Observe the special precautionary measures if maintenance is required while the device is live. Have maintenance work carried out by qualified personnel.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
31
Maintenance and servicing
5.2 Defining the maintenance interval
NOTICE
Electrostatic-sensitive devices
The device contains electrostatic-sensitive devices (ESD). ESD can be destroyed by voltages far too low to be detected by humans. These voltages can occur if you simply touch a component part or the electrical connections of a module without being electrostatically discharged. The damage to a module caused by overvoltage cannot normally be detected immediately; it only becomes apparent after a longer period of operating time has elapsed.
Protective measures against the discharge of static electricity:
•
Make sure that no power is applied.
•
Before working with modules, make sure that you discharge static from your body, for example by touching a grounded object.
•
Devices and tools used must be free of static charge.
•
Hold modules only by their edges.
•
Do not touch connector pins or conductor tracks on a module with the ESD notice.
5.2 Defining the maintenance interval
WARNING
No maintenance interval has been defined
Device failure, device damage, and risk of injury.
•
Define a maintenance interval for regular tests in line with device use and empirical values.
•
The maintenance interval will vary from site to site depending on corrosion resistance.
32
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.3 Checking the gaskets
5.3 Checking the gaskets
Inspect the seals at regular intervals
Note
Incorrect seal changes
Incorrect measured values will be displayed. Changing the seals in a process flange of a differential pressure measuring cell can alter the start-of-scale value.
• Changing seals in devices with differential pressure measuring cells may only be carried out by personnel authorized by Siemens.
Note
Using the wrong seals
Using the wrong seals with flush-mounted process connections can cause measuring errors and/or damage the diaphragm.
• Always use seals which comply with the process connection standards or are recommended by Siemens.
1. Clean the enclosure and seals.
2. Check the enclosure and seals for cracks and damage.
3. Grease the seals if necessary.
— or —
4. Replace the seals.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
33
Maintenance and servicing
5.4 Display in case of a fault
5.4 Display in case of a fault
Check the start of scale value of the device from time to time.
Differentiate between the following in case of a fault:
● The internal self test has detected a fault, e.g. sensor break, hardware fault/Firmware fault.
Displays:
– Display: «ERROR» display and ticker with an error text
– Analog output: Factory setting: Failure current 3.6 or 22.8 mA
Or depending on the parameterization
– HART: detailed error breakdown for display in the HART communicator or SIMATIC
PDM
● Grave hardware faults, the processor is not functioning.
Displays:
– Display: no defined display
– Analog output: failure current < 3.6 mA
In the event of a defect, you can replace the application electronics by following the warning notes and the provided operating instructions.
5.5
Related
Changing the measuring cell and application electronics
34
Each of the individual components «Measuring cell» and «Electronics» has a non-volatile memory (EEPROM).
Measuring cell data (e.g.: measuring range, measuring cell material, oil filling) and user data of the application electronics (e.g.: downscaling, additional electrical damping) are located in the measuring cell EEPROM. User data is lost when the measuring cell is replaced.
Application-specific data are not lost when the application electronics are changed.
You can backup user data before changing the measuring cell and reload it afterwards. Use an input device which supports the HART protocol. (e.g. HART communicator, PC with
HART modem and HART software or PC with HART modem and PDM software). Factory settings will be used if user data is not backed up before the measuring cell is changed.
Technical developments enable advanced functions to be implemented in the firmware of the measuring cell or application electronics. Further technical developments are indicated by modified firmware statuses (FW). The firmware status does not affect whether the modules can be replaced. However, the scope of functions is limited to the function of existing components.
If a combination of certain firmware versions of measuring cell and application electronics is not possible for technical reasons, the device will identify this problem and go into «Fault current» mode. This information is provided via the HART interface.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.6 User data following replacement
5.6 User data following replacement
This chapter describes which user data is reset to the factory setting following replacement of the application electronics or measuring cell.
The following tables are identified as follows:
*: The parameter names identified by * can be found in SIMATIC PDM under the menu items
«Device» or «View».
①
: The user data identified by
①
is reset to the factory setting following replacement of the measuring cell.
②
: The user data identified by
②
is reset to the factory setting following replacement of the application electronics.
Table 5- 1 SITRANS P DS III with HART
Parameter name in SIMATIC PDM
Operating unit / TAG
Device / sensor serial number
Unit and cycle time / unit
Unit and cycle time / cycle time
Measuring limits / min. measuring range
Measuring limits / min. start-of-scale value, max. full-scale value
Measured-value scaling, start-of-scale value
Measured-value scaling, full-scale value
Analog output limits / lower/upper limit
Alarm status / analog output alarm type
Alarm status / lower/upper alarm value
Damping
Characteristic / transfer function
Characteristic / start of root extraction
Display and user interface / tracking unit
Design (all material data)
Sensor calibration / upper/lower calibration point
Sensor calibration / lower calibration point
Sensor calibration / upper calibration point
Service interval for sensor (all settings)
Status of user data following replacement of application electronics or measuring cell
①
①
①
①
①
①
①
①
①
①
①
①
①
①
①
①
①
①
①
①
Value following resetting to factory setting
—
—
—
— bar
90 ms
0.0
Upper sensor limit
3.8 / 20.5 mA
Lower
3.6 / 22.8 mA
0.1 s
Linear
5 % mA
—
Like factory-set sensor limits, without transformation
0.0
Upper sensor limit
—
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
35
Maintenance and servicing
5.6 User data following replacement
Parameter name in SIMATIC PDM
Certificates and approvals / explosion protection
* Polling address
* Min/max pointers for pressure / sensor temperature
* Sensor calibration / zero calibration
* Sensor calibration / upper/lower calibration
* Position error calibration
* Operating hours counter, sensor
Operating unit / message
Operating unit / description
Device / software revision
Device / hardware revision
Device / field device revision
Device / date
Device / factory number
Display and user interface / local display unit
Display and user interface / bargraph
Display and user interface / local operation
Calibration interval for application electronics
(all settings)
Current saturation monitoring / alarm activation
Current saturation monitoring / saturation alarm, alarm duration
* Operating hours counter, application electronics
* Analog output D/A calibration (customerspecific)
* Min/max pointers for application electronics temperature
Status of user data following replacement of application electronics or measuring cell
①
①
①
②
②
②
②
②
②
②
②
②
②
①
①
①
①
②
②
②
②
②
②
Table 5- 2 SITRANS P DS III with PA
Parameter name in SIMATIC PDM
Identification / device / sensor type
Identification / device / sensor serial number
Status of user data following replacement of application electronics or measuring cell
①
①
Value following resetting to factory setting
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.0
—
—
—
—
—
Like factory-set D/A calibration
—
36
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.6 User data following replacement
Parameter name in SIMATIC PDM
Input / transducer block 1 / measuring limits / min. start-of-scale value
Input / transducer block 1 / measuring limits / max. full-scale value
Conditions of use / process conditions / max. media pressure limit
Diagnostics settings / service interval for sensor (all settings)
Design / type / measuring cell / measuring cell filling
Design / type / measuring cell / seal diaphragm material
Design / type / measuring cell / O-ring material
Design / type / remote seal / number of remote seal flanges
Design / type / remote seal / remote seal type
Design / type / remote seal / diaphragm material
Design / type / remote seal / remote seal filling
Status of user data following replacement of application electronics or measuring cell
①
①
①
①
①
①
①
①
①
①
Design / type / remote seal / tube length
①
①
①
Design / type / process connection / process connection type
Design / type / process connection / venting valve material
Design / type / process connection / venting valve position
Design / type / process connection / process flange screws
Design / type / process connection / flange type
Design / type / process connection / flange material
Design / electrical connection / electronics housing material
Design / electrical connection / electrical connection
Certificates and approvals / explosion protection
* Operating hours counter, sensor
* Min/max pointers for pressure / sensor temperature
Identification / operating unit / TAG
Identification / operating unit / description
①
①
①
①
①
①
①
①
①
①
②
②
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
37
Maintenance and servicing
5.6 User data following replacement
Parameter name in SIMATIC PDM
Identification / operating unit / message
Identification / device / device serial number
Identification / device / software revision
Identification / device / hardware revision
Identification / device / PROFIBUS Ident
Number
Identification / device / installation date
Identification / device / Order No.
Input / transducer block 1 / transducer type
Input / transducer block 1 / measuring limits / pressure unit, raw value
Input / transducer block 1 / measuring range / unit (secondary variable 1)
Input / transducer block 1 / measuring range / start-of-scale value
Input / transducer block 1 / measuring range / full-scale value
Input / transducer block 1 / working range / unit
Input / transducer block 1 / working range / start-of-scale value
Input / transducer block 1 / working range / full-scale value
Input / transducer block 1 / characteristic / low-flow cut-off
Input / transducer block 1 / characteristic / start of root function
Input / transducer block 1 / interpolation points
(all settings)
Input / transducer block 1 / sensor temperature / temperature unit
Output / Function Block 1 — analog input (all settings)
Output / Function Block 2 — totalizer (all settings)
Display and user interface / local operation
Display and user interface / source for display
Display and user interface / decimal places in display
Diagnostics settings / enabling of diagnostics
Diagnostics settings / calibration interval for application electronics (all settings)
Status of user data following replacement of application electronics or measuring cell
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
②
38
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.6 User data following replacement
Parameter name in SIMATIC PDM
* Sensor calibration
* Position error calibration
* Write block
* Operating hours counter, application electronics
* Min/max pointers for electronics temperature
Status of user data following replacement of application electronics or measuring cell
②
②
②
②
②
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
39
Maintenance and servicing
5.7 Replacing parts
5.7 Replacing parts
5.7.1 Guarantee information
Following replacement of a part, a guarantee is only valid for the individual components and not for the complete device.
5.7.2 Exploded view of the device
Depending on a customer-specific order, the device comprises different parts. The next chapters show you how to replace the components.
40
1
4
5
2
3
6
7
Cover (front), optionally with inspection window
O-ring between the cover and housing
Display (optional)
Threaded bolts
Application electronics
Measuring cell PCB
Housing
Figure 5-1 Exploded view of the transmitter
8
9
Cover (rear) for electronic terminal compartment
Connection for digital display
10 Measuring cell
11 Connection board
12 Keyboard PCB
13 Mounting screws
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
5.7.3 Replacing the connection board
Procedure for replacing the connection board
1. Isolate the device from power.
2. Use a 3 mm Allen key to loosen the cover.
3. Open the cover (rear) of the electronic connection compartment.
Maintenance and servicing
5.7 Replacing parts
4. Disconnect the cables from the connection board.
5. On the left and right side, remove the recessed-head screws that hold the connection board to the enclosure.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
41
Maintenance and servicing
5.7 Replacing parts
6. Make sure when loosening the recessed-head screws that the washers (serrated washers) are not lost.
7. Remove the connection board.
42
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.7 Replacing parts
To install the connection board, proceed as follows
1. Insert the new connection board so that its contact pins on rear side mate the contacts in the housing.
5.7.4
2. Work in the reverse order as described in «Procedure for replacing the connection board».
3. Close the device as described in Chapter Closing the device (Page 26).
Replacing the pushbutton module
1. Isolate the device from power.
2. In order to open the pushbutton flap, loosen the two recessed-head screws on the outside.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
43
Maintenance and servicing
5.7 Replacing parts
3. Remove the two splints on the pushbutton flap using flat-nose pliers.
4. Remove the pushbutton flap.
5. Use a TX10 Torx screwdriver or Phillips screwdriver to loosen the two screws of the pushbutton insert you can now see.
6. Remove the pushbutton insert from the housing.
7. Remove the three keys with springs from the pushbutton insert.
Procedure for installing the pushbutton module
1. Work in the reverse order as described in «Procedure for replacing the pushbutton module».
2. When inserting the new pushbutton module, make sure that the magnets of the keys point to the front in the direction of the display.
44
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.7 Replacing parts
5.7.5 Replacing the display
Procedure for replacing the display
1. Open the front cover (optional with inspection window).
2. Remove the recessed-head screws on the left and right on the display.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
45
Maintenance and servicing
5.7 Replacing parts
3. Pull the display out of the housing.
4. Remove the connector of the ribbon cable from the application electronics.
Procedure for installing the display
1. You can also turn the mounting position of the display by 90 ° or 180 °.
2. Work in the reverse order as described in «Procedure for replacing the display».
3. Close the device as described in Chapter Closing the device (Page 26).
46
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.7 Replacing parts
5.7.6 Replacing the application electronics
Procedure for replacing the application electronics
1. Isolate the device from power.
2. Remove the display. Compare section Replacing the display (Page 45).
3. Use a 7 mm socket wrench to remove the hexagon stud bolts on the left and right.
4. Remove the application electronics.
5. Remove the measuring cell PCB from the application electronics. To do this, carefully release the clip using a screwdriver as shown in the following picture.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
47
Maintenance and servicing
5.7 Replacing parts
6. Use a TX9 Torx screwdriver or Phillips screwdriver to unscrew the two screws of the keyboard PCB you can now see from the base of the housing.
7. Remove the keyboard PCB.
Procedure for installing the application electronics
NOTICE
Frequent insertion of the measuring cell PCB
Device damage.
•
Avoid frequent insertion of the measuring cell PCB.
1. Work in the reverse order as described in «Procedure for replacing the application electronics».
2. When inserting the new application electronics, make sure that the contact pins fit in the rear of the application electronics.
The ribbon cable of the measuring cell should be positioned between the contact pins, and that of the keyboard PCB on the left of the pins.
3. Do not kink, pinch, tension or twist the ribbon cable when plugging it onto the application electronics.
4. Close the device as described in Chapter Closing the device (Page 26).
5. Following a replacement, permanently obliterate the firmware ID on the nameplate if applicable.
6. Write the new firmware ID on the nameplate.
7. Calibrate the zero point of the device, and also the span if necessary. Calibration of the span is necessary if the device was matched e.g. to a control system prior to replacement
of the application electronics. Compare section Technical specifications (Page 55).
48
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.7 Replacing parts
5.7.7 Replacing the measuring cell
Procedure for replacing the measuring cell
Note
When using the differential pressure cell, replace the complete measuring cell with process flanges.
1. Isolate the device from power.
2. Remove the display. Compare section Replacing the display (Page 45).
3. Remove the application electronics. Compare section Replacing the application electronics (Page 47).
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
49
Maintenance and servicing
5.7 Replacing parts
4. Use a 2.5 mm Allen key to loosen the locking screw for fixing the measuring cell.
NOTICE
Damage to the ribbon cable
To avoid damage to the ribbon cable when installing or removing the measuring cell, do not kink, pinch, tension or twist it.
•
Do not kink, pinch, tension or twist the ribbon cable.
5. Turn the measuring cell counter-clockwise to remove it from the housing. To do this, use a matching open-end wrench (relative pressure transmitter) or rotate the measuring cell by hand.
50
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.8 Cleaning
Procedure for installing the measuring cell
1. Clean residues off the thread of the housing.
2. Push the measuring cell PCB through the threaded hole.
3. Turn the measuring cell into the housing until an overhang of 2.6 mm ± 0.75 remains.
The ribbon cable must be present as a loop between the two feed-through pins, and must follow every rotation of the cell.
Make sure that the mounting flange is correctly orientated on the differential pressure cell.
The arrow
②
must remain visible within the marked area
①
.
4. Work from here on in the reverse order as described in «Procedure for replacing the measuring cell».
5. Close the device as described in Chapter Closing the device (Page 26).
6. Following a replacement, permanently obliterate the hardware ID on the nameplate if applicable.
7. Write the new hardware ID on the nameplate.
8. Following replacement of the measuring cell, carry out an insulation test between the short-circuited input terminals and the protective earth connection. The insulation resistance should have a value greater than 10 MOhm.
5.8 Cleaning
WARNING
Dust layers above 5 mm
Danger of explosion in hazardous areas. Device may overheat due to dust build up.
•
Remove dust layers in excess of 5 mm.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
51
Maintenance and servicing
5.8 Cleaning
NOTICE
Penetration of moisture into the device
Device damage.
•
Make sure when carrying out cleaning and maintenance work that no moisture penetrates the inside of the device.
Cleaning the enclosure
● Clean the outside of the enclosure and the display window using a cloth moistened with water or a mild detergent.
● Do not use aggressive cleaning agents or solvents. Plastic components or painted surfaces could be damaged.
WARNING
Electrostatic charge
Danger of explosion in hazardous areas if electrostatic charges develop, for example, when cleaning plastic enclosures with a dry cloth.
•
Prevent electrostatic charging in hazardous areas.
5.8.1 Servicing the remote seal measuring system
The remote seal measuring system usually does not need servicing.
If the mediums are contaminated, viscous or crystallized, it could be necessary to clean the diaphragm from time to time. Use only a suitable solvent to remove the deposits from the diaphragm. Do not use corrosive cleaning agents. Prevent the diaphragm from getting damaged due to sharp-edged tools.
NOTICE
Improper cleaning of diaphragm
Device damage. The diaphragm can be damaged.
• Do not use sharp or hard objects to clean the diaphragm.
52
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Maintenance and servicing
5.9 Return procedure
5.9 Return procedure
Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the outside of the packaging.
Required forms
● Delivery note
● Return goods delivery note
( http://www.siemens.com/processinstrumentation/returngoodsnote ) with the following information:
– Product (item description)
– Number of returned devices/replacement parts
– Reason for returning the item(s)
● Decontamination declaration ( http://www.siemens.com/sc/declarationofdecontamination )
With this declaration you warrant «that the device/replacement part has been carefully cleaned and is free of residues. The device/replacement part does not pose a hazard for humans and the environment.»
If the returned device/replacement part has come into contact with poisonous, corrosive, flammable or water-contaminating substances, you must thoroughly clean and decontaminate the device/replacement part before returning it in order to ensure that all hollow areas are free from hazardous substances. Check the item after it has been cleaned.
Any devices/replacement parts returned without a decontamination declaration will be cleaned at your expense before further processing.
The forms can be found on the Internet as well as in the documentation which comes with the device.
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
53
Maintenance and servicing
5.10 Disposal
5.10 Disposal
Devices identified by this symbol may not be disposed of in the municipal waste disposal services under observance of the
Directive 2002/96/EC on waste electronic and electrical equipment (WEEE).
They can be returned to the supplier within the EC or to a locally approved disposal service. Observe the specific regulations valid in your country.
Note
Special disposal required
The device includes components that require special disposal.
•
Dispose of the device properly and environmentally through a local waste disposal contractor.
54
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Technical specifications
This chapter describes the deviations from the technical specifications in the operating instructions.
Deviations exist as follows in the measuring accuracy following replacement of the application electronics or measuring cell:
Table 6- 1 Technical specifications > measuring accuracy
SITRANS P DS III with HART No calibration of zero and span Calibration of zero and span
Measurement deviation with limit setting, including hysteresis and repeatability
Linear characteristic curve
• r ≤ 10
Value doubled Value remains unchanged
Effect of ambient temperature
• At -10 … +60 °C (14 … 140
°F)
Value doubled
r = maximum measuring span/set measuring span
Value doubled
6
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
55
Technical specifications
56
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Ordering data for spare parts/accessories
7
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
57
Ordering data for spare parts/accessories
58
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Ordering data for spare parts/accessories
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
59
Ordering data for spare parts/accessories
60
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Ordering data for spare parts/accessories
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
61
Ordering data for spare parts/accessories
See also
Process instrumentation catalog ( http://www.siemens.com/processinstrumentation/catalogs )
62
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Ordering data for spare parts/accessories
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
63
Appendix
A
A.1 Certificate
The certificates can be found on the enclosed CD and on the Internet under:
Certificates ( http://www.siemens.com/processinstrumentation/certificates )
A.2 Technical support
Technical Support
You can contact Technical Support for all IA and DT products:
● Via the Internet using the Support Request:
Support request ( http://www.siemens.com/automation/support-request )
● E-mail ( mailto:[email protected]
)
● Phone: +49 (0) 911 895 7 222
● Fax: +49 (0) 911 895 7 223
Further information about our technical support is available on the Internet at
Technical Support ( http://www.siemens.com/automation/csi/service )
Industry Online Support
In addition to our documentation, we offer a comprehensive knowledge base on the Internet at:
Services & Support ( http://www.siemens.com/automation/service&support )
There you will find:
● The latest product information, FAQs, downloads, tips and tricks.
● Our newsletter with the latest information about our products.
● A Knowledge Manager to find the right documents for you.
● Our bulletin board, where users and specialists share their knowledge worldwide.
● Your local contact partner for Industry Automation and Drives Technologies in our partner database.
● Information about field service, repairs, spare parts and lots more under «Services.»
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
65
Appendix
A.2 Technical support
Additional Support
Please contact your local Siemens representative and offices if you have any questions about the products described in this manual and do not find the right answers.
Find your contact partner at:
Partner ( http://www.automation.siemens.com/partner )
Documentation for various products and systems is available at:
Instructions and manuals ( http://www.siemens.com/processinstrumentation/documentation )
See also
Product information on SITRANS P in the Internet ( http://www.siemens.com/sitransp )
Process instrumentation catalog ( http://www.siemens.com/processinstrumentation/catalogs )
66
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Appendix
A.3 Repair report for installation of spare parts
A.3 Repair report for installation of spare parts
For your local documentation
Check mark the relevant items and fill out the fields
1. Customer information:
Company:
Address:
Department:
Tel / Fax:
E-mail:
System part:
2. Information on the original device: first replacement of a component ⃞
Electronic serial number:
Sensor serial number:
F-no.: (rating plate)
HW: Approval plate)
FW: (approval plate)
Device order no.:
Additional components
7MF4 _ _ _ _ — _ _ _ _ _ — _ _ _ _ — Z _ _ _
— Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _
3a. Device information Spare Part(1): Measuring cell
Sensor serial number:
Spare part order no.:
Additional components
7MF499 _ — _ _ _ _ _ _ — Z _ _ _
— Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _ — Z _ _ _
3b. Device information Spare Part(2): Application electronics
Electronic serial number:
ES: (electronic cup)
FW: (electronic cup)
Spare part order no.: 7MF4999 — _ _ _ _ _ — _ _ _ _
3c. Device information Spare Part(3): Connection board
HW: (connection board)
Spare part order no.: 7MF4999 — _ _ _ _ _ — _ _ _ _
3d. Device information Spare Part(4): Pushbutton module
HW: (connection board)
Spare part order no.: 7MF4999 — _ _ _ _ _ — _ _ _ _
3e. Device information Spare Part(5): Display
HW: (connection board)
Spare part order no.: 7MF4999 — _ _ _ _ _ — _ _ _ _
3f. Device information Spare Part(6): Additional spare parts
HW: (connection board)
Spare part order no.:
4. Additional information
Installation location (precise definition)
7MF4999 — _ _ _ _ _ — _ _ _ _
67
Appendix
A.3 Repair report for installation of spare parts
For your local documentation
Repair period:
Safety measures:
Work completed:
5. Approval
Check mark the relevant items and fill out the fields
Replacement documentation was read and observed: ⃞
ESD guidelines were observed: ⃞
Inspected by Ex expert: ⃞
Function test completed: ⃞
Name of Ex expert:
Signature of Ex expert:
Author name:
Author signature:
From:
To:
Date:
Date:
68
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Glossary
ATEX
ATEX is an abbreviation of the French term «Atmosphère explosible» (potentially explosive atmosphere). ATEX stands for both EC directives in the area of explosion protection: ATEX product directive 94/9/EC and ATEX operating directive 1999/92/EC.
Auxiliary power supply
Auxiliary power supply refers to an electrical supply or reference voltage which some electrical circuits require apart from the standard supply. The auxiliary power supply can, for example, be specially stabilized, have a particular level or polarity and/or other properties which are important for the correct functioning of switch components.
Auxiliary voltage
→ Auxiliary power supply
Dangerous failure
Failure with the potential to switch a safety-instrumented system to a hazardous or nonfunctioning safety state.
EEPROM
Failure/Fault/Error
Failure:
A resource is no longer capable of executing a required function.
Fault/Error:
Undesired state of a resource indicated by its incapability of executing a required function.
Fault/Error
EEPROM (Electrically Erasable Programmable Read-Only Memory): a non-volatile, electronic memory module.
EEPROMs are often used where individual bytes of data (e.g. configuration data or runtime meters) change over time and must be stored safely in the event of a mains power failure.
→ Failure/Fault/Error
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
69
Glossary
Final controlling element
Converter that converts electrical signals into mechanical or other non-electric variables.
Firmware
Firmware (FW) is software that is embedded on a chip in electronic devices – in contrast to software which is saved on hard disks, CD-ROMs or other media. These days, firmware is mostly stored in a flash memory or EEPROM.
Firmware usually contains the elementary functions for controlling the device, as well as input and output routines.
Frequency shift keying
Frequency shift keying is a simple form of modulation, where the digital values 0 and 1 modulate the actual current signal by means of two different frequencies.
Frequency Shift Keying (FSK)
→
Frequency shift keying
HART
HART (Highway Addressable Remote Transducer) is a standardized, widely used communications system used to structure industrial fieldbusses. The communications system provides digital communications for multiple participants (field devices) via a common databus. HART is based especially on the equally widely used 4/20 mA standard for the transfer of analog sensor signals. The cabling from existing older systems can be used directly and both systems operated in parallel.
HART specifies several protocol levels in the OSI model. It facilitates the transfer of process and diagnostics data and control signals between field devices and high-level control systems. Standardized parameter sets can be used for the manufacture-independent operation of all HART devices.
Typical applications include transmitters for measuring mechanical and electrical dimensions.
MAWP (PS)
Maximum Allowable Working Preassure (PS)
Non-volatile memory
→
EEPROM
Risk
Combination of the probability of damage occurring and the extent of the damage.
70
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Glossary
Safety function
Defined function executed by a safety-instrumented system with the objective of attaining or maintaining a safe system state by taking a defined hazardous incident into account.
Example:
Limit pressure monitoring
Safety Integrity Level
→
SIL
Safety-instrumented system
A safety-instrumented system (SIS) executes the safety functions that are required to achieve or maintain a safe state in a system. It consists of a sensor, logic unit/control system and final controlling element.
Example:
A safety-instrumented system is made up of a pressure transmitter, a limit signal sensor and a control valve.
Sensor
Converter that converts mechanical or other non-electric variables into electrical signals.
SIL
The international standard IEC 61508 defines four discrete safety integrity levels (SIL) from
SIL 1 to SIL 4. Each level corresponds to a probability range for the failure of a safety function. The higher the SIL of the safety-instrumented system, the higher the probability that the required safety function will work.
The SIL which can be achieved is determined by the following safety-instrumented characteristics:
● Average probability of failure on demand (PFD
AVG
)
● Hardware fault tolerance (HFT)
● Safe failure fraction (SFF)
srli2
→ srlin2
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
71
Glossary
srlin2
«srli2» or «srlin2» is a type of square root extracting characteristic curve for the output current.
This characteristic curve type is proportional to the flow rate, linear in two levels up to the application point and has a pre-defined application point of 10%.
«srli2» or «srlin2» are synonymous and technically there is no difference between them. The abbreviation «srli2» is used in sections that refer to the on-site operation of the pressure transmitter. The reason for the abbreviation is that the pressure transmitter display is restricted to five characters. The abbreviation «srlin2» is used for HART operation.
72
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
Index
A
Additional Support, 66
Approval plate,
C
Certificate, 65
Certificates, 15
Certification, 65
Correct usage,
Customer Support Hotline, 65
D
Device
Electrostatic-sensitive, 32
E
Electrostatic-sensitive device (ESD), 32
F
Firmware, 7
H
Hazardous area
Laws and directives, 15
History, 7
Hotline, 65
I
Improper device modifications, 15
Internet, 65
N
Nameplate, 20
Nameplate with general information, 20
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
P
Process connection, 20
Q
Qualified personnel, 16
R
Remote seal
Maintenance, 52
S
Scope of delivery, 8
Service, 65
Structure, 19
Support, 65
T
Test certificates, 15
73
3.0
Rated 3 out of 5
3 out of 5 stars (based on 1 review)
Your overall rating
SIEMENS SITRANS P DS III (01) PDF MANUAL
Click here to download SIEMENS SITRANS P DS III (01) PDF MANUAL
SIEMENS SITRANS P DS III (01) PDF MANUAL
FREE ENGLISH PDF
OPERATING INSTRUCTIONS
USER GUIDE – USER MANUAL
OWNER GUIDE – OWNER MANUAL
REFERENCE GUIDE – REFERENCE MANUAL
INSTRUCTION GUIDE – INSTRUCTION MANUAL
Your overall rating
SIEMENS SITRANS P DS III (01) PDF MANUAL
SIEMENS SITRANS P DS III (01) PDF MANUAL