4033452 / 8

BC3250

Blowdown Controller

Installation and Maintenance Instructions

BC3250

100

50

0

%

SP

PV

AL

OK

IM-P403-89

EMM Issue 8

1.

Safety information

2.

User instructions and

delivery information

3.

System overview

4.

Mechanical installation

5.

Electrical installation

6.

Commissioning

— Quick set-up

— Full

7.

Communications

8.

Maintenance

9.

Fault finding

10. Technical information

— Default settings

11. Appendix

— Summary of the

Modbus protocol

12. Menu map

© Copyright 2017

Printed in GB

Commissioning password

Current legislation states that in order to prevent tampering and potentially

hazardous programming errors, access to the pass codes required to enter

commissioning mode should only be available to qualified and trained personnel.

Enter commissioning

This is done from the run mode by pressing and holding down the

The bar graphs will disappear and the display will show ‘PASS

PASS

CODE’ with ‘8888’ at the bottom right corner of the screen. The

flashing leading digit indicates the position of the cursor. The

CODE

default, or factory set pass code is 7452 but this can be changed

from within the commissioning mode. The pass code can be

entered by using the

the flashing value and the

Pressing

will enter the pass code. If an incorrect pass code is

OK

used, the display automatically returns to the run mode.

8888

This page MUST be removed after

commissioning and kept in a safe,

access controlled location.

button for 5 seconds.

OK

and

buttons to increase or decrease

and

buttons to move the cursor.

IM-P405-89 EMM Issue 8

loading

Summary of Contents for Spirax Sarco BC3250

Контроллер продувки котла BC3250 Spirax Sarco

Контроллер продувки котла BC3250 Spirax Sarco

  • Описание

  • ЗАДАЙТЕ ВОПРОС ПРОДАВЦУ

Описание

Устройство BC3250 – это контроллер продувки для парогенераторов. Открывая и закрывая клапан
продувки, контролирует TDS (общее содержание растворенных в растворе солей) в воде. Кроме того,
контролирует дренажный клапан, который удаляет с днища котла растворенные соли.
Функция оборудования – контроль электрической проводимости жидкости вместе с датчиком
проводимости, дренажным клапаном днища или дренажным клапаном конденсата.
Дренажный клапан днища регулируется таймером.
Контроллер может быть установлен на панели, на DIN-рейке или непосредственно на специальной
монтажной раме, питание 99/264 Vca.
Передняя панель снабжена графическим LCD дисплем и клавиатурой из 5 кнопок.
В случаях, когда датчик установлен непосредственно на котле, можно дополнительно использовать
фильтр с целью увеличения эффекта угасания. Данная система поможет избежать слишком частого
срабатывания клапана в случае турбулентности.

ЗАДАЙТЕ ВОПРОС ПРОДАВЦУ

Special functions in run mode

Purge

Manually opens the blowdown valve for the purge time set during commissioning. If the purge

time has been set to zero,· the valve will open for 1 minute.

Using the ‘

‘ or ‘

‘ buttons, select ‘PURGE’.

Pressing the ‘

‘ or ‘

‘ opens the blowdown valve for the purge time or 1 minute.

The display will return to the process variable run menu.

‘BLOWDOWN-PURGE’ or ‘BLOWDOWN-TDS TEST’ will appear on the information line

during this period.

On completion of the purge time, the controller will revert to normal control.

Cleaning

Activates a probe cleaning cycle for the period of time set during commissioning.

Using the ‘

‘ or ‘

‘ buttons, select ‘CLEAN’.

Pressing the ‘

‘ or ‘

‘ to active the cleaning cycle and the blowdown valve will close.

The display will return to the process variable run menu.

‘CLEANING’ will appear on the information line during this period.

On completion of the cleaning time, the controller will revert to normal control after 20

seconds. This is to allow any bubbles to disperse.

CAL

Enables the water treatment engineer / specialist to calibrate the controller from the run

menu. A pass code is not required.

Using the ‘

‘ or ‘

‘ buttons, select ‘CAL’.

Pressing the ‘

‘ or ‘

‘ will access the calibration menu in commission mode. See Section

6.4.6.5 INPUT-TDS-CAL.

On completion or exiting calibration, the display will return to the process variable run

menu and normal control will be resumed.

This page MUST be removed after

commissioning and kept in a safe,

access controlled location.

IM-P405-89 EMM Issue 8

1. Safety information

Safe operation of this product can only be guaranteed if it is properly installed,

commissioned, used and maintained by qualified personnel (see Section 1.11) in

compliance with the operating instructions. General installation and safety instructions

for pipeline and plant construction, as well as the proper use of tools and safety

equipment must also be complied with.

Your attention is drawn to IEE Regulations (BS 7671, EN 12953, EN 12952 and

EN 50156). Elsewhere, other regulations will normally apply.

All wiring materials and methods shall comply with relevant EN and IEC standards

where applicable.

Warning

This product is designed and constructed to withstand the forces encountered during

normal use. Use of the product other than as a boiler controller, or failure to install the

product in accordance with these Instructions, product modifications or repair could:

Cause injury or fatality to personnel.

Cause damage to the product / property.

Invalidate the

marking.

These instructions must be stored in a safe place near the product installation at

all times.

Warning

This product complies with Electromagnetic Compatibility Directive 2014/30/EU and

all its requirements.

This product is suitable for Class A Environments (e.g. industrial). A fully detailed EMC

assessment has been made and has the reference number UK Supply BH BC3250 2008.

The product may be exposed to interference above the limits of Heavy Industrial

Immunity if:

The product or its wiring is located near a radio transmitter.

Excessive electrical noise occurs on the mains supply. Power line protectors

(ac) should be installed if mains supply noise is likely. Protectors can combine

filtering, suppression, surge and spike arrestors.

Cellular telephones and mobile radios may cause interference if used within

approximately 1 metre (39″) of the product or its wiring. The actual separation

distance necessary will vary according to the surroundings of the installation

and the power of the transmitter.

This product complies with Low Voltage Directive 2014/35/EU by meeting the

standards of:

EN 61010-1:2010 Safety requirements for electrical equipment for measurement,

control, and laboratory use.

Static precautions (ESD)

Static precautions must be observed at all times to avoid damage to the product.

2

IM-P405-89 EMM Issue 8

Table of Contents for Spirax Sarco BC3250:

  • IM-P403-89 EMM Issue 8 59 10. Technical information 10.1 For technical assistance Contact your local Spirax Sarco representative. Details can be found on order / delivery documentation or on our web site: www.spiraxsarco.com 10.2 Returning faulty equipment Please return all items to your local Spirax Sarco representative. Please ensure all items are suitably packed for transit (preferably in the original cartons). Please provide the following information with any equipment being returned: 1. Your name, company n

  • IM-P403-89 EMM Issue 8 24 Note: Before installing observe the ‘Safety Information’ in Section 1. Warning: Isolate the mains supply before touching any of the wiring terminals as these may be wired to hazardous voltages. Use only the connectors supplied with the product, or spares obtained from Spirax Sarco Ltd. Use of different connectors may compromise product safety and approvals. Connecting the mains supply incorrectly can cause damage and may compromise safety. 5.1 General wiring notes: Every effort has been made du

  • IM-P403-89 EMM Issue 8 67 10.8.4 OUTPUT MENU CLEAN — DRIVE (Action on blowdown / solenoid valve) Ranges STANDARD or PULSED — 10 sec open, 20 sec closed Default STANDARD CLEAN — DURATION (Time to clean probe) Ranges 0 – 99 seconds or 0 – 9 seconds (If purge time > 0) Default 20 (9 seconds (If purge time > 0)) Resolution (steps) 1 Units Seconds CLEAN — INTERVAL (Time between probe cleaning) Only available if CLEAN — DURATION is greater than 0 seconds. Ranges 1 – 99 Default 12 Resolution (steps) 1 U

  • IM-P403-89 EMM Issue 8 7 2.3 Using the buttons The and buttons are used to: — scroll up and down through the menus. The and buttons are used to move between the Bar graph and the Trend graph. The OK button is used to clear errors or alarms. OK BC3250 100 50 0 % SP PV AL Fig. 1 Front panel keypad and definitions. Graphic display Clears any errors or alarms (Press and hold for 5 seconds) 2.2 Front panel The front panel has an LCD graphics display and five- button keypad: Horizontal arrows are used to toggle between the Bar graph and the Trend

  • IM-P403-89 EMM Issue 8 39 6.4 Commissioning — Full Sub-menus and their functions are outlined within this section, and enables the user to programme the unit. Additional information is given in the sub-menu notes where further choices can be made. Allows the user to view and change the valve status (OPEN or CLOSED). See MODE sub-menu. Allows displayed units to be configured. S

  • IM-P403-89 EMM Issue 8 58 Error message Cause Action 5 VALVE FAILED TO CLOSE Blowdown valve fails to close fully 1. Check the correct closing time has been entered in the INPUT — CLOSING menu. 2. See VALVE FAILED TO OPEN. 3. Enter the commissioning mode and enter the correct passcode.* 4. Press OK to Clear. 6 PROBE SCALED (CP32 Only) The probe drive has increased to the maximum voltage. 1. The probe tip may be scaled. Ensure the correct water treatment is be used. 2. Ensure the boiler water is not been contaminated. 3. Che

  • IM-P403-89 EMM Issue 8 9 PV AL PV Fig. 3 PV (conductivity) bar graph definitions Fig. 4 SP and alarm bar graph definitions Highest process variable reached This can be reset by entering the commissioning mode. Lowest process variable This can be reset by entering the commissioning mode. Current process variable Graphical representation of the process variable in terms of percentage of full scale. High alarm

  • IM-P403-89 EMM Issue 8 27 5.3 Blowdown valve wiring notes: Note: The protective earth must be connected in accordance with National or Local regulations Solenoid valve (BCV1, BCV20 or BCV31) 1 2 3 4 5 6 7 8 9 10 11 Alarm 1 relay Control relay L N 3 A Fuse L 1 A Fuse N Alarm Norm Input 3 A Fuse BACK FRONT Open Input 3 A Fuse N Fig. 18 BCV30 230 / 115 Vac blowdownvalve Caution live terminal AC supply Burner supply Fig. 19 BCV1, BCV20 or BCV31 solenoid valves See Section 5.2 Mains wiring notes Link Link BCV

  • IM-P403-89 EMM Issue 8 72 OUTPUT – VALVE (Opens or closes blowdown valve manually) Ranges ON or OFF Default ON Press the OK button to activate relay – Automatic control of relays is selected by selecting cancel or after 5 minutes has elapses. OUTPUT – BB VALVE (Opens or closes bottom blowdown valve manually) Only available if TIMER – DURATION is > 0. Ranges ON or OFF Default ON Press the OK button to activate the relay – Automatic control of relays is selected by selecting cancel or after 5 minutes has elapses. OUTPUT –

  • IM-P403-89 EMM Issue 8 62 10.6 Input technical data Water conductivity Probes type: CP10, CP30 and CP32 Ranges Minimum ≥ 1 µS @ 25 °C 0 – 9.99 ppm or µS / cm 0 – 99.9 ppm or µS / cm 0 – 999 ppm or µS / cm 0 – 9990 ppm or µS / cm Accuracy ±2.5% FSD (Poss > if high EMC) ±5% FSD for 0 — 9.999 range pH factor 0.50 – 1.00 (0.7 default) Neutralising factor 0.7 Resolution 0.1% FSD Drive ac – 4

  • IM-P403-89 EMM Issue 8 42 6.4.6 INPUT sub menu notes 6.4.6.1 INPUT – TDS – SENSOR – FLT MODE Only shown if the CP32 probe is selected. Allows selection of the action to be taken if the probe detects a fault. ‘OFF’ No action. ‘CLEAN’ If the probe is scaled then the time between probe conditioning cycles will change from the CLEAN-INTERVAL time set to 10 minutes, until the probe is clean. The display will flash

  • IM-P403-89 EMM Issue 8 55 9. Fault finding WARNING: Before fault finding read the Safety information in Section 1 and the General wiring notes in Section 5.1. Please note that there are hazardous voltages present and only suitably qualified personnel should carry out fault finding. The product must be isolated from the mains supply before touching any of the wiring terminals. Safety may be compromised if the fault finding procedures are not c

  • OK BC3250 100 50 0 % SP PV AL 1. Safety information 2. User instructions and delivery information 3. System overview 4. Mechanical installation 5. Electrical installation 6. Commissioning — Quick set-up — Full 7. Communications 8. Maintenance 9. Fault nding 10. Technical information — Default settings 11. Appendix — Summary of the Modbus protocol 12. Menu map IM-P405-89 EMM Issue 8 Commissioning password Current legislation states that in order to prevent tampering and potentially hazardou

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of Spirax Sarco BC3250 device using right now.

Понравилась статья? Поделить с друзьями:
  • Spheros thermo 300 инструкция на русском
  • Srnubi магнитола t10 инструкция на русском
  • Sph 10bt инструкция по эксплуатации pioneer
  • Srnubi android 11 инструкция на русском языке
  • Spg 2700 инструкция по применению